Your Smart Energy Copyright Statement Copyright Statement This manual is copyrighted by Alpha ESS Co., Ltd., and all rights are reserved. Without the written permission of our company, no organization or individual may extract or copy part or all of the content of this document without authorization, and may not disseminate it in any form.
Notice Notice The products, services, or features you purchase are subject to the AlphaESS commercial contract and terms, and some of the products, services, or features described in this document may not be within the scope of your purchase or use.
Preface Preface The STORION-G2-H30/H50-O energy storage system has been developed by AlphaESS over many years and has been successfully applied in many fields. It is a high-tech product with excellent quality and stable performance that meets today's power supply needs.
Your Smart Energy Terminology Terminology 1. Battery Management System (BMS) Monitors the operational information of battery cells, battery packs, and system units (such as voltage, current, temperature, and battery protection parameters), and intelligently assesses the state of charge (SOC), state of health (SOH), and total energy output to ensure battery safety.
Page 6
Your Smart Energy Terminology On-grid systems typically consist of PV strings, PCSs such as G2-H30/H50 inverters, battery systems, and the power grid. When the electricity generated by the PV strings is sufficient, the excessive electricity can be fed into the grid. When the electricity generated by the PV strings and battery system is insufficient, the grid can supply power to the load.
Version Information Version Information Version Date Content 2024.10.17 ______________________________________________________________ Alpha ESS Co., Ltd. Page 7 of 74...
Page 10
Contents 4.4.1 Safety Precautions ..........................57 4.4.2 Communication Connection Between System Cabinet and PCS ........57 4.4.3 Battery Power Cable Connection ....................58 4.4.4 Communication Connection between Expansion Cabinet and System Cabinet (Optional) ............................... 58 4.4.5 Expansion Cabinet Battery Power Line Connection (Optional) ..........59 4.4.6 AC Load Cabling ............................60 4.4.7 AC Power Grid Cabling and Electricity Meter ................61 4.4.7.1 AC Power Grid Cabling ....................
Introduction 1. Introduction 1.1 System Introduction STORION-G2-H30/H50-O is equipped with a 30kW/50kW PCS, paired with M7790-S or M38210-SC batteries, and can be optionally configured with an ATS cabinet for a dual power supply switching system. The total capacity range of STORION-G2-H30/H50-O is from 34.56kWh to 104.83kWh.
When a system malfunctions during normal operation, please refer to the troubleshooting table to diagnose the problem. If the problem persists, contact an AlphaESS engineer in a timely manner. Before the AlphaESS engineer responds, be sure to shut down the system (including the batteries and PCSs).
Introduction instructions in this manual. AlphaESS does not assume any responsibility for violating general safety operation requirements or product safety standards for design, production, and use. Any consequential damage caused to the product will not be covered by the warranty.
Introduction The installation tools are listed in the following table. Quantity Number Name Model specifications Unit Diagonal pliers Screwdriver 2/4/6/8mm Cable tie Multimeter DC 1000V Impact drill Socket wrench Socket wrench set Open end wrench Open end wrench set Socket torque wrench / PV cable connector tool The protective equipment is listed in the following table.
Introduction 3.Avoid unnecessary contact with the circuit board to prevent damage to it or other static-sensitive components caused by contact or improper operation. During maintenance, all products must be powered off and maintained strictly in accordance with the relevant requirements of this manual. 1.4 Electrical Safety 1.4.1 Grounding Requirements 1.When you install the product, install the protective ground wire first.
Introduction 1.5 Transportation Requirements When moving large products without dismantling the transportation packaging boxes, use a forklift to lift items such as the PCS or battery rack from the bottom, as shown in the following schematic diagram: When handling batteries, to prevent dropping due to their weight, it is recommended that two to four people carry them.
2. Product Introduction 2.1 Product Features The lithium iron phosphate battery produced by AlphaESS features long life and high reliability, meeting the application demands of various energy storage systems. The system is designed with a high degree of modularity, making it easy to assemble, transport, and maintain.
