Fujitsu AIRSTAGE ABUH18KUAS Service Manual
Fujitsu AIRSTAGE ABUH18KUAS Service Manual

Fujitsu AIRSTAGE ABUH18KUAS Service Manual

Ceiling type
Hide thumbs Also See for AIRSTAGE ABUH18KUAS:
Table of Contents

Advertisement

Quick Links

AIR CONDITIONER
Ceiling type
INDOOR
OUTDOOR
SERVICE MANUAL
ABUH18KUAS
AOUH18KUAS1
ABUH24KUAS
ABUH30KUAS
AOUH24KUAS1
ABUH36KUAS
AOUH30KUAS1
AOUH36KUAS1
SR_AB018ES_01
2024.11.21

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AIRSTAGE ABUH18KUAS and is the answer not in the manual?

Questions and answers

Summary of Contents for Fujitsu AIRSTAGE ABUH18KUAS

  • Page 1 AIR CONDITIONER Ceiling type SERVICE MANUAL INDOOR ABUH18KUAS ABUH24KUAS ABUH36KUAS ABUH30KUAS OUTDOOR AOUH18KUAS1 AOUH24KUAS1 AOUH30KUAS1 AOUH36KUAS1 SR_AB018ES_01 2024.11.21...
  • Page 2 Mobile” is a trademark of FUJITSU GENERAL LIMITED. ™ Google Play is trademark of Google LLC. ® App Store is a service mark of Apple Inc., registered in the U.S. and other countries. Copyright © 2024 Fujitsu General Limited. All rights reserved.
  • Page 3: General Information

    CONTENTS 1. GENERAL INFORMATION 2. TECHNICAL DATA AND PARTS LIST 3. TROUBLESHOOTING 4. CONTROL AND FUNCTIONS 5. FIELD WORKING...
  • Page 5 1. GENERAL INFORMATION 2024.11.06 SR_CH01_AB018ES_01...
  • Page 6 CONTENTS 1. GENERAL INFORMATION 1. Specifications....................01-1 1-1. Indoor unit ........................01-1 1-2. Outdoor unit........................01-7 2. Dimensions....................01-10 2-1. Indoor unit ........................01-10 2-2. Outdoor unit........................01-14...
  • Page 7 1. Specifications 1-1. Indoor unit Ceiling Type Inverter, Heat pump Model name ABUH18KUAS Power supply intake Outdoor unit Voltage 208/230 System power supply Frequency Available voltage range 187—253 Indoor unit power supply (from outdoor unit) 208/230 k→ 5.28 Rated Btu/h 18,000 Cooling k→...
  • Page 8 Ceiling Type Inverter, Heat pump Model name ABUH18KUAS Remote controller type (Option) →ired, →ireless, Mobile app* (AIRSTAGE Mobile) NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB/67°F→B (26.67°CDB/19.44°C→B), and outdoor temperature of 95°FDB/75°F→B (35°CDB/23.9°C→B). –...
  • Page 9 Ceiling Type Inverter, Heat pump Model name ABUH24KUAS ABUH30KUAS Power supply intake Outdoor unit Voltage 208/230 System power supply Frequency Available voltage range 187—253 Indoor unit power supply (from outdoor unit) 208/230 k→ 7.03 8.79 Rated Btu/h 24,000 30,000 Cooling k→...
  • Page 10 Ceiling Type Inverter, Heat pump Model name ABUH24KUAS ABUH30KUAS NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB/67°F→B (26.67°CDB/19.44°C→B), and outdoor temperature of 95°FDB/75°F→B (35°CDB/23.9°C→B). – Heating: Indoor temperature of 70°FDB/60°F→B (21.11°CDB/15.56°C→B), and outdoor temperature of 47°FDB/43°F→B (8.33°CDB/6.11°C→B). –...
  • Page 11 Ceiling Type Inverter, Heat pump Model name ABUH36KUAS Power supply intake Outdoor unit Voltage 208/230 System power supply Frequency Available voltage range 187—253 Indoor unit power supply (from outdoor unit) 208/230 k→ 10.55 Rated Btu/h 36,000 Cooling k→ 2.81—11.43 Min.—Max. Btu/h 9,600—39,000 k→...
  • Page 12 Ceiling Type Inverter, Heat pump Model name ABUH36KUAS NOTES: • Specifications are based on the following conditions: – Cooling: Indoor temperature of 80°FDB/67°F→B (26.67°CDB/19.44°C→B), and outdoor temperature of 95°FDB/75°F→B (35°CDB/23.9°C→B). – Heating: Indoor temperature of 70°FDB/60°F→B (21.11°CDB/15.56°C→B), and outdoor temperature of 47°FDB/43°F→B (8.33°CDB/6.11°C→B). –...
  • Page 13: Outdoor Unit

    1-2. Outdoor unit ¢ Model: AOUH18KUAS1 Type Inverter, Heat pump Model name AOUH18KUAS1 Power supply 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Starting current Cooling 1,318 (2,240) Airflow rate CFM (m Heating 1,154 (1,960) Type ×...
  • Page 14 ¢ Model: AOUH24KUAS1 Type Inverter, Heat pump Model name AOUH24KUAS1 Power supply 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Starting current Cooling 2,187 (3,715) Airflow rate CFM (m Heating 2,187 (3,715) Type × Qty Propeller fan ×...
  • Page 15 ¢ Models: AOUH30KUAS1 and AOUH36KUAS1 Type Inverter, Heat pump Model name AOUH30KUAS1 AOUH36KUAS1 Power supply 208/230 V~ 60 Hz Power supply intake Outdoor unit Available voltage range 187—253 V Starting current 11.0 14.1 Cooling 2,301 (3,910) 2,502 (4,250) Airflow rate CFM (m Heating 2,219 (3,770)
  • Page 16 2. Dimensions 2-1. Indoor unit ¢ Model: ABUH18KUAS Unit: in (mm) 42-1/2 (1,080) 36-5/16 (923) 1-15/16 3-5/16 (49) (84) 4-15/16 4-1/16 (125) (103) Side view Top view 13-3/4 (349) 7-1/8 (181) 12-5/16 (313) 5-11/16 (145) 3-7/8 4-11/16 (119) 3-1/2 (89) (98) ø3-5/16 (100)-mm hole Rear view...
  • Page 17 ¢ Models: ABUH24KUAS and ABUH30KUAS Unit: in (mm) 54-3/4 (1,390) 48-9/16 (1,233) 1-15/16 3-5/16 (49) (84) 4-15/16 4-1/16 (125) (103) Side view Top view 13-3/4 (349) 7-1/8 (181) 12-5/16 (313) 5-11/16 (145) 3-7/8 3-1/2 (89) 4-11/16 (119) (98) ø3-15/16 (100)-mm hole Rear view Suspension bolt pitch 2-15/16 (75)
  • Page 18 ¢ Model: ABUH36KUAS Unit: in (mm) 66-15/16 (1,700) 60-3/4 (1,543) 1-15/16 3-5/16 (49) (84) 4-15/16 4-1/16 (125) (103) Side view Top view 13-3/4 (349) 7-1/8 (181) 12-5/16 (313) 5-11/16 (145) 3-7/8 4-11/16 (119) 3-1/2 (89) (98) ø100-mm hole Rear view Suspension bolt pitch 2-15/16 (75) 60-3/4 (1,543)
  • Page 19: Installation Space Requirement

