9.2 Checking Scroll Compressor Rotation 17.7 Check Cabling 9.2.1 Correcting Direction of Rotation 17.8 Detection of Flammable Refrigerants 17.9 Removal and Evacuation 10 Start-up 17.10 Charging Procedures 10.1 Unit Start Up Cooling Mode 17.11 Recovery MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 4
Belt-Drive Motor 21.4 Two-Stage, Three-Phase Standard Unit with Dual-Point Power and Belt-Drive Motor 21.5 DDC Control 6126 21.6 DDC I/O Flex EX8160 22 Terminology 22.1 Acronyms 22.2 Terms 23 Check-Out Sheet MC Series Heat Pumps - 8733850301 (2025/02) US...
Use a quenching cloth for brazing, and place a fire 1.1.2 Important information extinguisher close to the work area. The info symbol indicates important information where there is no risk to property or people. MC Series Heat Pumps - 8733850301 (2025/02) US...
Children should be supervised to ensure that they do not play with the appliance. To avoid the release of refrigerant into the atmosphere, the refrigerant circuit of this unit must be serviced only by technicians who meet local, state, and federal proficiency requirements. MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 7
If a compressor is removed from this unit, refrigerant circuit oil will remain in the compressor. To avoid leakage of compressor oil, refrigerant lines of the compressor must be sealed after it is removed. MC Series Heat Pumps - 8733850301 (2025/02) US...
Modulating Hot Gas Reheat N — Modulating Hot Gas Reheat with Straight Cool S — Straight Cool T — Hot Gas Bypass with Straight Cool X — None Figure 1 Model Nomenclature MC Series Heat Pumps - 8733850301 (2025/02) US...
Note: Maximum and minimum operating limits may not be combined. Refer to Engineer Submittal Sheet on the product information page. (See the QR code on the back page of the IOM). Acronyms: EXT: Extended Range application option STD: Standard application option LWT: Leaving Water Temperature EWT: Entering Water Temperature MC Series Heat Pumps - 8733850301 (2025/02) US...
If the equipment is not needed for immediate installation upon its arrival at the job discovered until after removing the units from packaging must be reported to Bosch site, it should be left in its shipping factory condition and stored in a clean and dry area.
This section contains information on the following: Product damage! • Location Selection—page 11 MC series units are not approved for outdoor installation; therefore, they must be • Minimum Conditioned Room Area—page 12 installed inside a structure in a conditioned space.
Once the unit is properly positioned on the job site, cover it with either a shipping All MC Series models are provided with a supply air outlet collar and return air duct carton, vinyl film, or an equivalent protective covering. Cap opens ends of pipes flange to facilitate duct connections.
The water flow can be accurately set by measuring the water-to- refrigerant heat exchangers water-side pressure drop. See the unit specification sheets for the water flow and pressure drop information. 14 | MC Series Heat Pumps - 8733850301 (2025/02) US...
All field-installed wiring must comply with the National Electric Code as well as all Product damage! applicable local codes. Power to the unit must be within the operating voltage range indicated on the unit’s nameplate or on the performance data sheet. MC Series Heat Pumps - 8733850301 (2025/02) US | 15...
208-V option is ordered. For job sites with a 208-V power supply, the primary leads on the unit transformer will need to be changed from 240-V to 208- V. Refer to the unit wiring diagrams starting on page 54. 16 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Exceeding the transformer capacity will result in low control voltage, erratic unit 18 AWG (0,75mm2) 385 ft. (117m) operation, or damage to the heat pump. Table 5 Length by Wire Gauge for Thermostat to HVAC Equipment Wiring MC Series Heat Pumps - 8733850301 (2025/02) US | 17...
Total VA draw Total Draw Is Dependant on the Options Installed Installed Table 8 Low-Voltage VA Draw Table Units supplied with 100VA Transformer(s) from factory (360 QTY 1; 480-720 QTY 2) 18 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Figure 7 Typical Cooling Tower and Boiler System Setup 1] Supply and Return Line of Central System [2] Ball Valves [3] Hose Kits (optional) [4] Line-Voltage Control Connection [5] Low-Voltage Control Connection [6] Flex Duct Connection 20 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Fouling due to iron bacteria can also pose problems in some open loop installations. Iron bacteria fouling can quickly degrade system performance and plug heat exchangers. Air in the water system will greatly accelerate the fouling or corrosion process. MC Series Heat Pumps - 8733850301 (2025/02) US | 21...
