Installation, use and maintenance manual e-NextPro 40 Split air/air heat pump system for the air conditioning of large spaces powered by electricity and renewable energy...
Page 2
The rights of those who have legitimately filed the registered trademarks contained within this publication are not affected. With the aim of continuously improving the quality of its products, Robur S.p.A. reserves the right to modify the data and contents of this Installation, use and maintenance manual without prior notice.
CONTROL DEVICE Installation, use and maintenance manual In order to be able to work, the e-NextPro 40 appliance needs a This Manual is an integral part of the e-NextPro 40 appli- control device (PGD control panel, RCC control panel, Multi RCC ance and must be handed to the end user together with control panel), which must be connected by the installer.
The appliance has a sealed circuit classified as a pres- necessary for its operation (except the connection pipes sure vessel, the tightness of which is tested by the of the two modules, the electrical cables between the Installation, use and maintenance manual – e-NextPro 40...
TAC. Protection devices III.3.1 EU directives and standards The e-NextPro 40 appliance complies with the essential require- The adoption of safety measures and all the necessary ments of the following Directives: protective equipment is recommended, in relation to 2006/42/EC "Machine Directive"...
Abnormal actions transmitted to the appliance by the plant or installation (mechanical stresses, pressure, vi- brations, thermal expansion, electrical surges...). Accidental damages or due to force majeure. Installation, use and maintenance manual – e-NextPro 40...
Operation ▶ Low RPM BLDC modulating fan, rotating clockwise or coun- ▶ The e-NextPro 40 split air/air heat pump system for the air con- terclockwise ditioning of large spaces, powered by electricity and renewable 1.1.3.2 Control devices energies, has been designed and built to meet the air condition- Room temperature probe ing needs of high-volume environments.
OPERATION MODE a VNC program. It features a 7” colour resistive touch screen with 800x600 The e-NextPro 40 appliance operates in complete modulation of resolution. both the heat or cooling output and the ventilation of the in- It can be installed on the wall using the appropriate optional door module.
Page 10
The Multi RCC control panel allows independent control of the operation and the main parameters of several appliances, up to a maximum of 15 e-NextPro 40. It provides the possibility of being connected to the Internet via LAN for remote control via the Easy Access application and a VNC program.
Suitable quantity for refrigerant gas piping up to a maximum length of 10 m (Paragraph 3.2.1 p. 15 ). The equivalent length given must be understood for each gas and liquid piping. It does not correspond to the piping's physical length. Installation, use and maintenance manual – e-NextPro 40...
Warranty sheet. ▶ Figure 1�7 Operation field in cooling mode OPTIONALS For the control of the e-NextPro 40 appliance it is necessary to use one of the available controls: PGD control panel (ODSP055), Paragraph 1.4.2 p. 9 . ▶ RCC control panel (ODSP056), Paragraph 1.4.3 p. 9 .
(detail C, Fig- ure 1.1 p. 8 ). Make sure that the outdoor module is in a perfectly hori- zontal position so that the defrost water and rainwater Installation, use and maintenance manual – e-NextPro 40...
Transport and positioning can be correctly discharged from the condensate drain. Figure 2�3 Minimum clearance distances 2.3.1.3 Acoustic issues Pre-emptively assess the appliance's sound effect in connection to the site, taking into account that building corners, enclosed courtyards, restricted spaces may amplify the acoustic impact due to the reverberation phenomenon.
10 meters each, no addition of refrigerant is required. The connection requires the use of welding equipment. For longer lines, multiply the grams of additional charge indicated in Table 3.2 p. 16 by the linear length of the Installation, use and maintenance manual – e-NextPro 40...
Page 16
Table 3�2 Sizing of refrigerant piping and additional circuit charge e-NextPro 40 Maximum length of each gas/liquid pipe (m of equivalent length) Recommended additional refrigerant charge over 10 linear m (g/m of linear length)
Page 17
Figure 3.2 p. 17 . Consequently, the use of a pair of siphons is required, on both gas and liquid circuits, in the vertical pipe The online configurator can be reached from the Robur section, positioned about halfway along the vertical section. The siphons must be positioned so that the difference in height be- tween each of the two vertical sections is less than 4 m.
