DOLD VARIMETER BA 9065 Series Translation Of The Original Instructions

Underload monitor

Advertisement

Quick Links

Monitoring Technique
VARIMETER
Underload Monitor (cos ϕ)
BA 9065
Function Diagram
S
X1 L1/i L1/k L2
L1
L2
L3
U bzw. L1/L2/L3
H
K
I
0
X1
L1/i
cos
cos
(set)
(Alarm- Auto -Reset)
0
11-14
Relay normally
off
Alarm (I=0)
off
11-12
11-14
Relay normally
on
Alarm (I=0)
off
11-12
11-14
Relay normally
off
Alarm (I=0)
on
11-12
11-14
Relay normally
on
Alarm (I=0)
on
11-12
Circuit Diagrams
L1/i
L1/k
X1
L2
L3
L1/i L2
11
23
L1/k
L3
12 14
24
11
12
14
23
24
M8077
BA 9065.20
All technical data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
K
BA9065
L3
M
3~
t
t
t
t
t
t
t
t
M6591_e
L1/i
L1/k
X1
L2
L3
A1
L1/i L2
A2
L1/k
L3
12 14
11
12
14
A1
A2
BA 9065.11/001
Translation
of the original instructions
• According to IEC/EN 60255-1
• Detection of underload (cos ϕ)
• Current ranges up to 10 A, for higher values a CT must be used
• Adjustable response value
• Programmable functions:
- Alarm when I = 0
- Automatic or manual reset
- Closed or open circuit operation
• Manual remote reset
• Adjustable operate delay
• Independent of phase sequence
• Also for 400 Hz systems
• Optionally for motors with frequency converters (10 ... 100 Hz)
(see notes)
• Width 45 mm
Approvals and Markings
Applications
Monitors underload and no load on squirrel cage motors e.g.
• Fan monitoring (broken belt)
• Filter monitoring (blocked filter)
• Pump monitoring (blocked valve, dry running)
t
Function
The underload monitor BA 9065 measures the phase shift between voltage
and current. The phase angle changes with changing load. This measuring
method is suitable to monitor asynchronous motors on underload and no
t
load independent of motor size. The change of cos ϕ has to be bigger then
the hysteresis of the monitor (see diagram). In some cases the cos ϕ does
not change much with load change on the motor, e.g.:
- small load change on oversized motor
t
- single phase chaded-pole and collector motors
In these cases we recommend the use of our motor load monitors e.g BH 9097.
The BA 9065 can also be used on systems with variable frequency because
of it's frequency independent measuring principle.
The BA 9065.20 does not need a separate auxiliary supply as it takes the
required energy from the monitored mains.
A yellow LED indicates operation. If the cos ϕ goes under the setting value
the device reacts after a settable time delay. A green LED shows the state
of the output relay.
Functions programmable with DIP-switches:
• Open circuit operation (relay normally off)
• Alarm when no current is flowing (Alarm at I = 0 on)
• Closed circuit operation (relay normally on)
• No alarm when no current is flowing (Alarm at I = 0 off)
Function programmable with bridge X1-L1/i:
11
bridge
X1-L1/i
· ·
Manual reset, reset with built-in reset button or remote reset
· ·
with button connected to X1-L1/i
M8078
Automatic reset when system returns to correct load (cos ϕ)
1
11.01.21 en / 335A

Advertisement

loading
Need help?

Need help?

Do you have a question about the VARIMETER BA 9065 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for DOLD VARIMETER BA 9065 Series

  • Page 1 Monitoring Technique VARIMETER Translation Underload Monitor (cos ϕ) of the original instructions BA 9065 • According to IEC/EN 60255-1 • Detection of underload (cos ϕ) • Current ranges up to 10 A, for higher values a CT must be used •...
  • Page 2 Technical Data Connection Terminals General Data Terminal designation Signal description L1/i, L2, L3 Connection for 3-phase systems Operating mode: Continuous operation Temperature range Current measuring circuit, connection for L1/i, L Operation: - 20 ... + 60°C external current transformer possible Storage: - 20 ...
  • Page 3 Characteristic Operating Instructions The example of a frequency controlled fan motor shows how to set up Hysteresis the unit. 0,10 1) Setting on BA 9065 0,09 - Set BA 9065 to automatic restart (bridge X1-L/i; or while doing below mentioned tests press the reset button continuously) 0,08 - Adjust time delay to minimum (left position) 0,07...
  • Page 4 The nominal voltage is the phase to phase voltage. The sens of winding of the CT is of impartance! E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen • Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356 dold-relays@dold.com •...

This manual is also suitable for:

Varimeter ba9065.20Varimeter ba9065.11/001