Page 22
< 10 ppm, < 600 µm size** Erosion Maximum Water Velocity 6 ft/sec 6 ft/sec Table 9 Water Quality * No "rotten egg" smell present at < 0.5 ppm H2S. ** Equivalent to 30 mesh strainer 22 | MC Series Heat Pumps - 8733850301 (2025/02) US...
(See 16.7 Pulley Alignment and Belt Tensioning Procedure on page 36.) 9.2 Checking Scroll Compressor Rotation Scroll compressors, like the ones used on the MC series, are phase sensitive. When out of phase, the compressors will run in reverse. After a few minutes of reverse operation, the compressor internal overload protection will open, activating the unit lockout.
Once the unit has begun to run, check for warm air delivery at the unit grille. Check air temperature rise across the coil when compressor is operating. Check for vibration, noise, and water leaks. 24 | MC Series Heat Pumps - 8733850301 (2025/02) US...
[9] UPM Board Settings DIP Switch [10] A2L Sensor [11] 24VAC Power Common [12] 24VAC Power Input [13] UPM Standoff [14] Power LED [15] Fan (Fan in the event of an A2L leakage) 26 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 27
Figure 10 MC Freeze Sensor Locations • Air coil freeze protection sensors are mounted close to evaporator coil between the thermal expansion valve and evaporator coil. (Refer to Fig. 10.) MC Series Heat Pumps - 8733850301 (2025/02) US | 27...
LED Status Indicator displays either a solid green indicating no faults or will blink a fault code in red. (Refer to Table 11 for a description of the blink codes.) 28 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 29
(above Refrigerant Leak 15% LFL, refer to leak detection system section) Lost communications with the Second- Second-Stage UPM Board Fault Stage UPM board Table 11 UPM Fault Blink Codes MC Series Heat Pumps - 8733850301 (2025/02) US | 29...
Lockout DIP switch position “1” is set to "OFF" or "ON")(See Table 10) before 60 minutes, the unit will go into a hard lockout and requires a manual lockout reset. 30 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Installation, Operation, and Maintenance Manual 13 UPM Sequence of Operation Figure 13 UPM Sequence of Operation MC Series Heat Pumps - 8733850301 (2025/02) US | 31...
Once the thermostat is satisfied, the compressor shuts down and the fan ramps down to either fan-only mode or OFF over a span of 30 seconds. 32 | MC Series Heat Pumps - 8733850301 (2025/02) US...
There are several ways to control the heat pumps with hot gas reheat. You should choose the means that best suits your specific application. Most heat pump A number of options are available on MC Series of Heat Pumps. The following compatible thermostats in conjunction with a humidistat are acceptable for use.
If at any time the water temperature rises above the aquastat set point the MBV will be energized in the bypass mode and fluid MC series heat pumps can be provided an optional waterside economizer. The will bypass the economizer coil.
• air flow problems, or • air temperature problems Use of the pressure and temperature charts for the unit may be required to properly determine the cause. MC Series Heat Pumps - 8733850301 (2025/02) US | 35...
Using a gauge, apply 4 lb of force to the center of the belt and adjust the tension until a deflection of 1/64-in. is achieved for every inch of shaft center distance. (Refer to Fig. 15.) 36 | MC Series Heat Pumps - 8733850301 (2025/02) US...
At all times the manufacturer's maintenance and service guidelines must be followed. If in doubt, consult Bosch service and support All work must be undertaken under a controlled procedure to minimize the risk of a for assistance.
Ensure the system is leak-tested on completion of charging but prior to commissioning. A follow-up leak test must be carried out prior to leaving the site. 38 | MC Series Heat Pumps - 8733850301 (2025/02) US...
The compressor body must NOT be heated by an open flame or other ignition sources to accelerate this process. When oil is drained from a system, it must be carried out safely. MC Series Heat Pumps - 8733850301 (2025/02) US | 39...
Equipment must be labeled stating that it has been decommissioned and collection site. emptied of refrigerant. The label must be dated and signed. Ensure that there are labels on the equipment stating the equipment contains flammable refrigerant. 40 | MC Series Heat Pumps - 8733850301 (2025/02) US...
After the compressor has cooled, check the continuity of the compressor windings. If the windings are open, Compressor Windings Open replace the compressor. MC Series Heat Pumps - 8733850301 (2025/02) US | 41...
Page 42
Check the TXV for possible restriction or defect. Replace if necessary. The refrigerant system may be contaminated with moisture or non-condensable. Reclaim the refrigerant, replace Moisture, Non-Condensable the filter dryer, evacuate the refrigerant system, and recharge with the factory-recommended charge. 42 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 43
High water temperature is Closed Check to see if sensor is not attached securely to line." Scaled or Fouled Heat Low heat output Clean the heat exchanger. Exchanger Table 13 Unit Troubleshooting MC Series Heat Pumps - 8733850301 (2025/02) US | 43...