    ¢ Installation space requirement Unit: in (mm) Ceiling Indoor unit 2 (30) or more Ceiling 8 (200) or more 0 or more Obstruction Floor Required ceiling height varies according to the ceiling mode setting of function setting No. 20. Ceiling height in (mm) Ceiling mode Standard...
  • Page 20 2-2. Outdoor unit ¢ Model: AOUH18KUAS1 Unit: in (mm) 4-M10 hole 22-13/16 (580) 4-5/16 (109) Pitch of bolts for installation Top view 3/4 (19) 31-7/16 (799) 2-11/16 (68) 1/2 (13) 11-7/16 (290) 1-5/16 (33) 1-3/16 (30) Side view Front view Side view Airflow Hole...
  • Page 21 ¢ Model: AOUH24KUAS1 Unit: in (mm) 5-13/16 25-9/16 (650) 5-5/8 (147) (143) 3-way valve (Gas) 3-way valve (Liquid) 1-1/4 (48) Liquid Top view Detail A Detail B 12-5/8 (320) 37 (940) 1-9/16 (40) 9/16 (14) 2-Ф7/8 (22) Cable port 2-Ф7/8 (22) Cable port 2-Ф1/8 (28) Cable port...
  • Page 22 ¢ Models: AOUH30KUAS1 and AOUH36KUAS1 Unit: in (mm) 5-13/16 5-5/8 (147) 25-9/16 (650) (143) 1-7/8 (48) 1-3/8 (35.7) Top view 37 (940) 1-9/16 12-5/8 (320) 3/16 (40) 3-way valve (Liquid) 3-way valve (Gas) 2-Ф7/8 (22) 2-Ф7/8 (22) Cable port Cable port 2-Ф1/8 (28) Cable port 2-Ф1/8 (28)
  • Page 23 2. TECHNICAL DATA AND PARTS LIST 2024.11.06 SR_CH02_AB018ES_01...
  • Page 24 CONTENTS 2. TECHNICAL DATA AND PARTS LIST 1. Precautions....................02-1 2. Indoor unit parts list..................02-2 2-1. Model: ABUH18KUAS ....................02-2 2-2. Models: ABUH24KUAS and ABUH30KUAS..............02-4 2-3. Model: ABUH36KUAS ....................02-6 3. Outdoor unit parts list.................02-8 3-1. Model: AOUH18KUAS1....................02-8 3-2. Model: AOUH24KUAS1....................02-12 3-3. Models: AOUH30KUAS1 and AOUH36KUAS1............02-16 4.
  • Page 25 • Service parts information and design are subject to change without notice for product improve- ment. • For the latest information of the service parts, refer to our Service Portal. https://fujitsu-general.force.com/portal/ • Precise figure of the service parts listed in this manual may differ from the actual service parts. - (02-1) -...
  • Page 26 2. Indoor unit parts list 2-1. Model: ABUH18KUAS ¢ Chassis - (02-2) - 2-1. Model: ABUH18KUAS 2. Indoor unit parts list...
  • Page 27 Item no. Part no. Part name 9384321015 Intake grille B sub assy 9383342011 Air filter B 9384307002 Casing U assy 9384110015 Sirocco fan assy 9383443008 Rubber (Vibration proof) 9603817008 DC fan motor 9384311009 Casing B assy 9383406003 Side panel L 9384144027 Flap assy (2-fan) 9383386008...
  • Page 28 2-2. Models: ABUH24KUAS and ABUH30KUAS ¢ Chassis - (02-4) - 2-2. Models: ABUH24KUAS and ABUH30KUAS 2. Indoor unit parts list...
  • Page 29 Item no. Part no. Part name 9384321015 Intake grille B sub assy 9383342011 Air filter B 9384321008 Intake grille A sub assy 9383342004 Air filter A 9384307002 Casing U assy 9357921006 Bearing B assy 9384110008 Sirocco fan assy 9384270009 Shaft 9378038011 Joint assy 9383443008...
  • Page 30 2-3. Model: ABUH36KUAS ¢ Chassis - (02-6) - 2-3. Model: ABUH36KUAS 2. Indoor unit parts list...
  • Page 31 Item no. Part no. Part name 9384321008 Intake grille A sub assy 9383342004 Air filter A 9384307002 Casing U assy 9357921006 Bearing B assy 9384110008 Sirocco fan assy 9384270009 Shaft 9378038011 Joint assy 9383443008 Rubber (Vibration proof) 9603815004 DC fan motor 9384311009 Casing B assy 9383406003...
  • Page 32 3. Outdoor unit parts list 3-1. Model: AOUH18KUAS1 ¢ Exterior parts and Chassis - (02-8) - 3-1. Model: AOUH18KUAS1 3. Outdoor unit parts list...
  • Page 33 Item no. Part no. Part name 9322556028 Top panel assy 9377854001 Protective net 9322327000 Thermistor holder 9900565145 Thermistor (Outdoor temp.) 9712996052 Main PCB 9900935054 Thermistor assy 9900984014 Thermistor (Heat exchanger temp.) 9900985011 Thermistor (Compressor temp.) 9322570062 Switch cover assy 9384276001 Conduit cover 9322552365 Cabinet right assy...
  • Page 34 ¢ Compressor - (02-10) - 3-1. Model: AOUH18KUAS1 3. Outdoor unit parts list...
  • Page 35 Item no. Part no. Part name 9810521002 Compressor 9322446015 4-way valve assy 9970194023 Solenoid 9970222016 Expansion valve coil 9322463029 Pulse motor valve assy 9322474001 2-way valve assy 9387831016 3-way valve assy - (02-11) - 3-1. Model: AOUH18KUAS1 3. Outdoor unit parts list...
  • Page 36 3-2. Model: AOUH24KUAS1 ¢ Exterior parts and chassis 13 13 - (02-12) - 3-2. Model: AOUH24KUAS1 3. Outdoor unit parts list...
  • Page 37 Item no. Part no. Part name 9383880001 Top panel sub assy 9383779008 Protective net 9900984038 Thermistor (Heat exchanger temp.) 9900727154 Thermistor assy 9900565152 Thermistor (Outdoor temp.) 9383607004 Thermostat holder 9383874000 Right panel sub assy 9384997005 Rear pipe cover 9712996083 Inverter PCB 9901031014 Thermistor (Heat sink temp.) 9900203061...
  • Page 38 ¢ Compressor - (02-14) - 3-2. Model: AOUH24KUAS1 3. Outdoor unit parts list...
  • Page 39 Item no. Part no. Part name 9900186029 Pressure switch 9374425723 4-way valve assy 9970194016 Solenoid 9375250263 Accumulator assy 9970209000 Expansion valve coil 9370947373 Expansion valve assy 9970221002 3-way valve assy 9317171182 2-way valve assy 9900985035 Thermistor (Compressor temp.) 9811000001 Compressor - (02-15) - 3-2.
  • Page 40 3-3. Models: AOUH30KUAS1 and AOUH36KUAS1 ¢ Exterior parts and chassis 14 14 - (02-16) - 3-3. Models: AOUH30KUAS1 and AOUH36KUAS1 3. Outdoor unit parts list...
  • Page 41 Item no. Part no. Part name 9383880001 Top panel assy 9381013005 Protective net 9900984038 Thermistor (Heat exchanger temp.) 9900727154 Thermistor assy 9383607004 Thermostat holder 9900565152 Thermistor (Outdoor temp.) 9383874017 Right panel sub assy 9384997005 Rear pipe cover 9712996090 Inverter PCB 9901031014 Thermistor (Heat sink temp.) 9900203061...
  • Page 42 ¢ Compressor - (02-18) - 3-3. Models: AOUH30KUAS1 and AOUH36KUAS1 3. Outdoor unit parts list...
  • Page 43 Item no. Part no. Part name 9900186029 Pressure switch 9374425761 4-way valve assy 9970194016 Solenoid 9375250232 Accumulator assy 9970209000 Expansion valve coil 9370947427 Expansion valve assy 9379079037 3-way valve assy 9387794007 3-way valve assy 9900985028 Thermistor (Compressor temp.) 9810621009 Compressor - (02-19) - 3-3.
  • Page 44 4. Accessories 4-1. Indoor unit ¢ Models: ABUH18KUAS, ABUH24KUAS, ABUH30KUAS, and ABUH36KUAS Part name Exterior Part name Exterior Operation manual Drain hose Installation manual Hose band Template Cable tie (large) →asher A Cable tie (small) (with insulation) →asher B Cable hole cap Coupler heat insulation Self-tapping screw (large)
  • Page 45: Outdoor Unit

    4-2. Outdoor unit ¢ Model: AOUH18KUAS1 Part name Exterior Part name Exterior Installation manual Cable tie Drain pipe Protection label Drain cap ¢ Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 Part name Exterior Part name Exterior Installation manual Drain pipe Protection label Drain cap - (02-21) - 4-2.
  • Page 46 5. Optional parts 5-1. Indoor unit ¢ Controllers Exterior Part name Model name Summary Remote controller that provides the functions you need in a sleek design →ired Remote that uniquely transforms itself to blend Controller UT↔-RVRU with any interior. (Touch Panel) Connecting point: Terminal block (↔1 and ↔2) Easy finger touch operation with LCD...
  • Page 47 UART interface and a Modbus Modbus UT↔-VMS↓ open network. Converter Connecting point: CN65 or CN75 on Main PCB This converter can control Fujitsu General products using a third-party Thermostat UT↔-TTR↓Z* thermostat controller. Converter Connecting point: Terminal block (↔1 and ↔2) - (02-23) - 5-1.
  • Page 48 Exterior Part name Model name Summary This converter is required when connecting single split system to VRF Network UT↔-VTG↓ network system. Converter Connecting point: Terminal block (↔1 and ↔2) This converter is required when Network connecting single split system to VRF Converter UT↔-VTG↓V network system.
  • Page 49: Refrigerant System Diagrams

    6. Refrigerant system diagrams 6-1. Model: AOUH18KUAS1 Heat exchanger 3-way 2-way (INDOOR) valve valve Muffler Muffler Strainer 4-way valve Expansion valve Accumulator Heat exchanger Strainer (OUTDOOR) Cooling Heating : Thermistor (Compressor temperature) : Thermistor (Discharge temperature) : Thermistor (Heat exchanger middle temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature)
  • Page 50 6-2. Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 Heat exchanger 3-way 3-way (INDOOR) valve valve Pressure switch 4-way valve Strainer Expansion valve Strainer Heat exchanger (OUTDOOR) : Cooling : Heating : Thermistor (Compressor temperature) : Thermistor (Discharge temperature) : Thermistor (Heat exchanger middle temperature) : Thermistor (Outdoor temperature) : Thermistor (Heat exchanger out temperature) : Thermistor (Pipe temperature)
  • Page 51 7. Wiring diagrams 7-1. Indoor unit ¢ Models: ABUH18KUAS, ABUH24KUAS, and ABUH30KUAS - (02-27) - 7-1. Indoor unit 7. →iring diagrams...
  • Page 52 ¢ Model: ABUH36KUAS - (02-28) - 7-1. Indoor unit 7. →iring diagrams...
  • Page 53 7-2. Outdoor unit ¢ Model: AOUH18KUAS1 - (02-29) - 7-2. Outdoor unit 7. →iring diagrams...
  • Page 54 ¢ Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 - (02-30) - 7-2. Outdoor unit 7. →iring diagrams...
  • Page 55 8. PC board diagrams 8-1. Models: ABUH18KUAS, ABUH24KUAS, and ABUH30KUAS CONTROL UNIT 18 model: EZ-024PHSE 24 model: EZ-024RHSE 30 model: EZ-024SHSE EMI FILTER ZCAT1518-0730 TERMINAL DC 12 V 2 TURNS CN300-1 CN8 Thermistor Characteristics. UL1007 AWG22 RED REMOTE REMOTE CONTROLLER CN300-2 CN300 UL1007 AWG22 WHITE...
  • Page 56 8-2. Model: ABUH36KUAS CONTROL UNIT EZ-024THSE EMI FILTER ZCAT1518-0730 TERMINAL CN8 Thermistor Characteristics. 2 TURNS UL1007 AWG22 RED CN300-1 DC5 V OPTION UNIT Temperature CN300 32℉ 68℉ 86℉ Thermistor UL1007 AWG22 WHITE CN300-2 CN8-1 REMOTE CONTROLLER B04B-XARK-1-A (LF)(SN) BLACK (2-WIRE) CN300-3 WHITE B02B-XASK-1-A (LF)(SN)
  • Page 57 8-3. Model: AOUH18KUAS1 CONTROL UNIT EZ-0248HUE EMI FILTER TRM-31-20-15E-WE 3 TURNS UL3271 AWG16 W400 UL3271 AWG16 W401 WHITE WHITE COMPRESSOR UL3271 EMI FILTER EMI FILTER AWG16 Winding Resistance KRFC-13 KRFC-13 W402 BLACK BLACK TO INDOOR UNIT 2 TURNS 1 TURN UL1015 1.916 (68°F [20°C])
  • Page 58 8-4. Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 CONTROL UNIT 24 model: EZ-0245HUE 30, 36 models: EZ-0246HUE 5 V-1 UL1015 AWG20 GREEN BLACK P700 THERMISTOR (HEAT SINK TEMP.) B03B-XAKK-1-A (LF)(SN) INDOOR POWER SUPPLY/COM. BLACK BLACK TERMINAL P108 EMI FILTER B3P5-VH-B (LF)(SN) EMI FILTER GRFC-8 GRFC-13 BLUE...
  • Page 59: Troubleshooting

