Viking VSF303H Technical Manual
Viking VSF303H Technical Manual

Viking VSF303H Technical Manual

Multi-spectrum ir h2 flame detector

Advertisement

Quick Links

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VSF303H and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Viking VSF303H

  • Page 2 Rev: 3.0 Viking Corporation 5150 Beltway Dr. SE Caledonia MI 49316 Form No. F_111722 Rev 3.0 Ref: 3304.0001 Rev:0.1 ECN:4709 This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 3: Table Of Contents

    Detection Coverage ......................18 Exposure to Flare Radiation ..................... 18 Optical Contamination ...................... 19 Enclosed Areas ........................ 19 Detector Sensitivity ......................19 This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 4 Appendix B - Field of View ....................30 Appendix C - FM Approval Performance Report ..............31 Appendix D - IEC 61508 Failure Rate Data ................33 This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 5: Introduction

    The VSF303H has been designed for use in standalone operation. Detector Features • The VSF303H has a 90° cone of vision with a range of 131 ft (40 m) to a 36 inch (0.9 m) plume of burning hydrogen. •...
  • Page 6: Safety Instructions

    For European (ATEX) installations IEC/EN60079-14 ‘Electrical Installations in Hazardous Areas’ and ICE/EN60079-17 ‘Inspection and Maintenance in Hazardous Areas’ should be strictly observed. The IR3 type flame detector; Viking VSF303H, is to be installed in places where there is a low risk of mechanical damage.
  • Page 7: Important Safety Notices

    • mount the detector on a side wall approximately 3 to 6 ft (1 to 2 m) below the ceiling. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 8 The VSF303H is not designed to annunciate diagnostic failure of signal returns via external • wiring. Control systems and fire panels generally have fault monitoring for such an eventuality. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 9: 54-Part 10 Limitation Of Use

    The mounting bracket allows the detector’s vertical orientation to be adjusted from 0 to 45° and allows a horizontal rotation of +/-45° when mounted from above. Figure 1: Detector Mounting Bracket This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 10 When mounting on a wall in this orientation allow for the cable gland and cable as this may restrict the downward rotation of the detector. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 11: Wiring Procedure

    0-20mA (source non-isolated) • Relay (Alarm & Fault) Listed below are wiring options dependent on the functional requirements of the detector. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 12: 0-20Ma Output

    Note 4 – The 0-20mA signal has HART ® 7 protocol superimposed on top of it to give access to more diagnostic information. See HART ® 7 Technical Note. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 13: Relay Output

    See Figure 7 for field connections of Alarm/EOL resistors or jumper wires. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 14: Internal Inter-Connections

    The following diagram shows the internal inter-connections of the alarm and fault relay contacts and jumpers. Each field connection is listed on this diagram for clarity. Figure 7: VSF303H Internal Inter-connections VSF303H VSF303H VSF303H This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 15: Installation Checklist

    11 to 15 lb. ft (15 to 20 N m). Note – The IP seal washer only applies to metric threads. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 16: Electrical

    The enclosures external earth stud should be connected to a local earth point. Remove the transit plug(s) from the enclosure body gland entries. Fit approved cable glands. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 17: System Design Guidelines

    Cross Sectional Area (mm American Wire Gauge Typical Conductor Resistance (AWG) per km (3280 ft.) DC Ω/km @ 20°C (Approx.) This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 18: Application Guidelines

    The detector shall not have a direct view of the flare or a reflected view of the flare. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 19: Optical Contamination

    Factory Mutual to FM3260. The 20mA alarm signal if delayed is considered an Aux alarm level. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 20: Maintenance And Commissioning

    It is advisable to regularly review maintenance reports and adapt the maintenance period to the operating environment. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 21 De-isolate the detector and ensure the status LED indicates green. Reinstate the detector back into service. Check the mA output is indicating 4mA. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 22: Functional Testing

    Viking technical support. Please ensure that the flame detector and flame simulator are being used correctly in the first instance by referring to their manuals. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 23: Fault Finding

    3. Work systematically through the problem. 4. Keep good notes on the original problem, each step taken, and the results observed. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 24: Led Indication

    The VSF303H is set to standard sensitivity (100 ft (30 m)) Four yellow flashes at start-up The VSF303H is set to high sensitivity (131 ft (40 m)) This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 25: Power Fault

    (18V to 32V) under full load conditions as the voltages measured under no load conditions can be misleading. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 26: Technical Specification

    -58 / -50 +185 / +85 USA & Canada Storage Ambient Temperature -76 / -60 +185 / +85 Relative Humidity Non-condensing This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 27: Certification And Approvals

    0(4)-20mA, HART® 7, Relay contacts - alarm and fault Relay Rating 2 Relay Contacts – Alarm and Fault. SPST, 2A @ 30Vdc Communication/ Configuration RS485 and HART® 7 This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 28: Vsf303H Detector Ordering Information

    USB HART Modem 24592 Air Shield – Aluminium, Red 25518 Adaptor - Duct Mount Window Bracket – Sapphire 26299 Window This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 29: Appendix A - Acronyms, Terms & Abbreviations

    Personal Computer (IBM PC Compatible) R or Ω Ohms (electrical resistance) Safe Failure Fraction Safety Integrity Level Voltage Versus Watts (Wattage) This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 30: Appendix B - Field Of View

    Vertical Field of view to a 36 inch (0.9 m) Hydrogen plume fire with an alarm response at high sensitivity. 100%= 131 feet (40 metres) This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 31: Appendix C - Fm Approval Performance Report

    No Alarm 13 ft (4 m) 3000W electric heater modulated No Alarm 13 ft (4 m) No Alarm 13 ft (4 m) This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 32 13 ft (4 m) 67 ft (20 m) Alarm 3000W electric heater modulated 13 ft (4 m) 67 ft (20 m) Alarm This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.
  • Page 33: Appendix D - Iec 61508 Failure Rate Data

    Remove the bypass and otherwise restore normal operation. Personnel carrying out commissioning, testing and maintenance on this device shall be sufficiently competent and experienced to do so. This document is strictly private and confidential, reproduction without Viking Corporation approval is prohibited. © 2022 The Viking Group Inc.