Page 44
Is the Fault LED blink- ing four (4) times on Low-pressure fault— If Yes, Circuit 2 is affected. Check the refrigerant pressure with a gauge set. the 1st & 2nd stage Low refrigerant. UPMs? 44 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 45
Check the air filter and return air duct work for blockage. Condensate fault— Blocked return air. • Check that there is adequate space between the return air opening and the walls or other obstructions on free return applications. MC Series Heat Pumps - 8733850301 (2025/02) US | 45...
Page 46
1st & 2nd stage UPMs? Check that the harness is connected from the A2L sensor side. Check if there are any hissing or gurgling noises in the system. 46 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 47
Check the A2L sensor is going to both the 1st and 2nd ing twelve (12) times between the UPM 1st stage UPMs. No compressor Cooling or Heating on the 1st & 2nd stage & UPM 2nd stages. operation UPMs? Table 14 MC Series Heat Pumps - 8733850301 (2025/02) US | 47...
Page 49
Installation, Operation, and Maintenance Manual 20.2 Blower Curves M C360 M C480 - 720 Figure 16 1000 CFM MC Series Heat Pumps - 8733850301 (2025/02) US | 49...
Page 50
Installation, Operation, and Maintenance Manual M C480 - 720 1000 CFM Figure 17 1000 CFM 50 | MC Series Heat Pumps - 8733850301 (2025/02) US...
90.0 MC480 120.0 160.0 12.0 16.7 75.0 112.5 MC600 150.0 200.0 16.3 90.0 135.0 MC720 180.0 11.8 240.0 20.3 Table 20 All values based upon pure water at 70° F. MC Series Heat Pumps - 8733850301 (2025/02) US | 53...
Page 54
21.1 Two-Stage, Three-Phase Standard Unit with Belt-Drive Motor Figure 18 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 54 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 55
21.2 Two-Stage, Three-Phase Unit with Optional Components (MHGR) and Belt Drive Motor Figure 19 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. MC Series Heat Pumps - 8733850301 (2025/02) US | 55...
Page 56
Installation, Operation, and Maintenance Manual Figure 20 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 56 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 57
21.3 Two-Stage, Three-Phase Unit with DDC, Optional Components, and Belt-Drive Motor Figure 21 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. MC Series Heat Pumps - 8733850301 (2025/02) US | 57...
Page 58
BO-2 BO-5 BO-3 BO-5 BO-8 BO-2 BO-1 Figure 22 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 58 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 59
21.4 Two-Stage, Three-Phase Standard Unit with Dual-Point Power and Belt-Drive Motor Figure 23 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. MC Series Heat Pumps - 8733850301 (2025/02) US | 59...
Page 60
BO-2 BO-5 BO-3 BO-5 BO-8 BO-2 BO-1 Figure 24 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 60 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 61
21.5 DDC Control 6126 Figure 25 DDC Control 6126 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. MC Series Heat Pumps - 8733850301 (2025/02) US | 61...
Page 62
21.6 DDC I/O Flex EX8160 Figure 26 DDC I/O Flex EX8160 FOR REFERENCE ONLY. Actual unit wiring may vary from this example. Always refer to the wiring diagram attached to the unit. 62 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 63
Decommissioning — Means the final shut-down and removal from operation or usage of a product or piece of equipment containing fluorinated greenhouse gases. Discharge Pressure — Referring to the pressure leaving compressor. MC Series Heat Pumps - 8733850301 (2025/02) US | 63...
Page 65
Installation, Operation, and Maintenance Manual NOTES: MC Series Heat Pumps - 8733850301 (2025/02) US | 65...
Page 66
Installation, Operation, and Maintenance Manual NOTES: 66 | MC Series Heat Pumps - 8733850301 (2025/02) US...
Page 67
Installation, Operation, and Maintenance Manual NOTES: MC Series Heat Pumps - 8733850301 (2025/02) US | 67...
Page 68
United States and Canada Bosch Thermotechnology Corp. 65 Grove St. Watertown, MA 02472 Tel: 800-283-3787 www.bosch-homecomfort.us 8733850301/ (2025/02) US Bosch Thermotechnology Corp. reserves the right to make changes without notice due to continuing engineering and technological advances.
Need help?
Do you have a question about the MC Series and is the answer not in the manual?
Questions and answers