    3. TROUBLESHOOTING 2024.11.21 SR_CH03_AB018ES_01...
  • Page 60 CONTENTS 3. TROUBLESHOOTING 1. Error code ....................03-1 1-1. How to check the error memory..................03-1 1-2. How to erase the error memory ..................03-1 1-3. Error code table (→ired remote controller)..............03-2 1-4. Error code table (Outdoor unit: for 24/30/36 model only)..........03-3 1-5. Error code table (→ireless LAN indicator)...............03-5 1-6.
  • Page 61: Table Of Contents

    CONTENTS (continued) 2-32. E: 97.↓. Outdoor unit fan motor error (Outdoor unit)...........03-57 2-33. E: 99.↓. 4-way valve error (Outdoor unit) ..............03-59 2-34. E: A1.↓. Discharge temperature error (Outdoor unit)..........03-61 2-35. E: A3.↓. Compressor temperature error (Outdoor unit) ..........03-63 2-36. E: AC.↓. Heat sink temperature error (Outdoor unit) (24/30/36 model) ......03-65 3.
  • Page 63: Error Code

    1. Error code →hen a problem occurs in the system or the connected device, the error content is notified by dis- playing the code. NOTE: This function is only available in a system with indoor or IR receiver units equipped with in- dicator lamps to show the error content.
  • Page 64 1-3. Error code table (Wired remote controller) The operation, timer, and economy indicators operate according to the error contents. For confirmation of the error contents, refer the flashing pattern as follows. Wired remote Error contents controller display E: 11.↓. Serial communication error (Serial reverse transfer error) (Outdoor unit) E: 11.↓.
  • Page 65 1-4. Error code table (Outdoor unit: for 24/30/36 model only) The operation status is determined by the lighting up and blinking of the LED lamp. After check that ERROR LED lamp blinks, press the ENTER button once. NOTE: For the positions of LED lamp and buttons, refer to "Function settings (for 24–36 outdoor units)"...
  • Page 66: E: 97.↓. Outdoor Unit Fan Motor Error (Outdoor Unit)

    PUMP LOW NOISE PEAK CUT POWER/ DOWN Error contents ERROR MODE E: 95.↓. Compressor motor control ■ ● ■ ■ ○ ○ ○ ● error (Outdoor unit) E: 97.↓. Outdoor unit fan motor error ■ ● ■ ■ ○ ○ ●...
  • Page 67 1-5. Error code table (Wireless LAN indicator) • →ireless LAN control system diagram example Indoor unit Internet Main PCB Cloud Wireless Mobile app Parts: Outdoor unit router (Smart device) WLAN adapter • Name of parts WLAN adapter Wireless LAN label MAC: SSID: AP- PIN:...
  • Page 68 1-6. How to check the error code on Mobile app If there is an abnormality on the air conditioning, refer to as follows. →hen the (error button) on the home screen is tapped, error code and error name is displayed. Error button Error code Error name...
  • Page 69: Error Message

    1-7. Error code table (Mobile app) Error message Error contents Error code Serial reverse transmission error at start-up 11.1 E: 11.↓. Serial communication error (Serial Serial reverse transmission error during reverse transfer error) (Outdoor unit) 11.2 operation Serial forward transmission error at start-up 11.3 E: 11.↓.
  • Page 70 Error message Error contents Error code E: 71.↓. Discharge thermistor error (Outdoor Outdoor unit discharge temp. thermistor 1 error 71.1 unit) E: 72.↓. Compressor thermistor error Outdoor unit discharge temp. thermistor 1 error 72.1 (Outdoor unit) Outdoor unit heat ex. liquid temp. thermistor E: 73.↓.
  • Page 71 1-8. Error message for wireless LAN control (Mobile app) ¢ Error display If there is an abnormality on the wireless control system, refer to error messages as follows. Error message - (03-9) - 1-8. Error message for wireless LAN control (Mobile app) 1.
  • Page 72: Error Message List

