DOLD VARIMETER IMD RN 5897/321 Translation Of The Original Instructions

DOLD VARIMETER IMD RN 5897/321 Translation Of The Original Instructions

Insulation monitor

Advertisement

Monitoring Technique
VARIMETER IMD
Insulation monitor
RN 5897/321
RN 5897/321
Product Description
The insulation monitor RN 5897/321 of the VARIMETER IMD family
provides best and up to date insulation monitoring of modern IT systems
in an optimum and state of the art way fulfilling the relevant standards.
The device can be used in the most flexible way for AC, DC and AC/
DC systems. Mains areas of applications are non-earthed DC charging
stations for electric vehicles with mains voltages up to DC 1000 V, that
need an extended temperature range. The setting of the parameters and
the switching values is done via Modbus. All measured values, device
statuses and parameters can also be read out via Modbus. All functions
of the device can also be operated via Modbus. The operating status is
indicated user friendly via a multicolour LED. With a sealable transparent
cover the device is protectet against manipulation.
Circuit Diagram
VSG1
L(+)
L(-)
A1(+)
VSG2
L(+) L(-)
11
U H
PE1
PE2
12
X1 X2
11 12 14 21 22 24
PE1
Connection Terminals
Terminal designation
Signal description
A1(+), A2
Auxiliarx voltage AC or DC
L(+), L(-), VSG1, VSG2
Connection for coupling device
PE1, PE2
Connection for protective conductor
Control input
(combined external Test- and Reset-input
X1, X2
with additional Stop of the measuring
function)
11, 12, 14
Alarm signal relay K1(1 changeover contact)
Prewarning signal relay K2 (1 changeover
21, 22, 24
contact)
All Technical Data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
Coupling devices
RL 5898
RP 5898
A2
21
14
22
24
PE2
M11956_a
Translation
of the original instructions
Your Advantages
• Suitable for DC charging stations for electric vehicles acc. to
IEC/EN 61851-23:2014/AC:2016-06
• Insulation monitoring according to IEC/EN 61557-8
• Universal application in non-earthed AC-, DC-, AC/DC networks
up to AC max. 250 V resp. DC max. 300 V
• Connection of an external coupling device RL 5898
for voltages up to AC 400 V / DC 500 V or
RP 5898 for voltages up to AC 690 V / DC 1000 V possible
• Extended operating temperature range of - 40 ... + 70 °C
• Very fast reaction time ≤ 1 s
• Optimised insulation resistance monitoring also during
mains voltage variation
• Self-test every full operating hours
• Preventive fire and system protection
• Detection of symmetric and asymmetric insulation faults
• Easy adjustment of response values and setting parameter via Modbus
• Suitable for large leakage capacitances up to 5 µF
• Monitoring also with voltage-free mains
• Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
• Protective conductor PE1/PE2 with broken wire detection
(can't be switched off)
• With galvanic separated Modbus RTU interface
Features
• 2 separate adjustable response thresholds
(using e.g. for pre-alarm and Alarm)
• Setting range of 1st response value (Pre-alarm): 20 kΩ ... 500 kΩ
• Setting range of 2nd response value (alarm): 1 kΩ ... 100 kΩ
• 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
• Energized or de-energized on trip can be selected for indicator relay
• With multicolour status LED to indicate the state of operation.
• Automatic and manual device self-test
• Alarm storage selectable
• Protection against manipulation by sealable transparent cover
• External control input for combined test- / reset-button
with additional Stop of the measuring function
• 2 wide voltage input for auxiliary voltage
• Width 52.5 mm
Approvals and Markings
AC/DC
Applications
Insulation monitoring of:
• Non-earthed AC, DC, AC/DC networks
• DC charging stations for electric vehicles
• UPS systems
• Networks with frequency inverters
• Battery networks
• Networks with direct current drives
• Hybrid and battery-powered vehicles
• Mobile generator sets
1
12.07.22 en / 604A

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VARIMETER IMD RN 5897/321 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DOLD VARIMETER IMD RN 5897/321

  • Page 1 Monitoring Technique Translation of the original instructions VARIMETER IMD Insulation monitor RN 5897/321 Your Advantages • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06 • Insulation monitoring according to IEC/EN 61557-8 Coupling devices • Universal application in non-earthed AC-, DC-, AC/DC networks up to AC max.
  • Page 2: Measuring Circuit

    Function Function The device is supplied with DC auxiliary voltage via terminals A1(+) / A2. Broken wire detection Switching on the auxiliary voltage (Power-On) is followed by an internal As described in section "Measuring circut", the measuring circuits L(+) / self-test for 12 s (see „Device test functions“).
  • Page 3: Function Diagram

