Monitoring Technique
VARIMETER IMD
Insulation monitor
RN 5897/020
RN 5897/020
Product Description
The insulation monitor RN 5897/020 of the VARIMETER IMD family provi-
des best and up to date insulation monitoring of modern IT systems in an
optimum and state of the art way fulfilling the relevant standards. The de-
vice can be used in the most flexible way for AC, DC and AC/DC systems.
Mains areas of applications are non-earthed DC charging stations for
electric vehicles with mains voltages up to DC 1000 V. The adjustment of
the setting values is simple and user friendly done on 2 rotary switches on
the front of the device. Via display and LEDs the measured value, device
parameters and device status are indicated easy to read. With a sealable
transparent cover the device is protectet against manipulation.
Function Diagram
U H
R
E
Earth fault
R
pA
R
A
Hysteresis function
21-24
Open circuit operation
21-22
21-24
De-energized on trip
21-22
11-14
Open circuit operation
11-12
11-14
De-energized on trip
11-12
Manual reset
Reset
21-24
Open circuit operation
21-22
21-24
De-energized on trip
21-22
11-14
Open circuit operation
11-12
11-14
De-energized on trip
11-12
All Technical Data in this list relate to the state at the moment of edition. We reserve the right
for technical improvements and changes at any time.
Coupling devices
RL 5898
RP 5898
M11593
Translation
of the original instructions
Your Advantages
• Suitable for DC charging stations for electric vehicles acc. to
IEC/EN 61851-23:2014/AC:2016-06
• Insulation monitoring according to IEC/EN 61557-8
• With connection facility of an external coupling device RL 5898
for voltages up to AC 400 V / DC 500 V or
RP 5898 for voltages up to AC 690 V / DC 1000 V
• Very fast reaction time ≤ 1 s
• Optimised insulation resistance monitoring also during
mains voltage variation
• Self-test every full operating hours
• Preventive fire and system protection
• Detection of symmetric and asymmetric insulation faults
• Quick fault localisation through selective earth fault detection to L+
and L-
• Universal application in non-earthed AC, DC, AC/DC networks
up to AC max. 250 V or DC max. 300 V
• Easy adjustment of response values and setting parameter via
rotational switch and menu display
• Suitable for large leakage capacitances up to 5 µF
• Monitoring also with voltage-free mains
• Measuring circuit L(+)/L(-) with broken wire detection (can be switched off)
• Protective conductor PE1/PE2 with broken wire detection
(can't be switched off)
Features
• 2 separate adjustable response thresholds
(using e.g. for pre-alarm and Alarm)
• Setting range of 1st response value (Pre-alarm): 20 kΩ ... 500 kΩ
• Setting range of 2nd response value (alarm): 1 kΩ ... 100 kΩ
• 1 changeover contacts each for insulation failures-Pre-alarm and -alarm
• Energized or de-energized on trip can be selected for indicator relay
• Display for indication of measured value, device parameters and
device status
• Automatic and manual device self-test
• Alarm storage selectable
• Protection against manipulation by sealable transparent cover
• External control input for combined test- / reset-button
with additional Stop of the measuring function
t
• 3 wide voltage input for auxiliary voltage
• Width 52.5 mm
Approvals and Markings
t
Canada / USA
Applications
Insulation monitoring of:
• Non-earthed AC, DC, AC/DC networks
• DC charging stations for electric vehicles
• UPS systems
• Networks with frequency inverters
• Battery networks
• Networks with direct current drives
• Hybrid and battery-powered vehicles
• Mobile generator sets
1
AC/DC
RN 5897 only
1)
12.07.21 en / 423A

Advertisement

loading
Need help?

Need help?

