1 DESCRIPTION Multifunctional time relay with display TM-24 EKF is a two- channel electromechanical switching device designed to create an independent time delay and to ensure a certain sequence of operations in controlled circuits. The product complies with IEC 60947-5-1.
Page 3
Table 1 continued Characteristics Values Position in space Arbitrary Mounting 35mm DIN rail Conductor cross-section, mm 0,5-1 The product must be operated under the following environmental conditions: • non-explosive environment; • no corrosive gases and vapors in concentrations damaging to metals and insulation;...
Page 4
Channel 2, Power supply relay output 240V Display ONStart Buttons MENU Channel 1, Control signal relay output input channel Fig. 1 - Time relay TM-24...
Page 5
Selected Output time delay contact state Function Channel Switching time *If scenarios 9, 13, 14 are selected (see Table 3), information will not be shown on display. Fig. 2 - Front panel Display symbols: Tailing edge trigger Relay contact on Timer setpoint, minutes Relay contact off Time setpoint, seconds...
Page 6
The operation of the second channel contacts (25-28) is similar to the operation of contacts 15-18 described in Table 3. Table 3 On-delay. After the relay is energized, a count- down (T) is started. Once the countdown is fin- ished, relay is switched on (contacts 15-18 close) and remains on as long as the relay is energized.
Page 7
Table 3 continued Delay Off (Leading edge) After the relay is ener- gized, it remains in a steady state until a signal (S) is detected. As soon as the signal is detected, contacts 15-16 open, contacts 15-18 close, and the countdown timer (T) is started. Once the countdown is finished, contacts 15-18 open, and contacts 15-16 close.
Page 8
Table 3 continued One-shot Bi-stable. After the relay is energized, it remains in a steady state until a signal (S) is detected. As soon as the signal is detected, con- tacts 15-16 open, contacts 15-18 close, and relay remains in this state. As soon as the second signal is detected, contacts 15-18 open, and contacts 15-16 close.
Page 9
Table 3 continued Delay On (Leading edge) After relay is energized, it remains in a steady state until a signal (S) is detected and disap- pears.As soon as the signal disappears, con- tacts 15-16 open, contacts 15-18 close, and relay remains in this state.
Page 10
Table 3 continued One-shot (T1) / Delay On (T2) After the relay is energized, contacts 15-18 close, and contacts 15-16 open and remain in this state for the dura- tion of countdown (T1). Once the countdown (T1) is finished, contacts 15-18 open, contacts 15-16 close, and a new countdown (T2) is started.
Page 11
Table 3 continued Delay On (Leading edge, ≥T1) / Delay Off (Trail- ing edge, repeat countdown). After the relay is energized, it remains in a steady state until a signal (S) is detected.. After the sig- nal S is detected, the countdown (T1) begins. Once the countdown (T1) is finished, contacts 15-16 open, contacts 15-18 close and the relay remains in this state until the signal (S) disap-...
Page 12
Table 3 continued Alternating pulse generation. After the relay is energized, it remains in a steady state until a signal (S) is detected. As soon as the signal is detected, contacts 15-16 open, con- tacts 15-18 close, and the countdown timer (T1) is started.
Page 13
Table 3 continued Delayed On T2 Leading Edge ≥T1 After the relay is energized, it remains in a steady state until a signal (S) is detected.. After the sig- nal S is detected, the countdown (T1) begins. Once the countdown (T1) is finished, contacts 15-16 open, contacts 15-18 close, and a new countdown (T2) is started.
3 INSTALLATION AND OPERATION The device is installed onto a 35 mm DIN rail in the distribution enclosure. To avoid interference, false tripping, or malfunctioning of the relay, do not route the relay power supply wires along the power circuit wiring.
Page 15
Settings/Main menu Scenario selection (1-24) T1/T setup T2 setup Press the MENU button to begin setting the parameters. The SET symbol will appear on the display. If no buttons are pressed for 2 minutes, the device will return to the main menu. Scenario selection Select the MODE menu item and press OK to confirm.
Page 17
Select the T1/T menu item and press OK to confirm. Select a channel and press OK to confirm. Select the desired unit of measurement. SEC-seconds (0-9999s), MIN-minutes (see p.8). Select and set thousands (0-9), press OK to confirm. Select and set hundreds (0-9), press OK to confirm. Select and set tens (0-9), press OK to confirm.
Page 19
Select menu item T2 and press OK to confirm. Select a channel and press OK to confirm. Select the desired unit of measurement. SEC-seconds (0-9999s), MIN-minutes (see p.8). Select and set thousands (0-9), press OK to confirm. Select and set hundreds (0-9), press OK to confirm. Select and set tens (0-9), press OK to confirm.
7 DELIVERY SCOPE 1. Time relay TM-24 multifunctional with display EKF – 1 pc. 8 SAFETY REQUIREMENTS WARNING! Hazardous voltage The device conforms to IEC 61140 Class 0 for protection against electrical shock. The device shall be installed and serviced only by qualified electrical personnel.
Importer and EKF trademark service representative: EKF ELEC- TRICAL SOLUTION – FZCO, Dubai Silicon Oasis, DDP, Building A2, Dubai, United Arab Emirates. Importer and EKF trademark service representative on the terri- tory of the Russian Federation: OOO «Electroresheniya», Otradnaya st., 2b bld. 9, 5th floor, 127273, Moscow, Russia.