Page 18
Product Introduction *The above image is for reference only. For more information, refer to the actual product received. The product appearance is described in the following table: View Description ______________________________________________________________ Alpha ESS Co., Ltd. Page 18 of 74...
Product Introduction Front view 1. Air conditioner 2. Indicator lights 3. EPO 4. SCADA screen 5. PCS 6. Door lock 7. Bottom protective plate *The above image is for reference only. For more information, refer to the actual product received. 2.2.2 Indicator Lights There are three indicator lights installed on the SCADA screen to display the main operating status of the system: the power indicator light "POWER", the running...
Product Introduction always off when the system is in standby mode or powered off. Always on when a fault occurs during system operation, and FAULT always off during normal operation. The status and descriptions of the LED indicator lights are listed in the following table. Name Description POWER on, RUN on, FAULT off...
Product Introduction Machine Type ALPBC-105-O ALPBEC-105-O (With PCS) W (mm) 1200 1200+300 H (mm) 2160 2160 D (mm) 2.2.4 Outdoor Cabinet Interior Design (Using M38210-SC as an Example) The system adopts an all-in-one design that combines the PCS module with the energy storage battery system into a single unit.
Page 22
Product Introduction Front view 1. HV-BOX 2. PCS 3. Combiner BOX 4. EMS4.2 5. Wiring terminals and circuit breakers 6. Battery Back view 1. Main negative copper busbar 2. Series copper busbar Series copper busbar (bridging) ______________________________________________________________ Alpha ESS Co., Ltd. Page 22 of 74...
Product Introduction 2.2.5 Equipment Operation Switch Locations The STORION-G2-H30/H50-O cabinet system includes relevant operation switches, high-voltage box auxiliary source switches, and high-voltage box molded-case switches. The operating positions of each switch in the system are shown in the following figure: The functions of each switch in the system are described in the following table.
Product Introduction System cabinet Powers on the auxiliary source of the control auxiliary power switch system. 2.2.6 Cable Entry Design To facilitate cable connection on site, all cables between equipment inside the system cabinet have been connected before delivery. The communication cable connecting the system cabinet and external devices can enter the interior through the cable entrance on the bottom right side of the system cabinet.
Product Component Description 3. Product Component Description 3.1 M38210-SC The battery schematic diagram is shown below: The appearance is described in the following table. Number Description Number Description Battery negative terminal Box body Battery positive terminal BLMU Mounting hole Battery handle The technical parameters of the battery are described in the following table.
Product Component Description Numbe Description Technical parameter Remarks Model M38210-SC Cell grouping method 12S2P Rated voltage 38.4V Voltage range 36-43.2V Maximum Rated capacity 210Ah charging/discharging current 0.5C Rated energy 8.1kWh Working power consumption < 2W Sleep power consumption < 100 mW Battery sleep state Maximum 105A...
Page 28
Product Component Description The appearance of the battery is described in the following table. Number Description Number Description Battery negative terminal Box body Battery positive terminal BLMU Mounting hole x4 Battery handle ______________________________________________________________ Alpha ESS Co., Ltd. Page 28 of 74...
Product Component Description The technical parameters of the battery are described in the following table. Number Description Technical parameter Remarks Model M7790-S Cell grouping method 24S1P Rated voltage 76.8 V Voltage range 72~84.48V Maximum Rated capacity 90 Ah charging/discharging current 1C Rated energy 6.9 kWh Working power consumption...
Page 30
Product Component Description The appearance of the high-voltage box is described in the following table. Number Description Number Description AC auxiliary power switch Battery Positive input AC auxiliary power interface Battery Negative input BCMU communication port (CAN) HV-BOX Positive Output AC auxiliary power interface Molded case circuit breaker BCMU communication port (CAN)
Product Component Description Working voltage range 200~900V Module Connection Support series connection of 8-12 M38210-SC batteries; Support series connection of 5-8 M7790-S batteries Rated current 105 A Weight 20 kg Power dissipation < 10W Color RAL7035 3.4 EMS 4.2, SCADA, and Ports The three views of the SCADA are shown below: ______________________________________________________________ Alpha ESS Co., Ltd.
