JORDAN CONTROLS SM-1020-0144 Instruction Manual

Electronic actuator for hart communication

Advertisement

Quick Links

Instruction Manual
IM-0609
SM-1020-0144 Electronic Actuator
for HART Communication

Table of Contents

General Information .............................................. 2-3
Product Specifications .............................................. 4
Installation Wiring .................................................... 5
Setup Information ................................................. 5-7
Recommended Spare Parts List ................................ 7
Typical Wiring Diagram ............................................ 8
Troubleshooting Guide ............................................. 9
Component Location Drawing ............................... 10
Major Dimensions .................................................. 11
Due to wide variations in the terminal numbering
of actuator products, actual wiring of this device
should follow the print supplied with the unit.
-1-

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SM-1020-0144 and is the answer not in the manual?

Questions and answers

Summary of Contents for JORDAN CONTROLS SM-1020-0144

  • Page 1: Table Of Contents

    Instruction Manual IM-0609 SM-1020-0144 Electronic Actuator for HART Communication Table of Contents General Information ..........2-3 Product Specifications ..........4 Installation Wiring ............ 5 Setup Information ..........5-7 Recommended Spare Parts List ........ 7 Typical Wiring Diagram ..........8 Troubleshooting Guide ..........9 Component Location Drawing .......
  • Page 2: General Information

    Jordan Controls representative for received rough handling. Report all damage immedi- clarification. ately to the freight carrier and Jordan Controls, Inc. • Follow all warnings, cautions and instructions marked Unpack the product and information packet—taking on, and supplied with, the product.
  • Page 3: Identification Label

    SM-1020 ° F Degrees Fahrenheit 1628 C 99 Horsepower 120 / 50-60 / 1 / 1 95C 036051 - 1 Inch Increase SM-1020-0144 in.lbs. Inch Pounds Kilogram Line (power supply) Pounds Force Pounds Light Emitting Diode MODEL NUMBER: SM1020 Loss of Signal...
  • Page 4: Product Specifications

    SM-1020-0144 PRODUCT SPECIFICATIONS MECHANICAL: ELECTRICAL: Output Shaft Motion: CW on increasing command Supply Voltage: 24 Vdc +/- 20% facing output shaft. CCW on decreasing command Operating Current: 2 amperes maximum;1.5 am- Output Torque: 125 in. lb. maximum peres at 24 Vdc input, 10mA in standby when actuator is at null Output Shaft Speed: 3.3 rpm (90 seconds full stroke...
  • Page 5: Installation Wiring

    MECHANICAL SETUP CALIBRATION AND START-UP 1. Ensure valve stem is turned to its full closed posi- The SM-1020-0144 can be calibrated either remotely tion. (Full CW looking at top of stem) using the handheld calibrator connected to the HART network, or locally through the board-mounted INC &...
  • Page 6 SETUP INFORMATION HART Command Set - Universal Commands Command Data in Command Data in Reply Nbr. Function Byte Function Byte Function Read Unique Identifier None “254” (expansion) manufacturer identification code manufacturer’s device type code number of preambles universal command revision transmitter specific command revision software revision...
  • Page 7: Recommended Spare Parts List

    SETUP INFORMATION HART Command Set - Common Practice Commands Command Data in Command Data in Reply Nbr. Function Byte Function Byte Function Write Range Values Range units code As in command SPAN = upper range value (Float) ZERO = lower range value (Float) Reset Configuration None...
  • Page 8: Typical Wiring Diagram

    TYPICAL WIRING DIAGRAM Due to wide variations Note 1 in the terminal numbering of actuator products, actual wiring should follow the print supplied with the actuator. Note 1: Customer supplied jumper wire to be used when remote auto manual operation is needed. HART communication will be disabled.
  • Page 9: Troubleshooting Guide

    TROUBLESHOOTING GUIDE TROUBLE POSSIBLE CAUSE REMEDY a. Run into a mechanical stop. a. Set stroke within actuator limits. Can’t get full actuator travel. b. Actuator ZERO & SPAN calibration incorrect. b. Calibrate ZERO & SPAN. Output shaft goes in opposite Actuator ZERO &...
  • Page 10: Major Component Identification

    MAJOR COMPONENT IDENTIFICATION Handwheel (Rotates During Operation) Servo Amplifier Assembly Cover Stepper Motor Planetary Gear Set Captive Cover Screws Dual Conduit Entries Actuator Base Output Shaft Ground Screw Coupling Adapter for Merla FCV Valve (Coupling Furnished) Merla FCV Valve (Not Included) -10-...
  • Page 11: Installation Dimensions

    INSTALLATION DIMENSIONS All Dimensions in Inches -11-...
  • Page 12 The dimensions in this manual are subject to change without notice and should not be used JORDAN CONTROLS, INC. for preparation of drawings or fabrication of 5607 West Douglas Avenue installation mounting. Current installation Milwaukee, Wisconsin 53218 dimension drawings are available upon request.