Heating/refrigeration engineer 6 mm is recommended, suitable for the place of installation Do not charge refrigerant gas in the absence of TAC and installed in a workmanlike manner. 12� Once the welding operations have been completed, before The refrigerant gas must be charged by the installer, in reassembling the pin valves referred to in step 7 on the out- the quantities indicated by the TAC, exclusively in the door module, it is advisable to flush the entire circuit with...
Respect the right rotation field: if the wiring is incorrect, the heat pump will not start. If the wiring is incorrect, the control panel shows the relevant alarm. Correct the wir- ing accordingly. Power cable section Installation, use and maintenance manual – e-NextPro 40...
Electrical installer place of installation. Figure 4�1 Electrical connections of e-NextPro 40 Carry out the earthing. Perform an evaluation on the protection (differential) from indirect contacts, depending on the configuration of the electrical system at the installation site. In this regard, we recommend the use of type "A"...
Page 21
Figure 4�2 Electrical panel detail of the outdoor module (heat pump) Outdoor module power supply terminal block terminal block Outdoor module electronic board Indoor module electrical panel power supply Indoor module signal terminal block Outdoor module front panel Installation, use and maintenance manual – e-NextPro 40...
Table 4�1 Characteristics of protective devices and cables tion and the connection cables, depending on the place of laying, the ambient temperature, the length, the type e-NextPro 40 of cable and the absorption of the appliance. Power consumption 9,98 kW...
D, Figure 4.2 p. 21 ). This request can be used to enable and room and provide this information to the control system of the disable operation, even on multiple e-NextPro 40 appliances. appliance. This functionality does not replace the control panel connect-...
For further information on the operation and use of the 3P+N+T - 400 V AC - 50 Hz electrical distribution panel e-NextPro 40 appliances in this mode, please contact the Power cable from main switch to Maximum length 5 m if using the Robur technical service.
1000 m board of each outdoor module FIRST START-UP The first start-up can only be carried out by a Robur TAC. After performing the remedial actions (the installer's responsi- The user/installer is NOT authorised to perform such op- bility), if the TAC deems that safety and conformity conditions erations, under penalty of forfeiture of the warranty.
30 minutes have elapsed. If you want to switch off the appliance for a long period, please First start-up may exclusively be carried out by a Robur refer to Paragraph 7.5 p. 28 . TAC (Chapter 5 p. 25 ).
Diagnostics FAULTS AND RESETS supply for long periods, do not interrupt the compressor oil heating procedure which starts when the appliance is powered up again. This procedure prevents breakage of 7.4.1 Fault signals on the display the compressor. In the case of a blocked appliance, an appropriate alarm signal 7.5.1 is shown on the control panel connected to the appliance (PGD, Prolonged periods of inactivity...
Page 29
Immediate Stop the appliance ALD07 High evaporation temperature (MOP) Manual Immediate Stop the appliance ALD08 High condensing temperature (HiTcond) Manual Immediate Stop the appliance ALD09 Offline driver Automatic Immediate Stop the appliance Installation, use and maintenance manual – e-NextPro 40...
It is activated if the heat pump is producing energy that is not transmitted to the system. The compressor is brought Power limitation by temperature to the minimum speed to avoid generating an error. Installation, use and maintenance manual – e-NextPro 40...
For air-to-air heat pumps: air flow rate, outdoor Capacity control variable 17200 m³/h measured 59,6 / Sound power level, indoor/outdoor measured 60,2 kg CO GWP of the refrigerant (100 years) Contact details Robur SPA, Via Parigi 4/6, I-24040 Zingonia (BG)
Parigi 4/6 24040 Verdellino/Zingonia (BG) Italy Tel. +39 035.888.111 Fax +39 035.884.165 capitale sociale € 2.028.000,00 i.v. iscritta al Registro Imprese di Bergamo n.154968 codice fiscale/partita iva 00373210160 V.A.T. code IT 00373210160 società soggetta all'attività di direzione e coordinamento di Fin Robur S.r.l.
Page 36
Robur mission Robur is dedicated to dynamic progression in research, development and promotion of safe, environmentally-friendly, energy-efficiency products, through the commitment and caring of its employees and partners. Robur S.p.A. advanced technologies for air conditioning via Parigi 4/6 24040 Verdellino/Zingonia (BG) Italy +39 035 888111 - F +39 035 884165 www.robur.com export@robur.it...