If you have any suggestions for improving the design or if some information is missing in the document, please send your suggestions to techdoc@turck.com. V01.00 | 2024/08 | 4 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Number of contacts 2UPN8 2 switching outputs, 4 contacts voltage range 17…33 VDC Orientation Straight Design H1 Male connector M12 x 1 V01.00 | 2024/08 | 5 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
TS700…-30-…: 2 AFM flat seals Quick Start Guide Turck service Turck supports you in your projects – from the initial analysis right through to the commission- ing of your application. The Turck product database at www.turck.com offers you several soft- ware tools for programming, configuring or commissioning, as well as data sheets and CAD files in many export formats.
The product is designed according to state of the art technology. Residual hazards, however, still exist. Observe the following safety instructions and warnings in order to prevent danger to persons and property. Turck accepts no liability for damage caused by failure to observe these safety instructions.
The measured temperature value is passed on to the higher-level I/O. The device display shows the temperature value in the unit selected by the user. V01.00 | 2024/08 | 9 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
(TPM) or a window mode. In Legacy Mode, a window function or hysteresis function can be selected. V01.00 | 2024/08 | 10 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
SP2 switch-off point. If the process value decreases below the switch-off point SP2, the switching output becomes inactive. Switching state Process value Fig. 5: Two point mode V01.00 | 2024/08 | 11 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
(SP2-Hyst). If the process value decreases below (SP2- Hyst), the switching output becomes inactive again. Switching state Hyst Hyst Window Process value Fig. 6: Window mode V01.00 | 2024/08 | 12 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
(SP) and a release point (rP). The minimum hysteresis is 0.2 K. The release point is automatically adjusted if the switching point is changed. hysteresis Fig. 8: Behavior of the switching output (hysteresis function) V01.00 | 2024/08 | 13 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Output behavior of the analog outputs The following figures illustrate the behavior of the analog outputs: analog output process value Fig. 9: Rising output characteristic V01.00 | 2024/08 | 14 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 15
Value of the output when the ASP or AEP is reached Underrun/underrange Overrun/overrange Maximum process value min. Minimum process value V01.00 | 2024/08 | 15 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
When connected to an I/O module, the device detects the pre-defined switching output beha- vior (PNP/NPN) or the analog output characteristic. The auto detect function is activated by default. V01.00 | 2024/08 | 16 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Technical accessories 4.6.1 Connectivity accessories In addition to the above connection cables, Turck also offers other cable types for specific ap- plications with the correct terminals for the device. More information on this is available from the Turck product database at www.turck.de/products...
For TS700…-30-…: After removing and reinstalling the screw-in adapter, use a new seal (replacement seal included in the delivery). V01.00 | 2024/08 | 18 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Set the Compatible Device mode in the IO-Link master so that the device changes to Legacy Mode. Alternatively, set to Legacy Mode in the Extended Functions menu. V01.00 | 2024/08 | 20 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Load at the analog output outside the permissible range Oor+ Value outside of the measuring range, temperature > 5 % of full scale above the measuring range V01.00 | 2024/08 | 21 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 22
> 5 % of full scale below the measuring range No measurement data available PArA Incorrect user parameterization TEMP Device temperature outside the permissible range Unspecified error V01.00 | 2024/08 | 22 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Fully lock user interface (display and touchpads locked) Lock local parameters (user interface parameters — parameters are displayed but cannot be changed) V01.00 | 2024/08 | 23 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
LOC LED is yellow. The sensor is automatically locked if the touchpads of the device are not actuated for 1 min. V01.00 | 2024/08 | 24 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
In the EF menu, you can select Legacy Mode with its own menu guidance. Standard menu guidance — main menu Process value OUT1 OUT2 DISP Fig. 20: Main menu V01.00 | 2024/08 | 26 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 27
>3 s Current value AUTO Save value >3 s Current value OFF on Save value DOFF Fig. 21: Outputs submenu (OUT…) V01.00 | 2024/08 | 27 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 28
… GrEn r-CW COLr Save value >3 s Current value OFF on Save value CSP1 CSP2 Fig. 22: Display submenu (DISP) V01.00 | 2024/08 | 28 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 29
PASS Process value Software version OPHr >3 s Current value FACT rEBO APPL HIGH UnDO Fig. 23: Extended functions submenu (EF) V01.00 | 2024/08 | 29 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Default: 0.0 s Switch-off delay 0…60 s in increments of 0.1 s (0 = delay time not activated) DOFF Default: 0.0 s V01.00 | 2024/08 | 30 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Green if the process value is between the virtual switching points CSP1 and CSP2 r-CW Red if the process value is between the virtual switching points CSP1 and CSP2 V01.00 | 2024/08 | 31 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Reset the minimum value memory: The lowest process temperature is deleted. UnDO Reset the parameters to the previous settings (last device start) V01.00 | 2024/08 | 32 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
>3 s Current value 4…20 … rtio AUTO OUT2 Save value SP2/FH2/ASP rP2/FL2/AEP Fig. 24: Main menu TS700 in Legacy Mode V01.00 | 2024/08 | 33 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 34
>3 s APPL FACT rEbo >3 s Software version VDMA Save value Fig. 25: Extended functions (EF) submenu in Legacy Mode V01.00 | 2024/08 | 34 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 35
Setting via touchpads — Legacy Mode VDMA menu — main menu Run Mode SP1/FH1 rP1/FL1 SP2/FH2/ASP rP2/FL2/AEP Fig. 26: Main menu in the VDMA menu guidance V01.00 | 2024/08 | 35 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 36
Save value PASS >3 s Software version VDMA Save value Fig. 27: Extended functions (EF) submenu in the VDMA menu guidance V01.00 | 2024/08 | 36 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Release point 2 Lower limit value at which output 2 OUT2: Hno/Hnc changes its switching state as the temperature falls Default: 70.0 °C V01.00 | 2024/08 | 37 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Default: 0.0 s Switching delay of rP2 0…60 s in increments of 0.1 s drP2 (0 = delay time not active). Default: 0.0 s V01.00 | 2024/08 | 38 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 39
Lower switching point at which the display changes color point (if display color G-CW or r-CW is selected) Default: 70.0 °C V01.00 | 2024/08 | 39 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
In SIO mode, the device operates in accordance with the most recent set- ting configured in IO-Link mode. V01.00 | 2024/08 | 40 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
If there are no faults, there is a device malfunction. In this case, decommission the device and replace it with a new device of the same type. V01.00 | 2024/08 | 41 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Disposal The devices must be disposed of properly and do not belong in the domestic waste. V01.00 | 2024/08 | 42 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Via San Domenico 5, IT-20008 Bareggio (MI) www.turckbanner.it Japan TURCK Japan Corporation ISM Akihabara 1F, 1-24-2, Taito, Taito-ku, 110-0016 Tokyo www.turck.jp V01.00 | 2024/08 | 47 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 48
United Kingdom TURCK BANNER LIMITED Blenheim House, Hurricane Way, GB-SS11 8YT Wickford, Essex www.turckbanner.co.uk Turck Inc. 3000 Campus Drive, USA-MN 55441 Minneapolis www.turck.us V01.00 | 2024/08 | 48 Hans Turck GmbH & Co. KG | T +49 208 4952-0 | more@turck.com | www.turck.com...
Page 49
Over 30 subsidiaries and 60 representations worldwide! 100042251 | 2024/08 100042251 www.turck.com...
Need help?
Do you have a question about the TS700 Series and is the answer not in the manual?
Questions and answers