1. CONTENTS 2. SAFETY INSTRUCTIONS AND WARNINGS 3. INSTALLATION 3.1. CONNECTING ST-SA-CONTROL TO AIR HANDLING UNIT 3.2. HOW TO MOUNT ST-SA-CONTROL ON THE WALL? 3.3. TROUBLESHOOTING 4. PRODUCT INFORMATION 4.1. DESCRIPTION 4.2. TECHNICAL DATA 4.3. PACKAGE 5. INSTRUCTIONS FOR DEVICES WITH PRV CONTROL BOARD 5.1.
• Mounting and installation work can only be performed by a qualified person. • Electric connection must be performed according to electrical schematics and the technical requirements of the manufacturer. • Avoid the use of foreign objects in the equipment. ST-SA-CONTROL v2024.1 | EN...
15 mm 3.1. CONNECTING ST-SA-CONTROL TO AIR HANDLING UNIT Use the following steps to connect a ST-SA-Control remote controller to an air handling unit: • Unpack the ST-SA-Control remote controller • Connect the cable to the connector slot on the control panel pic. 3.1 - 3.3;...
123 mm 68 mm 3.2. HOW TO MOUNT ST-SA-CONTROL ON THE WALL? 9 mm • Turn the panel fig. 2.1. • Put it at the desired location on the wall pic. 8 - 11. Mark the positions of the mounting holes.
• Check the audio settings The colors are not correctly reflected on the screen • Contact the supplier Control panel doesn’t work • Contact the supplier Unable to update a software of the remote panel • Contact the supplier | EN ST-SA-CONTROL v2024.1...
4. PRODUCT INFORMATION 4.1. DESCRIPTION The ST-SA-Control remote control panel is designed for: • SALDA ventilation units and other devices based on PRV (RIS EKO 3.0, RIRS EKO 3.0), MCB/MiniMCB (Smarty, AmberAir, AmberAir Compact) controllers. Attention! • Some of the articles in this guide may not apply to you. It depends on the type of the control board on your device.
[ °C ] 2 OUTDOOR AIR [ °C ] 3 EXTRACT AIR CO [ PPM ] 4 SUPPLY AIR [ °C ] 5 EXHAUST AIR [ °C ] EXTRACT AIR RH [ % ] 5.2. MENU MENU ST-SA-CONTROL v2024.1 | EN...
ICON LABEL ICON LABEL 1 STATUS FILTERS 2 NIGHT COOLING ALARMS 3 BOOST SERVICE 4 DATE & TIME SETTINGS 5 WEEKLY SCHEDULE ABOUT 5.2.1. STATUS MENU » STATUS Detailed status of AHU. | EN ST-SA-CONTROL v2024.1...
Page 17
EXTRACT FAN SPEED [ % ] Options: FANS STATE • OFF • ON EXTRACT AIR RH Range: [ 0 .. 99 % ] SETPOINT Range: [ 15 .. 30 °C ] Options: STANDBY • OFF • ON ST-SA-CONTROL v2024.1 | EN...
EXTRACT FAN SPEED RPM [ RPM ] RETURN WATER TEMPERATURE [ °C ] OUTDOOR AIR DAMPER ACTUATOR Range: [ 0 .. 1 ] Range: [ SUMMER; WINTER; SEASON ALWAYS ] SOFTWARE VERSION 5.2.2. NIGHT COOLING MENU » NIGHT COOLING | EN ST-SA-CONTROL v2024.1...
5.2.3. BOOST MENU » BOOST LABEL DESCRIPTION BOOST TIMER Range: [ 0 .. 255 MINUTES] 5.2.4. DATE & TIME MENU » DATE & TIME ICON LABEL ICON LABEL 1 SET DATE & TIME 2 TIME KEEPING FUNCTION ST-SA-CONTROL v2024.1 | EN...
MENU » DATE & TIME » TIME KEEPING FUNCTION ST-SA-Control can keep the time for two days in case power is lost and provide time information for control board (needed for schedule function to work properly). If this function is disabled, time value will be read and displayed from control board (MCB control board).
