Combined Sounder/Detector/Visual Indicator
Installation Guide
1 Pre installation
!
Installation must conform to applicable local installation codes and should only be installed by a fully
trained competent person.
•
Ensure that the device is installed as per the site survey.
•
The use of a non-metallic spacer should be considered if mounting the device on to a metal surface.
•
Do NOT press the log on button on a pre-programmed device, as this will cause communication with the control
panel to be lost. Should this happen, delete the device from the system and add it back on.
•
This device contains electronics that may be susceptible to damage from Electrostatic Discharge (ESD). Take
appropriate precautions when handling electronic boards.
•
For pre-2024 versions of this device with a 4-way power/sounder configuration switch, refer to the legacy version
of this manual.
2 Components
1
1
Dust cover,
2
Detector,
4
Mounting plate
©2025 EMS Ltd. All rights reserved.
Example shown:
FCX-177-001
FCX-191-000
2
3
4
3
Wireless module,
Part no
Description
FCX-174-001
Multisensor Smoke Detector Only
FCX-175-001
Heat A1R Detector Only
FCX-176-001
Heat CS Detector Only
FCX-177-001
Optical Smoke Detector Only
FCX-191-000
Sounder/Detector Base Only
FCX-191-200
Sounder/Detector/Red Visual Indicator Base Only
See the Specification section for compliance information.
3 Fix mounting plate
Remove the mounting plate by turning the device
ANTICLOCKWISE, to release it from the mounting plate.
•
Use both fixing positions to ensure a firm fixing.
•
Use suitable fasteners and fixings.
Page 1 of 4
63mm
TSD001-99 (Issue 25) 06/01/2025 AJM
CPR
[1]
[2]
[2]
[3]
[4]
[4]