Nemalux EXC Series Installation Manual

Class i division 1, explosion proof

Advertisement

Quick Links

EXC Series Installation Manual
Class I Division 1 | Explosion Proof
APPLICATION
The EXC luminaire is an explosion-proof product suitable for hazardous locations. Installation areas
include indoor and outdoor use. The EXC is Class I Division 1 certi ed. CID1 locations are those in which
in ammable gases or vapours are or may be present in su cient quantities to produce explosive or
ammable mixtures during normal operational conditions. Furthermore, with an IP66 protection level, the
versatile EXC o ers a low-pro le solution for surface and yoke mount applications in the permanently
mounted LED xture category.
Certi ed to:
Hazardous Location
Certi cation:
Housing:
Input Voltage:
Rated Power:
Current (Typ):
Connections:
Temperature Range:
Ingress Protection:
MADE IN CANADA
Installation
UL 1598, UL 8750, UL 844;
CSA C22.2 No. 250.0, CSA C22.2 No. 137;
Class I, Division 1, Groups CD, T5;
Class II, Division 1, Groups EFG, T4A;
Class III, Division 1;
Class I, Zone 1, Group IIB;
Class I, Zone 20, Group IIIC
Copper-free cast aluminium with tempered glass lens
Su x - AC: 120-277 VAC | Su x - DC: 22-28VDC
Su x - AC: 30W | Su x - DC: 35W
Su x - AC: 0.2A @ 120VAC | Su x - DC: 1.1A @ 24VDC
3 x 3/4" NPT Conduit
Su x - AC: Black: Line | White: Neutral/Line 2 | Chassis: Ground
Class 1 Wiring only.
Su x - AC: Black: Line | White: Neutral | Chassis: Ground
Su x - DC: Black: Negative (-) | Red: Positive (+) | Chassis: Ground
For connections use wire rated to a minimum of 90°C. Daisy-chain wiring must use
#12AWG conductors and the total circuit load must not exceed 1200W.
The EXC does not contain any arcing, sparking, or hazardous temperature components,
and no conduit seals are required when installing luminaire. Refer to NEC 501.15(A) and
CEC 18-108 for details.
-50°C to +58°C
IP66 | Suitable for wet locations (luminaire enclosure only).
www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190
Spec Sheet
Webpage
EXC
rev. C-01
1-5

Advertisement

loading
Need help?

Need help?

Do you have a question about the EXC Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Nemalux EXC Series

  • Page 1 Refer to NEC 501.15(A) and CEC 18-108 for details. Temperature Range: -50°C to +58°C Ingress Protection: IP66 | Suitable for wet locations (luminaire enclosure only). www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 MADE IN CANADA...
  • Page 2 Use all four fastening points for more secure mounting. [9.47in] 240.5mm STEP 3. Using a 2mm Allen socket key, loosen the M4 JB lid set screw. Step 3 www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 MADE IN CANADA...
  • Page 3 Refer to NEC/CEC codes and follow all applicable local standards. All unused NPT entries must be plugged using the provided 3/4-14 NPT plugs. Connect Ground via provided #10-32 Green Grounding screw to Grounding Location. www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 MADE IN CANADA...
  • Page 4 Tighten rmly until the lid has bottomed out on the body. Torque lid to 40 ft-lbs (54 Nm). STEP 8. Tighten M4 JB lid set screw. Torque to 10-inch pounds. Step 8 STEP 9. Energize xture. www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 MADE IN CANADA...
  • Page 5: Installation Steps

    CEC/NEC requirements for the installation's speci c location. Step 4 STEP 6. 6.8mm [0.27in] Continue installation with STEP 6 on PAGE 3. 13.5mm [0.53in] [1.18in] 30mm [2.95in] 75mm 10deg www.nemalux.com | sales@nemalux.com | Tel 403•242•7475 | Fax 403•243•6190 MADE IN CANADA...