    ¢ Error message list • Registration error Cause Error Error message code Solution Communication failed. After Communication with the air conditioner failed. checking the following Check the following contents depending on the status of indoor contents, please try again unit wireless LAN indicator lamp or →LAN Adapter LED 2 and after a while.
  • Page 73 Cause Error Error message code Solution →LAN adapter password is Failed because the smartphone could not connect to the air wrong. Enter it again. conditioner. Check the following contents depending on the status of indoor →hen problems are not unit wireless LAN indicator lamp or →LAN Adapter LED 2 and resolved, there may be other operate again.
  • Page 74 Cause Error Error message code Solution • The air conditioner you are trying to register is already registered to another account. • Registration failed because the air conditioner cannot connect to the Internet. • Immediately after turning on the power of the air Air conditioner registration conditioner, wait for about 5 minutes before registering it.
  • Page 75 Cause Error Error message code Solution Registration may have failed because a problem occurred in communication with the server (cloud). 2944 Communication failed. →ait for a while and then operate again. The connected air conditioner ↔our air conditioner does not support Direct Control. 2946 cannot use the Direct control.
  • Page 76 • Sign in error Cause Error Error message code Solution Various settings could not be completed because Communication failed. After 4010 communication with the server (cloud) failed. checking the following 4410 contents, please try again after Check the following contents and operate again. a while.
  • Page 77 Cause Error Error message code Solution User information or temperature unit information could not be Loading of user information obtained because communication with the server (cloud) failed. failed. Check the following Check the following contents and operate again. contents. 4420 1.
  • Page 78 • General error Cause Error Error message code Solution 0100 Communication with the air conditioner failed. 0200 0300 0400 Check the following contents depending on the status of indoor 0500 unit wireless LAN indicator lamp or →LAN Adapter LED 2 and operate again.
  • Page 79 Cause Error Error message code Solution The outdoor unit low noise timer information could not be obtained because communication with the server (cloud) failed. Check the following contents depending on the status of indoor unit wireless LAN indicator lamp or →LAN Adapter LED 2 and operate again.
  • Page 80 Cause Error Error message code Solution The error history information could not be obtained because communication with the server (cloud) failed. Check the following contents depending on the status of indoor unit wireless LAN indicator lamp or →LAN Adapter LED 2 and operate again.
  • Page 81 Cause Error Error message code Solution Air conditioner group setting has not been completed because communication with air conditioner failed. Check the following contents depending on the status of indoor unit wireless LAN indicator lamp or →LAN Adapter LED 2 and operate again.
  • Page 82 Cause Error Error message code Solution Air conditioner group setting has not been completed because communication with air conditioner failed. Check the following contents depending on the status of indoor unit wireless LAN indicator lamp or →LAN Adapter LED 2 and operate again.
  • Page 83 Cause Error Error message code Solution Air conditioner group setting has not been completed because communication with air conditioner failed. Check the following contents depending on the status of indoor unit wireless LAN indicator lamp or →LAN Adapter LED 2 and operate again.
  • Page 84 Cause Error Error message code Solution Various settings could not be completed because Failed to update the screen. communication with the server (cloud) failed. After checking the following contents, please try again after Check the following contents and operate again. a while.
  • Page 85 2. Troubleshooting with error code 2-1. E: 11.X. Serial communication error (Serial reverse transfer error) (Outdoor unit) →ired remote Indicator Error code E: 11 controller Main PCB →hen the indoor unit cannot receive the serial signal from outdoor unit more than 2 minutes after power on, Detective actuator Outdoor unit or the indoor unit cannot receive the serial signal more...
  • Page 86 Check point 4. Check serial signal (Reverse transfer signal) Check serial signal (Reverse transfer signal) BLACK WHITE BLACK WHITE • Check if indicated value swings between AC 90 V and AC 270 V at the outdoor unit terminal 1 —3. •...
  • Page 87 2-2. E: 11.X. Serial communication error (Serial forward transfer error) (Indoor unit) →ired remote Indicator Error code E: 11 controller →hen the outdoor unit cannot receive the serial signal Detective actuator Indoor unit Main PCB from indoor unit more than 10 seconds. Connection failure Forecast of cause External cause...
  • Page 88 Check point 4. Check serial signal (Forward transfer signal) Check serial signal (Forward transfer signal) BLACK WHITE BLACK WHITE • Check if indicated value swings between AC 30 V and AC 130 V at outdoor unit terminal 2—3. • If it is abnormal, replace main PCB. Check point 1-2.
  • Page 89 2-3. E: 12.X. Wired remote controller communication error (Indoor unit) →ired remote Indicator Error code E: 12 controller Indoor unit Main PCB →hen the indoor unit cannot receive the signal from Detective actuator →ired remote controller more than 1 minute during →ired remote control normal operation.
  • Page 90 2-4. E: 15.X. Automatic air flow adjustment error (Indoor unit) →ired remote Indicator Error code E: 15 controller • On automatic airflow adjustment operation, when the fan speed other than 0rpm is detected at the 0rpm operation. • On automatic airflow adjustment operation, when Detective actuator Indoor unit Main PCB...
  • Page 91 2-5. E: 22.X. Indoor unit capacity error (Indoor unit) →hen the total capacity of the indoor units does not Detective actuator Indoor unit main PCB match outdoor unit capacity while 3 minutes after power Indoor unit selection is incorrect. Forecast of cause Main PCB failure Check point 1.
  • Page 92 2-6. E: 23.X. Combination error (Outdoor unit) →ired remote Indicator Error code E: 23 controller The outdoor unit receives the serial signal of applied Detective actuator Indoor unit refrigerant information from indoor unit. Forecast of cause Incorrect indoor unit is selected. Check point 1.
  • Page 93 2-7. E: 26.X. Address setting error in wired remote controller (Indoor unit) →ired remote Indicator Error code E: 26 controller →ired remote controller (2-wire) • →hen the address number set by auto setting and manual setting are mixed in one remote controller group Detective actuator Indoor unit controller PCB...
  • Page 94 2-8. E: 29.X. Connected unit number error (Indoor unit) →ired remote Indicator Error code E: 29 controller →ired remote controller (2-wire) →hen the number of the connected indoor unit exceeds Detective actuator the limitation. Indoor unit main PCB →rong wiring of indoor unit or remote controller Number of indoor unit or remote controller in remote Forecast of cause controller group...
  • Page 95 2-9. E: 32.X. Indoor unit main PCB error (Indoor unit) →ired remote Indicator Error code E: 32 controller →hen power is on and there is some below case. Detective actuator Indoor unit Main PCB 1. →hen model information of EEPROM is incorrect. 2.
  • Page 96 2-10. E: 33.X. Indoor unit motor electricity consumption detection error (Indoor unit) →ired remote Indicator Error code E: 33 controller Indoor unit motor electricity →hen the voltage value or the current value of the motor Detective actuator consumption detection go beyond the limits Fan motor failure Forecast of cause Main PCB failure...
  • Page 97 2-11. E: 35.X. MANUAL AUTO button error (Indoor unit) →ired remote Indicator Error code E: 35 controller Indoor unit controller PCB →hen the MANUAL AUTO button becomes on for Detective actuator Indicator PCB consecutive 60 or more seconds. Manual auto switch MANUAL AUTO button failure Forecast of cause Controller PCB and indicator PCB failure...
  • Page 98 2-12. E: 39.X. Indoor unit power supply error for fan motor (Indoor unit) →ired remote Indicator Error code E: 39 controller • →hen a momentary power cut off Detective actuator Indoor unit main PCB • →hen do not start fan motor External cause Forecast of cause Connector connection failure...
  • Page 99 2-13. E: 3A.X. Indoor unit communication circuit (wired remote controller) error →ired remote Indicator Error code E: 3A controller →ired remote controller (2-wire) Detect the communication error of microcomputer and Detective actuator communication PCB. Indoor unit controller PCB circuit Communication PCB defective Forecast of cause Indoor unit main PCB defective Check point 1.
  • Page 100 2-14. E: 41.X. Room temperature sensor error (Indoor unit) →ired remote Indicator Error code E: 41 controller Indoor unit main PCB Room temperature thermistor is open or short is Detective actuator detected always. Room temperature thermistor Connector failure Forecast of cause Thermistor failure Main PCB failure Check point 1.
  • Page 101 2-15. E: 42.X. Indoor unit heat exchanger sensor error (Indoor unit) →ired remote Indicator Error code E: 42 controller Indoor unit main PCB →hen heat exchanger temperature thermistor open or Detective actuator Heat exchanger temperature short circuit is detected. thermistor Connector connection failure Forecast of cause Thermistor failure...
  • Page 102 2-16. E: 51.X. Indoor unit fan motor error (Indoor unit) →ired remote Indicator Error code E: 51 controller Main PCB →hen the actual rotation number of the indoor unit fan Detective actuator Indoor unit motor is below 1/3 of the target rotation number Fan motor continuously for more than 56 seconds.
  • Page 103 2-17. E: 53.X. Drain pump error (Indoor unit) →ired remote Indicator Error code E: 53 controller Indoor unit main PCB Detective actuator →hen Float switch is ON for more than 3 minutes. Float switch Float switch failure Shorted connector/wire failure Forecast of cause Main PCB failure Drain pump failure...
  • Page 104 2-18. E: 58.X. Intake grille error (Indoor unit) →ired remote Indicator Error code E: 58 controller Indoor unit main PCB →hen the Micro switch is detected open while running Detective actuator the compressor. Micro switch Micro switch failure Forecast of cause Shorted connector/wire Main PCB failure Check point 1.
  • Page 105 2-19. E: 62.X. Outdoor unit main PCB error (Outdoor unit) →ired remote Indicator Error code E: 62 controller Access to EEPROM failed due to some cause after Detective actuator Outdoor unit Main PCB outdoor unit started. External cause (Noise, temporary open, voltage drop) Forecast of cause Main PCB failure Check point 1.
  • Page 106 2-20. E: 63.X. Inverter error (Outdoor unit) →ired remote Indicator Error code E: 63 controller Detective actuator Outdoor unit Inverter PCB Error information received from inverter PCB Forecast of cause External cause Power supply to inverter PCB wiring disconnection or open Inverter PCB failure Outdoor unit main PCB failure...
  • Page 107 2-21. E: 64.X. PFC circuit error (Outdoor unit) →ired remote Indicator Error code E: 64 controller • →hen inverter input DC voltage is higher than 425 V or lower than 80 V (for 18 model) or higher than 420 V for over 3 seconds (for 24/30/36 model), the Detective actuator Outdoor unit Main PCB...
  • Page 108 2-22. E: 65.X. Trip terminal L error (Outdoor unit) →ired remote Indicator Error code E: 65 controller →hen the signal from FO terminal (13—15) of IPM is “L” Detective actuator Outdoor unit Main PCB (0 V) during the compressor stopping. Forecast of cause Main PCB failure Check point 1.
  • Page 109 2-23. E: 71.X. Discharge thermistor error (Outdoor unit) →ired remote Indicator Error code E: 71 controller Outdoor unit main PCB →hen discharge pipe temperature thermistor open or Detective actuator short circuit is detected at power on or while running the Discharge pipe temperature compressor thermistor...
  • Page 110 2-24. E: 72.X. Compressor thermistor error (Outdoor unit) →ired remote Indicator Error code E: 72 controller Outdoor unit main PCB →hen compressor temperature thermistor open or short Detective actuator circuit is detected at power on or while running the Compressor temperature thermistor compressor Connector failure Forecast of cause...
  • Page 111 2-25. E: 73.X. Heat exchanger (Middle/Outlet) temperature thermistor error (Outdoor unit) →ired remote Indicator Error code E: 73 controller Heat exchanger liquid temperature • Heat exchanger liquid temperature thermistor short thermistor or open detected Detective actuator Heat exchanger middle • Heat exchanger middle temperature thermistor temperature thermistor short or open detected...
  • Page 112 2-26. E: 74.X. Outdoor temperature thermistor error (Outdoor unit) →ired remote Indicator Error code E: 74 controller Outdoor unit main PCB →hen outdoor temperature thermistor open or short Detective actuator circuit is detected at power on or while running the Outdoor temperature thermistor compressor Connector failure...
  • Page 113 2-27. E: 77.X. Heat sink thermistor error (Outdoor unit) (24/30/36 model) →ired remote Indicator Error code E: 77 controller Detective actuator Heat sink temperature thermistor Heat sink temperature thermistor short or open detected Connector failure Forecast of cause Thermistor failure Inverter PCB failure Check point 1.
  • Page 114 2-28. E: 84.X. Current sensor error (Outdoor unit) →ired remote Indicator Error code E: 84 controller Main PCB →hen input current sensor has detected 0 A, while inverter compressor is operating at higher than 50 rps, Detective actuator Outdoor unit after 1 minute upon starting the compressor.
  • Page 115 Check point 1-2. Check external cause at Indoor and Outdoor (Voltage drop or Noise) • Instant drop: Check if there is a large load electric apparatus in the same circuit. • Momentary power failure: Check if there is a defective contact or leak current in the power sup- ply circuit.
  • Page 116 2-29. E: 86.X. High pressure switch error (Outdoor unit) (24/30/36 model) →ired remote Indicator Error code E: 86 controller Outdoor unit main PCB →hen pressure switch open is detected in 10 seconds Detective actuator after the power is turned on. High pressure switch High pressure switch connector disconnection or open Forecast of cause...
  • Page 117 2-30. E: 94.X. Trip detection (Outdoor unit) →ired remote Indicator Error code E: 94 controller Inverter PCB Protection stop by over-current generation after inverter compressor start processing completed generated Main PCB consecutively 10 times. Detective actuator Outdoor unit NOTE: The number of generations is reset when the Compressor compressor starts up.
  • Page 118 2-31. E: 95.X. Compressor motor control error (Outdoor unit) →ired remote Indicator Error code E: 95 controller Inverter PCB "Protection stop by "overcurrent generation at inverter compressor starting" restart" generated consecutively 50 Main PCB Detective actuator Outdoor unit times x 3 sets (total 150 times) (for 18 model) or 10 Compressor times x 3 sets (total 30 times) (for 24/30/36 model).
  • Page 119 2-32. E: 97.X. Outdoor unit fan motor error (Outdoor unit) →ired remote Indicator Error code E: 97 controller Inverter PCB 1. →hen outdoor fan rotation speed is less than 100 rpm in 20 seconds after fan motor starts, fan motor Main PCB stops.
  • Page 120 Check point 4. Check output voltage of inverter PCB Check outdoor unit circuit diagram and the voltage. (Measure at inverter PCB side connector) FAN MOTOR BLACK WHITE YELLOW BROWN NOTE: For details of wiring diagram, refer to "→iring diagrams" in Chapter 2. TECHNICAL DATA AND PARTS LIST on page 02-27.
  • Page 121 2-33. E: 99.X. 4-way valve error (Outdoor unit) →ired remote Indicator Error code E: 99 controller Indoor unit main PCB →hen the indoor heat exchanger temperature is compared with the room temperature, and either Heat exchanger temperature following condition is detected continuously two times, thermistor the compressor stops.
  • Page 122 Check point 4. Check the solenoid coil and 4-way valve NOTE: Refer solenoid coil and 4-way valve in "Service parts information" on page 03-81. • Solenoid coil Remove P60 from PCB and check the resistance value of coil. Resistance value is 1.970 kΩ (at 68°F [20°C]).
  • Page 123 2-34. E: A1.X. Discharge temperature error (Outdoor unit) →ired remote Indicator Error code E: A1 controller Outdoor unit main PCB Protection stop by discharge temperature ≥ 230°F Detective actuator (110°C) during compressor operation generated 2 times Discharge temperature thermistor within 24 hours. 3-way valve not opened EEV or capillary tube defective, strainer clogged Outdoor unit operation failure, foreign matter on heat...
  • Page 124 Check point 5. Check the refrigerant amount Check the refrigerant leakage. Check point 6. Replace the main PCB If check point 1 to 5 do not improve the symptom, replace the main PCB. - (03-62) - 2-34. E: A1.↓. Discharge temperature error (Outdoor unit) 2.
  • Page 125 2-35. E: A3.X. Compressor temperature error (Outdoor unit) →ired remote Indicator Error code E: A3 controller Outdoor unit main PCB Protection stop by compressor temperature ≥ 226.4°F Detective actuator (108°C) during compressor operation generated 2 times Compressor temperature thermistor within 24 hours. 3-way valve not opened EEV defective, strainer clogged Outdoor unit operation failure, foreign matter on heat...
  • Page 126 Check point 5. Check the refrigerant amount Check the refrigerant leakage. Check point 6. Replace the main PCB If check point 1 to 5 do not improve the symptom, replace the main PCB. - (03-64) - 2-35. E: A3.↓. Compressor temperature error (Outdoor unit) 2.
  • Page 127 2-36. E: AC.X. Heat sink temperature error (Outdoor unit) (24/30/36 model) →ired remote Indicator Error code E: AC controller Outdoor unit inverter PCB Protection stop by heat sink temperature ≥ 176°F (80°C) Detective actuator during heat sink operation generated 2 times within 24 Heat sink temperature thermistor hours.
  • Page 128: Troubleshooting Without Error Code

