Single-ended reflected type projected beam smoke detector

Advertisement

Quick Links

INSTALLATION AND MAINTENANCE INSTRUCTIONS
FSB-200A, FSB-200SA
Single-ended Reflected Type Projected
Beam Smoke Detector
SPECIFICATIONS
GENERAL
Range:
Sensitivity:
Spacing:
Response Time:
Trouble Conditions:
Test/Reset Features:
Indicators:
Style 7 Operation:
ENVIRONMENTAL
Temperature:
Humidity:
MECHANICAL
Shipping Weight:
Shipping Size:
Mounting:
Wiring:
Adjustment Angle:
Paintable Trim Ring:
Electrical
Voltage:
Standby Current:
External Supply: (FSB-200SA only):
Remote Output: (alarm)
GENERAL DESCRIPTION
Model FSB-200A/FSB-200SA is a long range projected beam smoke detector
designed to provide open area protection. It is to be used with ULC-listed com-
patible control panels only. The detector consists of a transmitter/receiver unit
and a reflector. Smoke entering the area between the transmitter/receiver and
reflector causes a reduction in signal. When the obscuration reaches alarm
thresholds (chosen at the transmitter/receiver unit), the detector generates
an alarm signal. Complete blockage of the beam causes a trouble signal. Slow
changes in obscuration due to a build up of dirt or dust on the lens of the
detector are compensated for by a microcontroller that continuously monitors
the signal strength and periodically updates the alarm and trouble thresholds.
N200-26-00
16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK
25% to 50% Total Obscuration in 6 levels
Level 1 = 25%
Level 2 = 30%
Level 3 = 40%
Level 4 = 50%
Level 5 = 30% to 50% (Acclimate)
Level 6 = 40% to 50% (Acclimate)
30 to 60 Feet (9.1 to 18.3m)
ALARM - 20 seconds typical; TROUBLE - 30 seconds typical
Beam Blockage (96% or More Obscuration)
Improper Initial Alignment
Self-compensation limit reached (service needed)
In Alignment mode
Integral Sensitivity Test Filter (FSB-200SA only, requires additional external power supply)
Sensitivity Filter (Incremental scale on reflector)
Local Alarm Test Switch
Local Alarm Reset Switch
Remote Test and Reset Switch Capability
ALARM - Remote Output, Local LED (red)
TROUBLE - Remote Output, Local LED (yellow) Blink Pattern Indicates Trouble Diagnostics
NORMAL OPERATION - Local LED (flashing green with communication)
ALIGNMENT AIDS - Optical Gunsight (coarse adjustment) 00 to 99 Digital Display (fine adjustment)
SENSITIVITY - Digital Display Readout in Percent Obscuration
On-board isolators provide style 7 operation. (may be disabled via shunts on circuit board)
–22°F to 131°F (–30°C to 55°C); NOTE: for applications below 32°F (0°C) see Special Applications section of this manual.
10% to 93% RH Noncondensing
3.9 lbs. (1.77 kg)
15˝ × 10.5˝ × 6.5˝ (381mm × 267mm × 165mm)
Wall only without optional accessories
Plug-in Terminal Blocks (12 to 22AWG)
±10° Horizontal and Vertical
May be painted using enamel or acrylic type paints
15 to 32 VDC
Avg. Standby:
Max. Alarm (LED on):
Max. Trouble (LED on):
Max. Alignment:
VOLTAGE - 15 to 32 VDC
CURRENT -0.5A Max.
VOLTAGE - 15 to 32 VDC; NOTE: Output voltage same as device input voltage.
CURRENT - 15mA maximum; 6mA minimum; NOTE: Output current is limited by 2.2Kohm resistor
2mA Max. (1 communication every 5 sec., LED flashing, SLC @ 24 V)
8.5mA Max.
4.5mA Max.
20mA Max.
When the self-compensation circuit reaches its limit, the detector generates a
trouble signal, indicating the need for service.
Three LEDs on the detector indicate the current status: a red LED for alarm, a
yellow LED for trouble, and a blinking green LED for standby operation. Note:
The panel controls the status of the red and green LEDs. The local reset but-
ton is accessible by removing the outer paintable trim ring. The yellow LED
will blink in specific patterns to provide a diagnostic aid when diagnosing the
cause of a trouble signal. It will also blink the amount of drift compensation
that has been used at the conclusion of the test. Trouble signals automati-
cally reset upon removing the cause of trouble. Red and yellow LEDs can be
remotely connected to the remote Alarm and Trouble outputs. These outputs
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
I56-2544-005R

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the NOTIFIER FSB-200A and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Honeywell NOTIFIER FSB-200A