Page 32
Product Component Description The ports are described in the following table: Number Port Name Definition Remarks EMS4.2 External normally closed Fire Action External normally open Dual power supply main power External normally open signal Dual power supply backup power External normally open signal External normally open SPD signal (surge protective...
Page 33
Product Component Description device) Limiting the charging power of External normally open energy storage Unrestricted charging power for DI10 External normally open energy storage DI11 RRCR_K1 External normally open DI12 RRCR_K2 External normally open DI13 RRCR_K3 External normally open DI14 RRCR_K4 External normally open DI15...
Page 34
Product Component Description SD 卡 SD card CAN1 PV INV RS485-2 HMI/SCADA_FS Connected to SCADA_FS's RS485-4 COM1. Meter RS485-5 RS485-7 Air conditioning SCADA Display screen INPUT Power input Connected to EMS's LAN1 via a LAN1 switch. COM1 Connected to EMS's RS485. The technical parameters of EMS4.2 and SCADA display screen are described in the following table.
Product Component Description Single machine for 3 years, and 180 days for Data Storage multiple machines. Power consumption < 19W Resolution 1280×800 Working voltage 3.5 G2-H30/H50-INV The appearance of the energy storage inverter G2-H30/H50-INV is shown in the following figure: The appearance is described in the following table: Number Description...
Page 36
Product Component Description Display panel Displays inverter information. Hanger Used for the installation of inverters. DC switch Controls the on and off of the PV input. PV input terminal Connects to PV input Battery input terminal Connects the battery power lines COM1 port Communicates with EMS COM2 port...
Page 37
Product Component Description Maximum charging/discharge 100 A/100A current Grid side Rated output power 30kW 50kW Max. output apparent power 33kVA 55kVA Max. input apparent power* 36kVA 60kVA Max. charging power of batter 30kW 50kW Rated AC voltage 3L/N/PE;220/380V;230/400V;240/415V Rated AC frequency 50/60Hz Max.
Installation 4. Installation 4.1 Installation Location and Environment 4.1.1 General Requirements The environmental requirements for installation are described in the following table. Install Environmental ation conditions for Environmental parameters Remarks enviro transportation nment and storage Project Paramete Unit Storage Transp conditi ℃...
Installation generated inside the product. When the altitude exceeds altitude 3000m and exceeds the maximum limit, it Altitud shall be used in accordance with High 3000 3000 3000 the provisions of altitude 5.11.2 in GB/T3859.2- 1993. For the installation environment conditions of the system, the system Remark performance will be affected when the temperature is below 0 °...
Page 41
Installation When installing the indoor cabinet of STORION-G2-H30/H50, ensure there is sufficient space for ventilation and cooling as well as for installation and maintenance. The specific installation location requirements are illustrated in the following figure: A ≥ 1300 mm: Ensure that the front door of the cabinet can be fully opened, allowing for proper ventilation and heat dissipation, as well as sufficient space for operation and maintenance.
Installation A ≥ 600 mm: Ensure that the PCS has enough space for operation and maintenance. 4.2 STORION-G2-H30/H50-O Outdoor Cabinet Body Fixing Before unpacking, check for obvious signs of damage to the packaging. If there are signs of damage, do not unpack. In this case, verify the system model, and contact the dealer as soon as possible.
Page 43
Installation The parts are described in the following table: M7790-S/M38210-SC battery 33300490(BT-BT) 40100088 1 pc 4 pcs Battery-to-battery Battery securing communication screw. cable M6*14 Length 310mm System accessories 1 pc 4 pc 1 pc 1 pc 33300476 BAT handling hook 33500056 33501119 communication...
Page 44
Installation bridging) 40100211 1pcs Stainless steel 304 2pcs 10pcs hex head bolt with 1pcs Number of base spring washer and M4 * 14 combination PCS grounding cable decorative panels: 1 flat washer screw each combination M10 * 30 Grounding screw 30500039 30300020 1pcs...
Installation Remove all existing or potential obstacles during the movement process, such as trees and cables. It is recommended that you transport and move the STORION-G2- H30/H50-O outdoor cabinet under favorable weather conditions whenever possible. Ensure that warning signs or safety barriers are set up to prevent ...