    3. Troubleshooting without error code 3-1. Indoor unit—No power Power supply failure Forecast of cause External cause Electrical components defective Check point 1. Check installation condition • Isn’t the breaker down? • Check loose or removed connection cable. -> If abnormal condition is found, correct it by referring to the installation manual or the “DESIGN & TECHNICAL MANUAL”.
  • Page 129: Outdoor Unit-No Power

    3-2. Outdoor unit—No power Power supply failure Forecast of cause External cause Electrical components defective Check point 1. Check installation condition • Is the circuit breaker on or off? • Check loose or removed connection cable. If abnormal condition is found, correct it by referring to the installation manual or the DESIGN & TECHNICAL MANUAL.
  • Page 130: No Operation (Power Is On)

    3-3. No operation (Power is on) Setting/ Connection failure Forecast of cause External cause Electrical components defective Check point 1. Check indoor and outdoor installation condition • Indoor unit: – Check incorrect wiring between indoor unit and remote controller. – Check if there is an open cable connection.
  • Page 131: No Cooling/No Heating

    3-4. No cooling/No heating Indoor unit error Outdoor unit error Forecast of cause Effect by surrounding environment Connection pipe/Connection wire failure Refrigeration cycle failure Check point 1. Check Indoor unit • Does Indoor unit fan run in the HIGH mode? •...
  • Page 132 NOTES: • Strainer normally does not have temperature difference between inlet and outlet as shown be- low. Pipe (In) Pipe (Out) • If there is a difference like shown below, there is a possibility of inside clogged. In this case, re- place the strainer.
  • Page 133: Abnormal Noise

    3-5. Abnormal noise Abnormal installation (indoor unit/outdoor unit) Forecast of cause Fan failure (indoor unit/outdoor unit) Compressor failure (outdoor) Diagnosis method when abnormal noise is occurred Abnormal noise is coming from Outdoor Abnormal noise is coming from Indoor unit. unit. (Check and correct followings) (Check and correct followings) •...
  • Page 134: Ater Leaking

    3-6. Water leaking Erroneous installation Forecast of cause Drain hose failure Diagnosis method when water is spitting Diagnosis method when water leak occurs • Is main unit installed in stable condi- tion? Is the filter clogged? • Is main unit broken or deformed at the time of transportation or maintenance? MPa MPa •...
  • Page 135: Troubleshooting With Error Code (For Wireless Lan Adapter)

    4. Troubleshooting with error code (For wireless LAN adapter) 4-1. E: 18.X. External communication error between indoor unit and wireless LAN adapter Operation indicator 1 time flash Timer indicator 8 time flash Economy indicator Continuous flash Indoor unit Indicator →ireless LAN Flashing slowly indicator Error code...
  • Page 136: Network Communication Error Between Wireless Lan Router And Wireless Lan Adapter

    4-2. Network communication error between wireless LAN router and wireless LAN adapter Operation indicator No indication Timer indicator No indication Economy indicator No indication Indoor unit Indicator →ireless LAN Flashing slowly indicator Error code — Mobile app No indication →ireless LAN router →hen the not connection between wireless LAN adapter and wireless LAN router.
  • Page 137 Check point 4. Replace wireless LAN adapter. If check point 3 do not improve the symptom, replace the wireless LAN adapter and cancel the reg- istration of air conditioner on the Mobile app. After replacing the adapter, perform the pairing on the Mobile app. For the method of the Mobile app, refer to "Mobile app setting method"...
  • Page 138: E: 18.↓. Communication Error

    4-3. E: 18.X. Communication error Operation indicator 1 time flash Timer indicator 8 time flash Economy indicator Continuous flash Indoor unit Indicator →ireless LAN Flashing slowly indicator Error code E: 18 Mobile app E: 18.1 →ireless LAN router →hen the external communication error between indoor unit and wireless LAN adapter and network →ireless LAN adapter PCB communication error between wireless LAN router and...
  • Page 139 Check point 4. Check the connection cable Check the connection cable on the wireless LAN router. -> If there is loose connector, open cable or mis-wiring, correct it. Check point 5. Check the connection status. Check the connection status to the Internet and wireless LAN router. ->...
  • Page 140: E: 18.↓. →Ireless Lan Adapter Non-Energized

    4-4. E: 18.X. Wireless LAN adapter non-energized Operation indicator 1 time flash Timer indicator 8 time flash Economy indicator Continuous flash Indoor unit Indicator →ireless LAN No indication indicator Error code E: 18 Mobile app No indication Indoor unit controller PCB →hen the voltage (DC 12 V) does not output from the Detective actuator controller PCB.
  • Page 141: Mobile App Setting Method

    4-5. Mobile app setting method ¢ Air conditioner delete method →hen the wireless LAN adapter is replaced, delete of all air conditioner is necessary on the mobile app. Launch the mobile app. Tap the icon to display the Setting screen. Tap the “Air conditioner editing”.
  • Page 142 Tap the air conditioner to be deleted. Tap the Delete button. Tap the OK button. Deletion of the air conditioner registered in the mobile app is completed. - (03-80) - 4-5. Mobile app setting method 4. Troubleshooting with error code (For wireless LAN adapter)
  • Page 143: Service Parts Information

    5. Service parts information 5-1. Compressor Diagnosis method of compressor (If outdoor unit LED displays error, refer to troubleshooting) Does not start up Stops soon after starting up Abnormal noise Check if vibration noise by Is there open or loose con- Is there open or loose con- loose bolt or contact noise of nection cable?
  • Page 144: Inverter Compressor

    5-2. Inverter compressor ¢ Model: AOUH18KUAS1 Check point 1. Check connection • Check terminal connection of compressor (loose or incorrect wiring) W(C) V(S) (BLACK) (WHITE) Main PCB U(R) (RED) • Check terminal connection of main PCB (loose or incorrect wiring) Main PCB W400(U) W401(V) W402(W)
  • Page 145 ¢ Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 Check point 1. Check the terminal connection. • Check the following terminal connections of the compressor. (Loosening or incorrect wiring.) S (V) C (W) R (U): Red S (V): →hite Main PCB C (W): Black R (U) •...
  • Page 146: Outdoor Unit Electronic Expansion Valve (Eev)

    5-3. Outdoor unit Electronic Expansion Valve (EEV) ¢ Model: AOUH18KUAS1 Check point 1. Check connections Check connection of connector. (Loose connector or open cable) NOTE: For details of wiring diagram, refer to "→iring diagrams" in Chapter 2. TECHNICAL DATA AND PARTS LIST on page 02-27. Check point 2.
  • Page 147 Check point 6. Check strainer • Strainer normally does not have temperature difference between inlet and outlet as shown be- low. Pipe (In) Pipe (Out) • If there is a difference like shown below, there is a possibility of inside clogged. In this case, replace the strainer.
  • Page 148 ¢ Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 Check point 1. Check connections Check connection of connector. (Loose connector or open cable) NOTE: For details of wiring diagram, refer to "→iring diagrams" in Chapter 2. TECHNICAL DATA AND PARTS LIST on page 02-27. Check point 2.
  • Page 149 Check point 6. Check strainer • Strainer normally does not have temperature difference between inlet and outlet as shown be- low. Pipe (In) Pipe (Out) • If there is a difference like shown below, there is a possibility of inside clogged. In this case, replace the strainer.
  • Page 150: Indoor Unit Fan Motor

    5-4. Indoor unit fan motor Check point 1. Check rotation of fan Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor) If fan or bearing is abnormal, replace it. Check point 2. Check resistance of indoor fan motor Refer to below.
  • Page 151: Outdoor Unit Fan Motor