Do you have a question about the VARIMETER IMD RN 5897/020 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for DOLD VARIMETER IMD RN 5897/020

  • Page 1 Monitoring Technique VARIMETER IMD Translation Insulation monitor of the original instructions RN 5897/020 Your Advantages • Suitable for DC charging stations for electric vehicles acc. to IEC/EN 61851-23:2014/AC:2016-06 • Insulation monitoring according to IEC/EN 61557-8 Coupling devices • With connection facility of an external coupling device RL 5898 for voltages up to AC 400 V / DC 500 V or RP 5898 for voltages up to AC 690 V / DC 1000 V •...
  • Page 2: Measuring Circuit

    Function Function Broken wire detection The device is supplied with DC auxiliary voltage via terminals A1(+) / A2. Switching on the auxiliary voltage (Power-On) is followed by an internal As described in section "Measuring circut", the measuring circuits L(+)/L(-) self-test for 12 s (see „Device test functions“). The test process is visible and the protective conductors PE1/PE2 are constantly monitored for wire in the display.
  • Page 3 Function Function Behaviour with internal device faults If internal device faults were detected during the test function, the display backlight changes into red and an error messages (failure code: „Int.1“) is indicated. The indicator relays K1 and K2 switch to the alarm state. Behavior on faulty connection When detecting broken wire on terminals L(+)/L(-), the measurement is disabled.
  • Page 4 Indicators Indicators The colour of the backlight indicates the operating status of the device. Connection measuring ciruit Auxiliary Off: No auxiliary voltage connected Coupling device voltage Green: Normal operation (Insulation resistance in healthy state) Red: Alarm (measured value below alarm response value, device failure, connection failure) Orange: Warning (measured value below pre-alarm response value, test mode, Parameter set-up mode)
  • Page 5: Display Indication

    Indicators Error Indication Display-Indication Measuring- resp. display value Display-Indication Failure cause Failure recovery Insulating resistance in kΩ resp. MΩ („----“ complies RE ≥ 2 MΩ) Check Broken wire detection measuring circuit on L(+)/L(-). L(+) and L (-) Asymmetrical insulating resistance in kΩ Check against L+ or L- at DC-mains Broken wire detection...
  • Page 6 Notes Risk of electrocution! Danger to life or risk of serious injuries. WARNING • Disconnect the system and device from the power supply and ensure they remain disconnected during electrical installation. • The display of the voltage is not in real time. The Value on the display is updated at the end of a measuring cycle.
  • Page 7 Running chart Press button Press button „Set/ESC“ „Set/ESC“ >2s Press button Scroll Down „ ▼“ Set parameters Press button Scroll Up „ ▲“ Parameter 1: Parameter 1: Parameter 1: Broken wire detect in Broken wire detect in Broken wire detect in measuring circuit measuring circuit measuring circuit...
  • Page 8 Technical Data Technical Data Nominal consumption: Measuring ciruit L(+)/L(-) to PE1/PE2 (without coupling device) DC 12 V, 24 V, 48 V: Max. 3 W Nominal voltage U AC / DC 0 ... 230 V AC 230 V: Max. 3.5 VA Max.
  • Page 9: Switching Capacity

    Technical Data Standard Types Wire connection DIN 46228-1/-2/-3/-4 RN 5897.12/020/61 DC 12 ... 24 V Cross section: 0.5 ... 4 mm² (AWG 20 - 10) solid or Article number: 0068260 0.5 ... 4 mm² (AWG 20 - 10) • Auxiliary voltage: DC 12 ...
  • Page 10: Connection Example

    Accessories Connection Example RP5898/61 Ungrounded mains Article number: 0066944 3N AC 400V/230V 40...1000Hz • Coupling device for RN 5897.12/020 • Extension of nominal voltage range U to DC 1000 V, AC 690 V • Weight: Approx. 110 g • Dimensions - Width x height x depth: 70 x 90 x 71 mm Setting of type of network...
  • Page 11 Connection Example Single phase mains, isolated from earth Single phase mains, isolated from earth RL5898: AC 0...440V 40...1000Hz AC 0...250V 40...1000Hz RP5898: AC 0...760V 40...1000Hz Setting of type of network Setting of type of network: L1(+) L2(-) External coupling device: External coupling device: RL5898 RP5898...
  • Page 12 E. Dold & Söhne GmbH & Co. KG • D-78120 Furtwangen • Bregstraße 18 • Phone +49 7723 654-0 • Fax +49 7723 654356 dold-relays@dold.com • www.dold.com 12.07.21 en / 423A...

This manual is also suitable for:

Varimeter imd rl 5898Varimeter imd rp 5898