Installation 4.2.2.3 STORION-G2-H30/H50-O Equipment Installation After you transport the STORION-G2-H30/H50 outdoor cabinet to the installation location with a forklift or other tools, secure its base with M8 screws (provided by the customer). The schematic diagram of the base is shown below: ______________________________________________________________ Alpha ESS Co., Ltd.
Page 48
Installation The wiring holes are located at the bottom of the STORION-G2-H30/H50-O outdoor cabinet, and the cables are passed through these holes into the cable trough. When the STORION-G2-H30/H50-O outdoor cabinet needs to be fixed to the channel steel, Φ9 holes should be drilled in the channel steel, and the cabinet should be secured to the channel steel with screws.
Installation Ensure that the STORION-G2-H30/H50-O outdoor cabinet is reliably grounded. If it is not connected or is loose, this may lead to electric shock. It is recommended that the exterior of the grounding terminal be painted after the grounding wire is installed for protection. 4.2.3 PCS Wall-Mounted Device Installation The installation diagram of wall-mounted equipment is shown below: ______________________________________________________________...
Page 50
Installation The PCS wall-mounted installation parts are described in the following table. Number Explanation PCS wall mounting plate (included in the pcs packaging box) PCS wall mounting plate installation screws ______________________________________________________________ Alpha ESS Co., Ltd. Page 50 of 74...
Installation PCS equipment body The installation steps for PCS wall-mounted devices are described in the following table. Steps Explanation Install the PCS wall mounting plate on the right side of the STORION- G2-H30/H50-O outdoor cabinet using four screws and the PCS wall Step 1 mounting plate.
Page 52
Installation The grounding resistance should be less than 4 ῼ. Step 2 Open the rear door, refer to the diagram for the positive pole position, and install the positive power cable for the battery according to the actual number of batteries. The schematic diagram of the connection between the wire harness and copper bar is shown below: ______________________________________________________________...
Page 53
Installation The wiring harness and copper bar connection configuration are described in the following table: Number Description Power cable (copper lugs) copper busbar ______________________________________________________________ Alpha ESS Co., Ltd. Page 53 of 74...
Page 54
Installation M8 flange nut M8 three-piece screw set Step 3 Refer to the following diagram to unpack the battery: The schematic diagram of screw fixation is shown below: The battery assembly location diagram is shown below: ______________________________________________________________ Alpha ESS Co., Ltd. Page 54 of 74...
Page 55
Installation The steps for unpacking and installing batteries are described in the following table. Step Description Open all the battery packaging, and be careful not to lose any Step 1 internal accessories. Check the battery model on the label and inspect the battery insulation and voltage.
Page 56
Installation According to the configuration differences of different projects, the communication cables between batteries are set up accordingly. The connection sequence and terminal resistor positions are shown in the following figure: Schematic diagram of communication cable connection sequence and terminal resistor positions. Please use the communication cable from the battery parts list to connect the batteries to each other.
Installation 4.4 Electrical Connections 4.4.1 Safety Precautions Throughout the entire process of making electrical connections and during all other operations on equipment such as the energy storage integration system, the following safety precautions must be observed: Disconnect all external connections to the energy storage integration ...
Installation 2. Connect the PCS to the outdoor cabinet communication harness, and use the reserved harness to connect the PCS COM1 port to the TOP BMU Box LAN1 port (at the switch) (already wired). 3. Connect the PCS to the outdoor cabinet dry contact harness, and use the reserved harness to connect the PCS COM2 (COM2:11/COM2:12) to the outdoor cabinet terminal block (XT2:14B/XT2:14D) (already wired).
Installation The communication cables between the expansion cabinet and the system cabinet are shown in the following figure: 3. Thread the smoke and temperature detector cable of the expansion cabinet into the system cabinet through the wire hole in the upper right corner, and connect it to the system cabinet terminal block (XT2:2D/XT2:3D) along the inner cable tray;...