    5-5. Outdoor unit fan motor Check point 1. Check rotation of fan Rotate the fan by hand when operation is off. (Check if fan is caught, dropped off or locked motor) If fan or bearing is abnormal, replace it. Check point 2. Check resistance of outdoor fan motor Refer to below.
  • Page 152: 4-Way Valve Coil (Solenoid Coil)/4-Way Valve

    5-7. 4-way valve coil (solenoid coil)/4-way valve Check point 1. Check connection • Check the connection of connector P60. BLACK SOLENOID COIL BLACK Check Point 2 : Check solenoid coil Remove P60 from PCB and check the resistance value of coil. Resistance value ≈...
  • Page 153: Thermistor Resistance Values

    6. Thermistor resistance values 6-1. Indoor unit ¢ Room temperature thermistor Temperature °F (°C) Resistance (kΩ) Voltage (V) 14.0 (-10.0) 58.25 0.73 23.0 (-5.0) 44.03 0.93 32.0 (0.0) 33.62 1.15 41.0 (5.0) 25.92 1.39 50.0 (10.0) 20.17 1.66 59.0 (15.0) 15.84 1.94 68.0 (20.0)
  • Page 154: Outdoor Unit

    6-2. Outdoor unit ¢ Heat sink thermistor  Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 Temperature °F (°C) Resistance (kΩ) Voltage (V) -22.0 (-30.0) 94.26 0.08 -12.0 (-25.0) 67.95 0.11 -4.0 (-20.0) 49.62 0.15 5.0 (-15.0) 36.68 0.20 14.0 (-10.0) 27.42 0.26 23.0 (-5.0) 20.73 0.34...
  • Page 155 ¢ Discharge temperature thermistor Temperature °F (°C) Resistance (kΩ) Voltage (V) -22.0 (-30.0) 1,013.11 0.06 -12.0 (-25.0) 729.09 0.09 -4.0 (-20.0) 531.56 0.12 5.0 (-15.0) 392.31 0.16 14.0 (-10.0) 292.91 0.21 23.0 (-5.0) 221.09 0.28 32.0 (0.0) 168.60 0.36 41.0 (5.0) 129.84 0.46 50.0 (10.0)
  • Page 156 ¢ Compressor temperature thermistor Temperature °F (°C) Resistance (kΩ) Voltage (V) -22.0 (-30.0) 1,013.11 0.06 -12.0 (-25.0) 729.09 0.09 -4.0 (-20.0) 531.56 0.12 5.0 (-15.0) 392.31 0.16 14.0 (-10.0) 292.91 0.21 23.0 (-5.0) 221.09 0.28 32.0 (0.0) 168.60 0.36 41.0 (5.0) 129.84 0.46 50.0 (10.0)
  • Page 157 ¢ Heat exchanger temperature thermistor Temperature °F (°C) Resistance (kΩ) Voltage (V) -22.0 (-30.0) 95.57 0.24 -12.0 (-25.0) 68.89 0.32 -4.0 (-20.0) 50.31 0.43 5.0 (-15.0) 37.19 0.57 14.0 (-10.0) 27.81 0.73 23.0 (-5.0) 21.02 0.92 32.0 (0.0) 16.05 1.14 41.0 (5.0) 12.38 1.39...
  • Page 158 ¢ Outdoor temperature thermistor Temperature °F (°C) Resistance (kΩ) Voltage (V) -22.0 (-30.0) 224.33 0.73 -12.0 (-25.0) 159.71 0.97 -4.0 (-20.0) 115.24 1.25 5.0 (-15.0) 84.21 1.56 14.0 (-10.0) 62.28 1.90 23.0 (-5.0) 46.58 2.26 32.0 (0.0) 35.21 2.61 41.0 (5.0) 26.88 2.94 50.0 (10.0)
  • Page 159: Control And Functions

    4. CONTROL AND FUNCTIONS 2024.11.21 SR_CH04_AB018ES_01...
  • Page 160 CONTENTS 4. CONTROL AND FUNCTIONS 1. Rotation number control of compressor...........04-1 1-1. Cooling operation ......................04-1 1-2. Heating operation ......................04-3 1-3. Dry operation ........................04-4 1-4. Rotation number of compressor at normal start-up ............04-5 1-5. Limitation of compressor rotation number by outdoor temperature.........04-8 2.
  • Page 161: Rotation Number Control Of Compressor

    1. Rotation number control of compressor 1-1. Cooling operation A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference or variation between a set temperature and present room temperature, and controls the operation rotation number of the compressor. •...
  • Page 162 • Limit of maximum speed based on outdoor temperature Outdoor temperature rises Outdoor temperature drops 96.8°F A zone 93.2°F (36°C) (34°C) 89.6°F B zone 86.0°F (32°C) (30°C) 69.8°F C zone 66.2°F (21°C) (19°C) 53.6°F D zone 50.0°F (12°C) (10°C) 35.6°F E zone 32.0°F (2°C)
  • Page 163: Heating Operation

    1-2. Heating operation A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or variation between setting temperature and present room temperature, and controls operation rota- tion number of compressor. • If the room temperature is 11°F (6.0°C) lower than a set temperature, the operation rotation num- ber of compressor will attain to maximum performance.
  • Page 164: Dry Operation

    1-3. Dry operation The rotation number of compressor shall change according to the temperature, set temperature, and room temperature variation which the room temperature sensor of the indoor unit has detected as shown in the table below. Zone is defined by set temperature and room temperature. •...
  • Page 165: Rotation Number Of Compressor At Normal Start-Up

    1-4. Rotation number of compressor at normal start-up ¢ Model: AOUH18KUAS1 Rotation number of compressor soon after starting is controlled as below. Rotation number VI Rotation number V Rotation number IV Rotation number III Rotation number II Rotation number I Time 1 Time 2 Time 3...
  • Page 166 ¢ Model: AOUH24KUAS1 Rotation number of compressor soon after starting is controlled as below. Rotation number VIII Rotation number VII Rotation number VI Rotation number V Rotation number IV Rotation number III Rotation number II Rotation number I Time 1 Time 2 Time 3 Time 4...
  • Page 167 ¢ Models: AOUH30KUAS1 and AOUH36KUAS1 Rotation number of compressor soon after starting is controlled as below. Rotation number X Rotation number IX Rotation number VIII Rotation number VII Rotation number VI Rotation number V Rotation number IV Rotation number III Rotation number II Rotation numbery I Time 1...
  • Page 168 1-5. Limitation of compressor rotation number by outdoor temperature ¢ Model: AOUH18KUAS1 The minimum rotation number of compressor is limited by outdoor temperature as below. • Cooling/Dry mode F zone 100.4°F (38°C) E zone 66.2°F (19°C) D zone 50.0°F (10°C) C zone 32.0°F (0°C)
  • Page 169 • Heating mode F zone 66.2°F (19°C) E zone 41.0°F (5°C) D zone 32.0°F (0°C) C zone 5.0°F (-15°C) B zone -13.0°F (-25°C) A zone Unit: rps Limitation of compressor rotation number Outdoor temperature zone AOUH18KUAS1 A zone B zone C zone D zone E zone...
  • Page 170: Limitation Of Compressor Rotation Number By Outdoor Temperature

    ¢ Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 The minimum rotation number of compressor is limited by outdoor temperature as below. • Cooling/Dry mode K zone 125.6°F (52°C) J zone 122.0°F (50°C) I zone 114.8°F (46°C) H zone 87.8°F (31°C) G zone 69.8°F (21°C) F zone...
  • Page 171 • Heating mode I zone 68.0°F (20°C) H zone 60.8°F (16°C) G zone 53.6°F (12°C) F zone 44.6°F (7°C) E zone 35.6°F (2°C) D zone 19.4°F (-7°C) C zone 14.0°F (-10°C) 5.0°F B zone (-15°C) A zone Unit: rps Limitation of compressor frequency Outdoor temperature zone AOUH30KUAS1 AOUH24KUAS1...
  • Page 172: Auto Changeover Operation

    2. Auto changeover operation →hen the air conditioner is set to AUTO mode by remote controller, operation starts in the optimum mode from among heating, cooling, dry and monitoring modes. During operation, the optimum mode is automatically switched in accordance with temperature changes. The temperature can be set be- tween 64.4 °F (18 °C) and 86.0 °F (30 °C) in 1.0 °F (0.5 °C) steps.
  • Page 173: Operation Flow Chart

    Operation flow chart Start Ts: Setting temperarure Monitor mode Room temp. > Ts+3.6°F(2°C)? Room temp. < Ts-3.6°F(2°C)? Middle zone Auto change over is second or more? Operation mode before the monitor mode is cooling mode? Operation mode of Heating operation Cooling operation outdoor unit: Cooling? Thermostat remains...
  • Page 174: Fan Control

    3. Fan control Tr: Room temperature Ts: Setting temperature 3-1. Indoor fan control ¢ Fan speed Indoor fan speed is defined as below. Speed (rpm) Operation mode Fan mode ABUH18KUAS ABUH24KUAS ABUH30KUAS ABUH36KUAS HIGH 1,090 1,090 MED+ 1,000 1,020 LO→ Heating QUIET Cool air...
  • Page 175 ¢ Dry operation During dry operation, fan speed setting can not be changed as shown in “Fan speed” above. ¢ Heating operation Switch the airflow AUTO, and the indoor fan motor will run according to a room temperature, as be- low.
  • Page 176 • MIN. HEAT operation Indoor heat exchanger Indoor heat exchanger temperature rises temperature drops AUTO 102.2°F (39°C) 93.2°F (34°C) ¢ Moisture return prevention control (cooling and dry mode) Switch the airflow AUTO at cooling mode, and the indoor fan motor will run as shown below. Compressor Indoor fan setting airflow...
  • Page 177: Outdoor Fan Control

