1 DESCRIPTION Multifunctional time relay RT-10 EKF is an electronic switching device with adjustable time settings and multiple relay operation scenarios. The relay is designed to switch the load on or off according to specified time values and selected scenarios. Timers and scenarios can be adjusted using the dials on the front panel of the relay.
Page 3
Table 1 continued Characteristics Values Item code RT-10 RT-10-2 RT-10-12-240 RT-10-12-240-2 Mechanical life, cycles 1 000 000 Number of switching contacts Rated load current, A 8 at 230V, AC1 3 in accordance with Interference immunity IEC 61000-4-4:2004 Max. altitude above sea 2000 level, m Degree of protection...
Page 4
Indication Green "U" LED: constantly lit when the relay is powered. Red " " LED: flashes red during timer countdown. The relay is on, contacts 15-18 (25-28) are closed - constantly lit. The relay is off, contacts 15-18 (25-28) are open - does not light up. Attention! In order to repeat the cycle after power off, wait for at least 200 ms before reconnecting the supply.
Page 5
Function diagram Function diagram Description Delay On (NOTC). After the relay is energized, a countdown (T) is started. During the count- down, relay contacts 15-16 (25-26) remain closed and contacts 15-18 (25-28) remain open (relay is off). Once the countdown is finished, contacts 15-16 (25-26) open, and contacts 15-18 (25-28) close (relay is on), remaining in this state until the relay is de-energized.
Page 6
Function diagram Description Leading edge On / Trailing edge Delay Off. After the relay is energized, it remains in a steady state until a signal (S) is detected. As soon as the signal is detected, contacts 15- 16 (25-26) open, contacts 15-18 (25-28) close, and relay remains in the steady state while the signal (S) is being detected.
Page 7
Function diagram Description Reappearance of the signal (S) while the countdown is running does not affect the execution of the relay scenario. Delay On (Leading edge) / Delay Off (Trailing edge).After the relay is energized, it remains in a steady state until a signal (S) is detected. Once the signal (S) is detected, a countdown (T) is started.
Page 8
Function diagram Description Delay On One-shot (0,5s).After the relay is energized, a countdown (T) is started. During the countdown, relay contacts 15-16 (25- 26) are closed and contacts 15-18 (25-28) are open. Once the countdown is finished, contacts 15-16 (25-26) open, and contacts 15-18 (25-28) close for 0,5 s and then open again, remaining open for as long as the relay is energized.
7 MAINTENANCE 7.1. For maintenance, follow national safety rules for operation of electrical Installations. 7.2. Under normal operating conditions, visually inspect the relay and check the set modes and trigger time every 6 months. Tighten the clamping screws during the inspection, as they may become loose due to cyclical changes in the ambient temperature and material flow.
Manufacturer: for information, refer to the product packaging. Importer and EKF trademark service representative: EKF ELECTRICAL SOLUTION – FZCO, Dubai Silicon Oasis, DDP, Building A2, Dubai, United Arab Emirates. Importer and EKF trademark service representative on the territory of the Russian Federation: OOO «Electroresheniya», Otradnaya st., 2b bld.