EMS FireCell FCX-174-001 Installation Manual

Combined sounder/detector/visual indicator

Advertisement

Quick Links

Combined Sounder/Detector/Visual Indicator
Installation Guide
1 Pre installation
!
Installation must conform to applicable local installation codes and should only be installed by a fully
trained competent person.
Ensure that the device is installed as per the site survey.
The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
Do NOT press the log on button on a pre-programmed device, as this will cause communication with the control
panel to be lost. Should this happen, delete the device from the system and add it back on.
This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take
appropriate precautions when handling electronic boards.
For pre-2024 versions of this device with a 4-way power/sounder configuration switch, refer to the legacy version
of this manual.
2 Components
1
1
Dust cover,
2
Detector,
4
Mounting plate
©2025 EMS Ltd. All rights reserved.
Example shown:
FCX-177-001
FCX-191-000
2
3
4
3
Wireless module,
Part no
Description
FCX-174-001
Multisensor Smoke Detector Only
FCX-175-001
Heat A1R Detector Only
FCX-176-001
Heat CS Detector Only
FCX-177-001
Optical Smoke Detector Only
FCX-191-000
Sounder/Detector Base Only
FCX-191-200
Sounder/Detector/Red Visual Indicator Base Only
See the Specification section for compliance information.
3 Fix mounting plate
Remove the mounting plate by turning the device
ANTICLOCKWISE, to release it from the mounting plate.
Use both fixing positions to ensure a firm fixing.
Use suitable fasteners and fixings.
Page 1 of 4
63mm
TSD001-99 (Issue 25) 06/01/2025 AJM
CPR
[1]
[2]
[2]
[3]
[4]
[4]

Advertisement

loading
Need help?

Need help?

Do you have a question about the FireCell FCX-174-001 and is the answer not in the manual?

Questions and answers

Summary of Contents for EMS FireCell FCX-174-001

  • Page 1 ANTICLOCKWISE, to release it from the mounting plate. • Use both fixing positions to ensure a firm fixing. • Use suitable fasteners and fixings. 63mm Dust cover, Detector, Wireless module, Mounting plate ©2025 EMS Ltd. All rights reserved. Page 1 of 4 TSD001-99 (Issue 25) 06/01/2025 AJM...
  • Page 2 • Refer to the programming manual for full programming details. FireCell = MK98 Fusion = TSD062 WZM = TSD143 Free to download from www.emsgroup.co.uk ©2025 EMS Ltd. All rights reserved. Page 2 of 4 TSD001-99 (Issue 25) 06/01/2025 AJM...
  • Page 3 800Hz - 970Hz at 100Hz 800Hz - 970Hz at 9Hz 800Hz - 970Hz at 3Hz 800Hz, 0.25s ON / 1s OFF 500Hz - 1200Hz, 3.75s / 0.25s OFF (AS2220) ©2025 EMS Ltd. All rights reserved. Page 3 of 4 TSD001-99 (Issue 25) 06/01/2025 AJM...