  • Page 1 INSTALLATION AND MAINTENANCE INSTRUCTIONS FSB-200A, FSB-200SA Single-ended Reflected Type Projected 12 Clintonville Road Beam Smoke Detector Northford, CT 06472-1653 Phone: 203.484.7161 SPECIFICATIONS GENERAL Range: 16 to 230 Feet (5 to 70m); 230 to 328 Feet (70 to 100m) using optional accessory BEAMLRK Sensitivity: 25% to 50% Total Obscuration in 6 levels Level 1 = 25%...
  • Page 2 6500-SMK mimic the functions of the detector’s red and yellow LEDs. In addition to these indicators, there is a dual digital display that reads 00 to 99. This display is The 6500-SMK allows the transmitter/receiver to be mounted to the 6500- used to indicate the signal strength of the beam in alignment mode and to MMK heavy duty multi-mount kit indicate the sensitivity setting of the detector in percent obscuration when...
  • Page 3: Mounting Locations

    NOTE: Projected beam smoke detectors should always be mounted to sta- cation and sensitivity of the detectors shall be the result of an engineering ble mounting surfaces. See the MOUNTING LOCATION section for details. evaluation that includes the following: ceiling heights above 30 feet (9.1 m) Some fire codes specify spacing on a given center-to-center distance between - refer to the “Single-Ended Reflected Beam Smoke Detector”...
  • Page 4: Mounting Instructions

    MOUNTING INSTRUCTIONS the protected space will be compromised. Reflective objects should be a mini- The transmitter/receiver unit may be mounted over a recessed junction box. mum of 4 feet (1.2m) from the line of sight between the detector and reflector. The cavity behind the detector is then used for routing of the wiring from the In cases where reflective objects cannot be avoided, the complete reflector junction box to the terminal blocks on the detector.
  • Page 5: Installation / Alignment

    FIGURE 6. wIRING CONNECTIONS AT DETECTOR FIGURE 8. wIRING DIAGRAM (RTS451A/RTS151A) DETECTOR T1-1 SLC IN + SLC OUT + T1-3 PIN 1 T1-2 SLC IN – SLC OUT – T1-4 PIN 2 T2-1 REMOTE ALARM OUT T2-2 PIN 4 AUX (–) T2-4 RESET INPUT PIN 3...
  • Page 6 You are now ready to begin the alignment procedure. NOTE: The alignment procedure is not complete yet. At this time it is possible to set the sensitivity of the detector using the sen- STEP 1. COARSE ALIGNMENT sitivity switch and digital display. See the Sensitivity Selection section of this Refer to Figures 11 and 12 for this step.
  • Page 7 FIGURE 10. SwITCh LOCATIONS FIGURE 12. COARSE ALIGNMENT PROCEDURE ALIGNMENT SENSITIVITY TEST REFLECTOR C0265-00 RESET FIGURE 13. hOUSING SCREw LOCATIONS SCREW LOCATIONS STYLE 7 ISOLATOR SHUNTS (SHOWN DISABLED) C0263-00 FIGURE 11. ALIGNMENT ADjUSTMENT LOCATIONS ALIGNMENT MIRROR ALIGNMENT POSITION ALIGNMENT GUNSIGHT INDICATOR DIGITAL SIGNAL STRENGTH...
  • Page 8 FIGURE 14. REFLECTOR TEST CARD PROCEDURE Sensitivity Display Acceptable Acceptable Setting Obscuration Reading Distance Distance LINE UP EDGE OF Between Between TEST CARD WITH APPROPRIATE Detector Detector OBSCURATION LEVEL Reflector Reflector (Feet) (meters) Level 1 16.4 to 120 5.0 to 36.6 Level 2 25 to 150 7.6 to 45.7...
  • Page 9: Maintenance Note

    These steps include: Verify all wiring connections and appropriate power is applied to the detector. Verify that the optical line of sight is free from obstructions and reflective objects. Apply the maintenance procedure in this manual. Repeat the test proce- dure.
  • Page 10: Appendix I. Operation Modes And Troubleshooting Guide

    APPENDIx I. OPERATION MODES AND TROUBLEShOOTING GUIDE Modes *Red Yellow and *Green Remote Dual Digital Display Initiating means Comments & Troubleshooting Tips Remote Alarm Note Trouble Note Output Below Output Below Normal Blink Blink Successful completion of initialization or detector reset Alignment Blink Blink...
  • Page 11: Appendix Ii. Detector Drilling Template

    APPENDIx II. DETECTOR DRILLING TEMPLATE 6.190˝ (157 mm) 4.345˝ (110 mm) Scale = 1:1 N200-26-00 I56-2544-005R...
  • Page 12 N200-26-00 I56-2544-005R...
  • Page 13: Appendix Iii. Reflector Drilling Template

    APPENDIx III. REFLECTOR DRILLING TEMPLATE 5.512˝ (140mm) 8.465˝ (215mm) Scale = 1:1 N200-26-00 I56-2544-005R...
  • Page 14 Please refer to insert for the Limitations of Fire Alarm Systems FCC Statement This projected beam smoke detector has been tested and found to comply frequency energy and, if not installed and used in accordance with the with the limits for a Class B digital device, pursuant to part 15 of the FCC instruction manual, may cause harmful interference to radio communica- Rules.