    Function Function Diagram Behaviour with internal device faults If internal device faults were detected during the test function, the status LED flashes with flash code 3. The indicator relays K1 and K2 switch to the alarm state. The device faults are also indicated via Modbus. Behavior on faulty connection Earth fault When detecting broken wire on terminals L(+)/L(-), the measurement is...
  • Page 4 Indicators Error Indication Connection Flash code measuring ciruit or Auxiliary Failure cause Failure recovery coupling device voltage Status-LED Check Broken wire detection measuring circuit on L(+)/L(-). L(+) and L (-) Check Broken wire detection protective earth on PE1/PE2. connections PE1 and PE2 Press test button again or restart the unit by interrupting the Internal failure...
  • Page 5: Risk Of Electrocution

    Notes Risk of electrocution! Danger to life or risk of serious injuries. WARNING • Disconnect the system and device from the power supply and ensure they remain disconnected during electrical installation. • The display of the voltage is not in real time. The Value on the display is updated at the end of a measuring cycle.
  • Page 6: Switching Capacity

    Technical Data Technical Data Auxiliary voltage input A1(+)/A2 Measuring ciruit L(+)/L(-) to PE1/PE2 (with coupling device) Nominal voltage U AC / DC 0 ... 230 V Nom. Voltage Voltage range Frequency range Max. max. voltage range U : AC 0 ... 250 V AC 19 ...
  • Page 7: Vibration Resistance

    Technical Data Standard Types Clearance and creepage RN 5897.12/321 AC/DC 24 … 60 V distances Article number: 0069399 Rated insulation voltage: 300 V • Auxiliary voltage: AC/DC 24 … 60 V Overvoltage category: RN 5897.12/321 AC/DC 100 … 230 V Rated impuls voltage / Article number: 0069400...
  • Page 8 Accessories Accessories RL 5898/61 Flush mounting kit Article number: 0068315 Order reference: KU 4087-150/0056598 • Coupling device for RN 5897.12/320 • Extension of nominal voltage range U to DC 500 V, AC 400 V • Weight: Approx. 60 g • Dimensions - Width x height x depth: 35 x 90 x 71 mm Insulation monitor...
  • Page 9: Connection Examples

    Connection Examples Ungrounded mains Ungrounded mains 3/N AC 400V/230V 40...1000Hz RL5898: 3 AC 0...440V 40...1000Hz RP5898: 3 AC 0...760V 40...1000Hz Setting of type of network 3N AC Setting of type of network: L1(+) L2(-) External coupling device: RL5898 VSG1 L(+) L(-) VSG2 A1(+) RP5898...
  • Page 10 Connection Examples Single phase mains, isolated from earth Single phase mains, isolated from earth AC 0...250V 40...1000Hz RL5898: AC 0...440V 40...1000Hz RP5898: AC 0...760V 40...1000Hz Setting of type of network Setting of type of network: L1(+) L2(-) External coupling device: External coupling device: RL5898 VSG1...
  • Page 11: Function Codes

    Bus Interface Protocol Modbus Seriell RTU Adress 1 to 99 Baud rate 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 Baud Data bit Stop bit Parity None More information about the interface, wiring rules, device identification and communication monitoring can be found in the Modbus user manual. Function-Codes At RN 5897/321 the following function codes are implemented: Function-...
  • Page 12 Parameter Table Coils Register- Protocol- Value Initial Name Description Data type Access rights Adress Adress range value Reset 0x0000 0x0000 No Function Write / read 0xFF00 Error acknowledgem. device error (relay 2) Device reset 0x0000 0x0000 No Function Write / read 0xFF00 Device restart Reserved...
  • Page 13 Parameter Table Input Registers Register- Protocol- Value Name Description Data type Access rights Adress Adress range 30001 Device failure 0 … 12 0: No failure UINT16 Read 1: Broken wire detection L(+)/L(-) 2: Broken wire detection PE1/PE2 3: Internal failure detected in test mode 4: Reserved 9: Communication fault Modbus 10: Checksum failure EEPROM...
  • Page 14 Parameter Table Holding Registers Register- Protocol- Initial Name Value range Description Data type Access rights Adress Adress value 40001 Control word 1 0 … 65535 Bit 0 = Reset UINT16 Write / read Bit 1 = Device reset Bit 2 = Reserved Bit 3 = Factory settings Bit 4 = Device selftesting Bit 5 = Fault memory acknowledgement...
  • Page 15 Notice 12.07.22 en / 604A...