Installation The power wiring of the expansion cabinet and system cabinet is shown in the following figure: 4.4.6 AC Load Cabling 1. Ensure the correct phase sequence on the AC side of the connection. 2. Use a multimeter to measure and ensure there is no voltage on the cables connected to the copper busbar.
Installation Pass the AC cable bundle through the center hole of the connector, and then continue to install it on the PCS side. The schematic diagram of the AC load connection is shown below: 4.4.7 AC Power Grid Cabling and Electricity Meter 4.4.7.1 AC Power Grid Cabling 1.
Install a circuit breaker between the power grid and the PCS. Please note that AlphaESS does not provide this circuit breaker. If a circuit breaker is installed, there is no need for a leakage protector between the power grid and the PCS.
Installation 4. The L3 phase of the power grid is threaded through the P1 side of the meter's CT and exits through the P2 side, connecting to the L3 phase of the grid side of the energy storage inverter. The secondary side port S1 of the meter's CT is connected to port 37 of the meter, and the secondary side port S2 is connected to port 39 of the meter.
Installation The positive direction corresponding to the positive value of the energy storage meter data is defaulted as shown in the preceding figure. The meters installed by STORION-G2-H30/H50-O include grid gateway meters, PV grid connection point meters, and diesel electromechanical meters. 4.4.7.4 Electricity Meter Settings The steps to set the communication address or baud rate of the electricity meter are as follows:...
Installation According to this step, the baud rate can be checked and the communication address can be set. The corresponding communication addresses and baud rates for each meter are as follows: Utility Meter Address PV Meter Address DG Meter Address Electricity Meter 9600 Communication Baud Rate...
Installation 4.4.8.2 Communication Line Connection Perform dry node communication between the ATS cabinet and the system cabinet, connect the (X1:1/X1:2/X1:3/X1:4) ports of the ATS cabinet to the terminal block of system cabinet (XT2:4B/XT2:4D/XT2:5B/XT2:5D). The connections are described in the following table. STORION-G2-H30/H50 Outdoor ATS Cabinet Cabinet...
Installation The dry contact voltage is 24V. It is recommended to use a 2-core shielded twisted pair cable with a cross-sectional area of 0.75m² or more. 4.4.9 Off-Grid Diesel Dry Contact Connection Diesel generator dry contact wiring, please connect the diesel generator dry contact (NO/COM) to the system cabinet (XT2:13B/XT2:13D), as shown in the following schematic diagram: After the wiring is completed, plug the entry hole with fireproof mud or other...
Installation The system cabinet auxiliary source wiring requires the customer to connect the AC auxiliary source wire to the system cabinet terminal block (XT1:1B/XT1:2B) for connection, as shown in the following schematic diagram. 4.4.11 System Parallel Connection Cabling 4.4.11.1 Grid-side Connection (Load Connected to the GRID Side) 1.
Installation 4.4.11.2 Communication Cable Connection 1. Connect the host SCADA to the slave SCADA using an Ethernet cable, with the connection made at the switch of the SCADA system. 2. Connect the auxiliary power sources to the system, respectively. 3. The electricity meter communication is connected only to the main system. ______________________________________________________________ Alpha ESS Co., Ltd.
Startup and Operation 5. Startup and Operation After the system wiring is completed, perform the following steps before proceeding with the operation: 1. Measure the input voltage of the high-voltage box with a multimeter. The voltage range is detailed in the system normal voltage range table at the end of the document.
Technical Contact 6. Technical Contact If you have any technical issues with our products, please contact us. The contact information can be found on the front page of this manual. To help us quickly resolve your issue, please provide the following information: A.
4.8 bolt, white zinc 1pcs fixation plated Please follow the recommended torque values in the table. If there are any special or abnormal situations, please provide your feedback to an AlphaESS engineer. ______________________________________________________________ Alpha ESS Co., Ltd. Page 73 of 74...
Attachment System Normal Voltage Range Table Number of Batteries M7790-S M38210-SC 360~422.4V 432~506.88V 504~591.36V 576~675.84V 288~345.6V 324~388.8V 360~432V 396~475.2V 432~518.4V ______________________________________________________________ Alpha ESS Co., Ltd. Page 74 of 74...