5.2.7. ALARMS MENU » ALARMS 5.2.8. SERVICE MENU » SERVICE List of parameters depends on configuration of AHU and can be different. | EN ST-SA-CONTROL v2024.1...
Range: [ 15 .. 24 °C ] LOW LIMIT SUPPLY TEMPERATURE Range: [ 25 .. 40 °C ] HIGH LIMIT OUTDOOR TEMPERATURE Range: [ 10 .. 30 °C ] SETPOINT 5.2.8.2. DX COOLER MENU » SERVICE » DX COOLER | EN ST-SA-CONTROL v2024.1...
Range: [ 10 .. 30 °C ] SETPOINT 5.2.8.3. FANS MENU » SERVICE » FANS ICON LABEL ICON LABEL 1 SAF (SUPPLY AIR FAN) 3 OTHER 2 EAF (EXTRACT AIR FAN) 5.2.8.3.1. SAF MENU » SERVICE » FANS » SAF ST-SA-CONTROL v2024.1 | EN...
Range: [ 1 .. 65535 ] 5.2.8.6.8. EAF MENU » SERVICE » PI » SAF LABEL DESCRIPTION Range: [ 1 .. 65535 ] Range: [ 1 .. 65535 ] 5.2.8.7. ANTIFROST MENU » SERVICE » ANTIFROST | EN ST-SA-CONTROL v2024.1...
Page 33
• HEATEX • KLINGB DETECTION • TSETPOINT • TOUTSIDE • DEWP PLATET • OFF Options: FANS SPEED REDUCTION • OFF • ON Options: BYPASS/ROTOR • OFF • ON Options: PASSIVE TEMPERATURE • OFF CONTROL • ON ST-SA-CONTROL v2024.1 | EN...
SETPOINT HIGH LEVEL VALUE Range: [ 0 .. 100 % ] HIGH LEVEL TIMER Range: [ 0 .. 255 MINUTES ] Options: HIGH LEVEL FUNCTION • DISABLED • ENABLED 5.2.8.12. COMMUNICATION MENU » SERVICE » COMMUNICATION | EN ST-SA-CONTROL v2024.1...
MENU » SERVICE » LOGOUT 5.2.9. SETTINGS MENU » SETTINGS Settings of the ST-SA-Control remote controller. For detailed information see section "6.2.14. SETTINGS" on page 56, as the information provided is identical to MCB/MiniMCB control board's. | EN ST-SA-CONTROL v2024.1...
[ °C ] 3 OUTDOOR AIR [ °C ] STANDBY BLOCKING TIME LEFT THIS 4 Range: [ 0 .. 500 MINUTES ] 5 NEXT EVENT IN Range: [ 0 .. 24 HOURS ] 6.2. MENU MENU | EN ST-SA-CONTROL v2024.1...
Page 43
ICON LABEL ICON LABEL 1 STATUS 10 HOLIDAY SCHEDULE 2 NIGHT COOLING 11 ALARMS 3 BOOST 12 ALARMS HISTORY 4 SETPOINTS 13 OTHER 5 HUMIDITY 14 SETTINGS 6 FILTERS 15 ADJUSTER 7 HEATING SEASON 16 SERVICE ST-SA-CONTROL v2024.1 | EN...
ICON LABEL ICON LABEL 8 DATE & TIME 17 ABOUT 9 WEEKLY SCHEDULE 6.2.1. STATUS MENU » STATUS Detailed status of AHU. | EN ST-SA-CONTROL v2024.1...
Page 45
Range: [ 0 .. 100 % ] EXTRACT AIR CO Range: [ 0 .. 2000 PPM ] SOFTWARE VERSION CONFIGURATION VERSION HYDRAULIC HEATER WATER [ °C ] HYDRONIC PREHEATER WATER [ °C ] HYDRONIC COOLER WATER [ °C ] ST-SA-CONTROL v2024.1 | EN...
CURRENT EXTRACT AIR FLOW [ % ] CURRENT SUPPLY AIR DUCT PRESSURE [ Pa ] CURRENT EXTRACT AIR DUCT PRESSURE [ Pa ] CURRENT EXTRACT AIR FLOW /h ] 6.2.2. NIGHT COOLING MENU » NIGHT COOLING | EN ST-SA-CONTROL v2024.1...