    3-2. Outdoor fan control ¢ Outdoor fan motor This outdoor unit has a DC fan motor. (Control method is different between AC and DC motors.) ¢ Fan speed  Model: AOUH18KUAS1 Fan speed is defined by outdoor temperature and compressor frequency. •...
  • Page 178  Model: AOUH24KUAS1 Fan speed is defined by outdoor temperature and compressor frequency. Unit: rpm Fan step Cooling or dry Heating — — — S-HIGH — • →hen the compressor frequency increases, the outdoor fan speed also changes to the higher speed.
  • Page 179  Models: AOUH30KUAS1 and AOUH36KUAS1 Fan speed is defined by outdoor temperature and compressor frequency. Unit: rpm Fan step Cooling or dry Heating — — — S-HIGH — • →hen the compressor frequency increases, the outdoor fan speed also changes to the higher speed.
  • Page 180: Louver Control

    4. Louver control 4-1. Individual louver control Each time the button is pressed, the air direction range will change as below: • Remote controller display is not changed. • Vertical airflow direction is set automatically as shown, in accordance with the type of operation selected.
  • Page 181: Timer Operation Control

    5. Timer operation control 5-1. Wireless remote control On/Off timer Program timer Sleep timer Weekly timer ○ ○ ○ — ¢ On/Off timer • Off timer: →hen the clock reaches the set timer, the air conditioner will be turned off. Operation mode Stop mode Set time of timer...
  • Page 182: Sleep Timer

    ¢ Sleep timer If the sleep timer is set, the room temperature is monitored and the operation is stopped auto- matically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time on. •...
  • Page 183: Ired Remote Control

    5-2. Wired remote control Temperature On/Off timer Program timer Sleep timer Weekly timer Setback Timer ○ ○ ○ ○ ○ ¢ On/Off timer • Off timer: →hen the clock reaches the set timer, the air conditioner will be turned off. Operation mode Stop mode Set time of timer...
  • Page 184: Weekly Timer

    ¢ Sleep timer If the sleep timer is set, the room temperature is monitored and the operation is stopped auto- matically. If the operation mode or the set temperature is change after the sleep timer is set, the operation is continued according to the changed setting of the sleep timer from that time on. •...
  • Page 185: Temperature Setback Timer

    ¢ Temperature Setback Timer • The temperature setback timer only changes the set temperature for 7 days, it cannot be used to start or stop air conditioner operation. • The temperature setback timer can be set to operate up to two times per day but only one temperature setting can be used.
  • Page 186: Defrost Operation Control

    6. Defrost operation control Tn: Outdoor unit heat exchanger temperature Ta: Outdoor temperature Tn10: Temperature at 10 minutes after compressor start Tnb: Temperature before 5 minutes Triggering condition • The defrost operation starts when outdoor unit heat exchanger temperature sensor detects the temperature lower than the values shown below.
  • Page 187: Defrost Operation In Heating Operation Stopped

    6-1. Defrost operation in heating operation stopped If the outdoor unit is frosted when stopping the heating operation, it stops after performing the auto- matic defrosting operation. In this time, if the indoor unit operation lamp flashes slowly (6 sec on/2 sec off), the outdoor unit al- low the heat exchanger to defrost, and then stop.
  • Page 188: Various Control

    7. Various control 7-1. Auto restart →hen the power was interrupted by a power failure etc. during operation, the operation contents at that time are memorized and when the power is recovered, operation is automatically started with the memorized operation contents. Operation contents memorized when the power is interrupted Operation mode Setting temperature...
  • Page 189: Compressor Preheating Operation

    7-5. Compressor preheating operation CAUTION To perform the preheat operation, turn on the power for the outdoor unit at least 12 hours before the operation. Especially in cold climate regions, the compressor may fail if the outdoor unit is on for less than 12 hours.
  • Page 190: External Electrical Heater Control

    7-6. External electrical heater control The external electrical heater is operated as below. When the room Ts: Setting temperature temperature rises Heater : Off -1.8°F (Ts -1°C) -5.4°F (Ts -3°C) Heater : On -18.0°F (Ts -10°C) -21.6°F (Ts -12°C) Heater : Off When the room temperature drops NOTES:...
  • Page 191: Drain Pump Control

    7-8. Drain pump control ¢ Drain control for defrosting operation  During cooling or dry mode • →hen the compressor starts, the drain pump starts simultaneously. • The drain pump operates continuously for 3 minutes after the compressor is turned off. Compressor Drain pump 3 minutes...
  • Page 192  During heating mode or fan mode and when operation is stopped • Triggering condition Drain pump is turned on at the same time that the float switch is turned on. • Operation details →hen the float switch turns on continuously for 3 minutes, "failure indication" operates. There- after, even if the float switch turns off, the "failure indication"...
  • Page 193: Prevention To Restart For 3 Minutes (3 Minutes St)

    7-9. Prevention to restart for 3 minutes (3 minutes st) →hen the compressor fails to start for the number of times below, it does not enter operation status for 3 minutes. • Model: AOUH18KUAS1 Retry number Retry set number • Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 Retry number Retry set number →hen the compressor fails to start in the retry set number above, the compressor is stopped.
  • Page 194: Unit Status Monitoring And The Detected Value Indication

    7-12. Unit status monitoring and the detected value indication The wired remote controller can monitor the indoor and outdoor units' status and display the detect- ed result as a relevant ID. For details of the display method, refer to the Chapter of “Display Sensor Values” in the Installation Manual of →ired Remote Controller (Touch Panel).
  • Page 195 Available Sensor ID Sensor ID Item Unit Remarks 0: Off, 1: On NOTE: The value is output even if Error On/Off (External output) 00: — the function setting or rotary switch is not set. 0: Off, 1: On Indoor unit fan interlocking On/Off NOTE: The value is output even if 00: —...
  • Page 196 Available Sensor ID Sensor ID Item Unit Remarks Outdoor unit fan 2 total operating 11: h hours Outdoor low noise input (External 00: — 0: Off, 1: On input) 0: Off 1: Mode 4 (100%) 2: Mode 3 (75%) Outdoor peak cut (External input) 00: —...
  • Page 197: Various Protections

    8. Various protections 8-1. Discharge gas temperature over-rise prevention control The discharge gas temperature sensor (discharge thermistor: outdoor unit side) detects the dis- charge gas temperature. • →hen the discharge temperature becomes higher than the trigger condition, the rotation number of compressor is decreased as the table below, and it continues to decrease until the discharge tem- perature becomes lower than the trigger condition.
  • Page 198: Current Release Control

    8-3. Current release control The rotation number of compressor is controlled so that the outdoor unit input current does not ex- ceeds current limit value set according to the outdoor temperature. The rotation number of compressor returns according to the operation mode, when the current be- comes lower than the release value.
  • Page 199: Compressor Temperature Protection

    8-4. Compressor temperature protection →hen the compressor temperature sensor detects higher than the trigger condition below, the com- pressor is stopped. →hen the compressor temperature sensor detects the release condition, the pro- tection is released. Trigger condition 226.4°F (108°C) 176.0°F (80°C) Release condition (3 minutes after compressor stop) 8-5.
  • Page 200: High Temperature And High Pressure Release Control

    8-7. High temperature and high pressure release control The compressor is controlled as follows. ¢ Model: AOUH18KUAS1 • Cooling mode Indoor unit heat exchanger Indoor unit heat exchanger temperature rises temperature drops 141.8°F (61°C) Zone A 140.0°F (60°C) 138.2°F (59°C) Zone B 129.2°F (54°C) Zone C...
  • Page 201 ¢ Models: AOUH24KUAS1, AOUH30KUAS1, and AOUH36KUAS1 • Cooling mode Indoor unit heat exchanger Indoor unit heat exchanger temperature rises temperature drops 147.2°F (64°C) Zone A 140.0°F (60°C) 136.4°F (58°C) Zone B Zone C Stable zone Zone D Zone Operation Zone A Compressor is stopped.
  • Page 202 - (04-42) - 8-7. High temperature and high pressure release control 8. Various protections...
  • Page 203 5. FIELD WORKING 2024.11.21 SR_CH05_AB018ES_01...
  • Page 204 CONTENTS 5. FIELD WORKING 1. Function settings (for indoor unit).............05-1 1-1. Function settings by using remote controller ..............05-1 2. Function settings (for 24–36 outdoor units) ...........05-11 2-1. Control PCB and switch buttons location..............05-11 2-2. Local setting procedure ....................05-13 3. External input and output (for indoor unit) ..........05-15 3-1.
  • Page 205: Function Settings (For Indoor Unit)

    1. Function settings (for indoor unit) To adjust the functions of this product according to the installation environment, various types of function settings are available. NOTE: Incorrect settings can cause a product malfunction. 1-1. Function settings by using remote controller Some function settings can be changed on the remote controller.
  • Page 206: Filter Sign

    1) Filter sign Select appropriate intervals for displaying the filter sign on the indoor unit according to the estimated amount of dust in the air of the room. If the indication is not required, select "No indication" (03). Function number Setting value Setting description Factory setting...
  • Page 207: Factory Setting

    4) Room temperature control for indoor unit sensor Depending on the installed environment, correction of the room temperature sensor may be re- quired. Select the appropriate control setting according to the installed environment. The temperature of the room temperature sensor is corrected as follows: Corrected temp.
  • Page 208: Auto Restart

    5) Room temperature control for wired remote controller sensor Depending on the installed environment, correction of the wire remote temperature sensor may be required. Select the appropriate control setting according to the installed environment. To change this setting, set Function 42 to “Both” (01). Ensure that the Thermo Sensor icon is displayed on the remote controller screen.
  • Page 209 8) Remote controller custom code (Only for wireless remote controller) The indoor unit custom code can be changed. Select the appropriate custom code. Function number Setting value Setting description Factory setting ♦ 9) External input control “Operation/Stop” mode or “Forced stop” mode can be selected. Function number Setting value Setting description...
  • Page 210 12) Switching functions for external output terminal Functions of the external output terminal can be switched. For details, refer to “External input and output”. Function number Setting value Setting description Factory setting Operation status ♦ 01—04 Cooling thermostat On Heating operation Operation/Stop 07—08 Cooling thermostat On...
  • Page 211 14) Operating temperature switching of external heaters Sets the temperature conditions when the external heater is ON. For details, refer to “External heater output” in "Details of control output function" on page 05-25. Setting description Setting value of function 61: Function Setting Factory...
  • Page 212 16) Outdoor temperature zone boundary temperature B Setting required if changing of the outdoor temperature setting for heat pump only zone is required when auxiliary heater control by outdoor temperature 1 and 3 is performed on the indoor unit. For details, refer to “External heater output” in "Details of control output function"...
  • Page 213 19) Standby time for auxiliary equipment operation Sets the standby time until the auxiliary equipment operation starts during primary equipment opera- tion. For details, refer to "Details of control output function" on page 05-25. Function number Setting value Setting description Factory setting Disable ♦...
  • Page 214 24) Fixed operation mode switching Sets the operation mode to heat pump, heating only, or cooling only. Function number Setting value Setting description Factory setting Heat pump ♦ Heating only Cooling only - (05-10) - 1-1. Function settings by using remote controller 1.
  • Page 215: Function Settings (For 24-36 Outdoor Units)

    2. Function settings (for 24–36 outdoor units) Perform appropriate function setting locally according to the installation environment. NOTE: Incorrect settings can cause a product malfunction. CAUTION • Before setting up the switch buttons, discharge the static electricity from your body. •...
  • Page 216: Switch Buttons And The Functions

    ¢ Switch buttons and the functions LED lamps S134 S133 S132 S131 S130 Switch buttons LED lamp Function or operation method Lights on while power on. (1) PO→ER/MODE Green Blinks to show the local setting on the outdoor unit or the error code. (2) ERROR Blinks during error operation.
  • Page 217: Local Setting Procedure

    2-2. Local setting procedure NOTE: Before performing the function setting, be sure to stop the operation of the air conditioner. ¢ Low noise mode Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”. After confirming the LED lamp of PO→ER/MODE blinks 9 times, press the ENTER switch but- ton (S132).
  • Page 218: Peak Cut Mode

    ¢ Peak cut mode Press the MODE switch button (S134) for 3 seconds or more to switch to “Local setting mode”. After confirming the LED lamp of PO→ER/MODE blinks 9 times, press the ENTER switch but- ton (S132). PUMP POWER LOW NOISE PEAK CUT DOWN...
  • Page 219: External Input And Output (For Indoor Unit)

    3. External input and output (for indoor unit) CN48 (Float SW) (IR receiver) Rotary switch CN65 Terminal (External in) CN75 CN47 CN106 (External out) (Drain pump) Fig. Indoor unit PCB Fig. External input and output PCB Connecting point Input/Output Function Input select Input signal Operation/Stop...
  • Page 220: External Input

    3-1. External input • “Operation/Stop” mode or "Forced stop" mode can be selected with function setting of indoor unit. • A twisted pair cable (22 A→G) should be used. Maximum length of cable is 492 ft (150 m). • Use an external input and output cable with appropriate external dimension, depending on the number of cables to be installed.
  • Page 221: Input Signal Type

    ¢ Input signal type • Indoor unit Input signal type is only "Edge". Edge • External Input and Output PCB The input signal type can be selected. Signal type (edge or pulse) can be switched by the DIP switch 2 (S→2) on the External Input and Output PCB.
  • Page 222: External Output

    3-2. External output Use an external output cable with appropriate external dimension, depending on the number of ca- bles to be installed. ¢ Indoor unit • A twisted pair cable (22 A→G) should be used. Maximum length of cable is 82 ft (25 m). •...
  • Page 223: Setting Of External Input And Output

    3-3. Setting of external input and output • Indoor unit Input Connecting point Function setting number 46 Function Operation/Stop mode 1 (Setting prohibited) Terminal Forced stop mode Operation/Stop mode 2 Output Connecting point Function setting number 60 Function Operation/Stop 01—04 Cooling thermostat On Heating thermostat On Operation/Stop...
  • Page 224 • External Input and Output PCB Switch setting Ex IN Ex OUT Rotary switch Edge Operation/Stop Not available Indoor unit fan Operation/Stop Error status operation Pulse Operation Stop status Indoor unit fan Forced External heater Not available Error status operation thermostat off output status...
  • Page 225: Details Of Control Input Function

    3-4. Details of control input function ¢ Operation/Stop mode 1 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Operation — Input of indoor unit Terminal Stop 46-00 Operation External Input and Edge...
  • Page 226 ¢ Forced stop • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Forced stop (R.C. disabled) — Input of indoor unit Terminal Normal (R.C. enabled) 46-02 Forced stop (R.C.
  • Page 227: Operation/Stop Mode

    ¢ Operation/Stop mode 2 • In the case of "Edge" input External Input and Output PCB Function External input Input signal Command setting Rotary switch Operation (R.C. enabled) — Input of indoor unit Terminal Stop (R.C. disabled) 46-03 Operation (R.C. enabled) External Input and Edge Ex IN 1...
  • Page 228: Forced Thermostat Off

    ¢ Forced thermostat off External Input and Output External input Input signal Command Rotary switch Thermostat off External Input and 2, B, C, D Ex IN 1 Output PCB Normal operation Thermostat off External Input and 4, 7, 8, A Ex IN 1 Output PCB Normal operation...
  • Page 229: Details Of Control Output Function

    3-5. Details of control output function ¢ Operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Operation 60-00 — Output of indoor unit CN47 60-06 Stop Operation External Input and — 1, B, C, D Ex OUT 1 Output PCB Stop...
  • Page 230: Indoor Unit Fan Operation Status

    ¢ Indoor unit fan operation status External Input and Function Output PCB External output Output signal Status setting Rotary switch Fan run 60-10 — Output of indoor unit CN47 Fan stop Fan run External Input and — 2, 3, 7, 8, B, D Ex OUT 2 Output PCB Fan stop...
  • Page 231: External Heater Output

    ¢ External heater output External Input and Function Output PCB External output Output signal Control setting Rotary switch Heater on 60-11 — Output of indoor unit CN47 Heater off Heater on External Input and — 2, 3, 4, 5, 7, 9, A, B, C Ex OUT 3 Output PCB Heater off...
  • Page 232: Operation

    • Inappropriate designing and installation of external heater may cause a fire by emitted heat from the external heater. • Fujitsu General Ltd. is not responsible for inappropriate designing or installation of external heating device. - (05-28) - 3-5. Details of control output function...
  • Page 233  Auxiliary equipment control by room temperature Auxiliary equipment control is switchable by room temperature. Auxiliary equipment switching is per- formed for each room temperature divided to following 3 zones. Zone A Ts +0.9°F (0.5 °C) Ts: Setting temperature Ts -0.9°F (-0.5 °C) Tr: Room temperature Zone B Zone C...
  • Page 234: Auxiliary Heater Control

     Auxiliary heater control 1 Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off • Error occurred •...
  • Page 235  Heat pump prohibition control Perform heating by external heater only. Indoor unit is continuous thermostat off. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 236  Auxiliary heater control by outdoor temperature 1 This control selects heat pump or external heater according to the outdoor temperature. →hen out- door temperature is high, the heating is performed by using heat pump only. Operation Condition Heater on Heater is on as shown in following diagram of heating temperature.
  • Page 237 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump Heat pump Combination zone only zone prohibition zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 238  Auxiliary heater control by outdoor temperature 2 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
  • Page 239 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition Combination zone zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 240  Auxiliary heater control by outdoor temperature 3 This control selects heat pump or external heater according to the outdoor temperature. Even when outdoor temperature is high, the heating is performed by using both of heat pump and external heater. Operation Condition Heater on...
  • Page 241 • Operation status Heat pump only zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 242  Auxiliary heat pump control • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. • Other than heating mode Heater off •...
  • Page 243  Auxiliary heat pump control by outdoor temperature 1 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 244 • Operation status 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Heat pump prohibition Combination zone zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 245  Auxiliary heat pump control by outdoor temperature 2 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 246 • Operation status Heat pump prohibition zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 247  Auxiliary heat pump control by outdoor temperature 3 • External heater output Operation Condition Heater on Heater is on as shown in following diagram of heating temperature. • Heater is off as shown in following diagram of heating temperature. •...
  • Page 248 • Operation status Heat pump prohibition zone 46.4°F (8°C) 42.8°F (6°C) Outdoor temperature (Factory setting) -0.4°F (-18°C) -4°F (-20°C) Combination zone Outdoor temperature zone * Comp. On/Off 12 V Heater * The outdoor temperature zone transition from one to another will stay in that zone for minimum of 30 min. NOTE: In following operations, compressor will be on in heat pump prohibition zone.
  • Page 249: Heating Thermostat On For Humidifier

    ¢ Heating thermostat on for humidifier Indoor unit Function External output setting Situation Mode Rotary SW Heating Indoor unit fan Heating thermostat on operation thermostat on no. 60 status 60-05 CN47 Example of 60-06 Output 3 individual Not used 60-07 Output 2 connection 60-08...
  • Page 250: External Input

    4. External input and output (for 24–36 outdoor units) →ith using external input and output functions, this product can be operated inter-connectedly with an external device. Connector Input Output Remarks P580 Low noise mode — PA580 Peak cut mode — See external input/output settings for details.
  • Page 251 ¢ Peak cut mode By performing following on-site work, operation that suppresses the current value can be enabled: The air conditioner is set to the “Peak cut mode” when closing the contact input of a commercial timer or on/off switch to a connector on the control PCB of the outdoor unit. •...
  • Page 252: External Output

    4-2. External output →ith using external output function, some status signals are transmitted to the control PCB, and the related LED lamp indicates the status of this product. ¢ Error status output Signal on air conditioner error status is generated when a malfunction occurs. •...
  • Page 253: Compressor Status Output

    ¢ Compressor status output Signal on compressor operation status is generated when the compressor is running. • Circuit diagram example • Output voltage (Vcc): DC 12 Outdoor unit V 50 mA or less control PCB Connected unit (Locally purchased) • *: Make the distance from Example: Connector...