○ TOO HIGH RH BOOSTING TIME — Range: [ 0 .. 600 MINUTES ] 6.2.6. FILTERS MENU » FILTERS Tap on timer display to reset its value. LABEL DESCRIPTION Options: RESET TIMER • NO ACTION • RESET ST-SA-CONTROL v2024.1 | EN...
TEMP. SETPOINT CORREC- Range: [ -15 .. 15 °C ] TION ON SEASON CHANGE 6.2.8. DATE & TIME MENU » DATE & TIME ICON LABEL ICON LABEL 1 SET DATE & TIME 2 TIME KEEPING FUNCTION | EN ST-SA-CONTROL v2024.1...
MENU » DATE & TIME » TIME KEEPING FUNCTION ST-SA-Control can keep the time for two days in case power is lost and provide time information for control board (needed for schedule function to work properly). If this function is disabled, time value will be read and displayed from control board (MCB control board).
• BUILDING PROTECTION • ECONOMY • COMFORT 6.2.11. ALARMS MENU » ALARMS 6.2.12. ALARMS HISTORY MENU » ALARMS HISTORY 6.2.13. OTHER MENU » OTHER LABEL DESCRIPTION FIRE DAMPER TESTING HOUR Range: [ 0 .. 23 HOURS ] ST-SA-CONTROL v2024.1 | EN...
6.2.14.1. COMMUNICATION MENU » SETTINGS » COMMUNICATION Settings of the RS485 connection. ICON LABEL ICON LABEL 1 MANUAL SETUP 2 AUTO SETUP 6.2.14.1.1. MANUAL SETUP MENU » SETTINGS » COMMUNICATION » MANUAL SETUP ST-SA-CONTROL v2024.1 | EN...
Auto search - search for multiple devices with different settings (don't know ID and other settings). ICON LABEL ICON LABEL 1 FIND SINGLE 3 AUTO SEARCH 2 FIND MULTIPLE 6.2.14.2. LANGUAGE MENU » SETTINGS » LANGUAGE | EN ST-SA-CONTROL v2024.1...
Screensaver will turn on after "Dimming delay" time runs out (MENU » SETTINGS » BRIGHTNESS). ICON LABEL ICON LABEL 1 NONE 3 CLOCK 2 DAMPED LOGO NOTE. Screensaver will only work if there is no active warnings or alarms. | EN ST-SA-CONTROL v2024.1...
MENU » SETTINGS » WI-FI MODULE » WI-FI MODULE To use a Wi-Fi module enable it. By default Wi-Fi module is disabled. LABEL DESCRIPTION Options: WI-FI MODULE • DISABLED • ENABLED 6.2.14.10.1. WI-FI MODULE MENU » SETTINGS » WI-FI MODULE | EN ST-SA-CONTROL v2024.1...
NETWORK WI-FI SELECTION MODULE VERSION 6 DHCP SOFTWARE UPDATE IP ADDRESS 6.2.14.10.2. AUTODISCOVER MENU » SETTINGS » WI-FI MODULE » AUTODISCOVER Autodiscover is used to automatically find a device in SALDA Air App. Autodiscover is enabled by default. ST-SA-CONTROL v2024.1 | EN...
6.2.14.10.3. AHUNAME MENU » SETTINGS » WI-FI MODULE » AHUNAME AHU name which is visible in SALDA Air app. Default name is "Default". 6.2.14.10.4. BMS PORT MODBUS MENU » SETTINGS » WI-FI MODULE » BMS PORT MODBUS Modbus TCP/IP port number. Default is 502.
MENU » SETTINGS » WI-FI MODULE » DHCP Enables/disables DHCP. Enabled by default. 6.2.14.10.7. IP ADDRESS MENU » SETTINGS » WI-FI MODULE » IP ADDRESS IP address of Wi-Fi module. Use this menu to enter IP address if DHCP is disabled. ST-SA-CONTROL v2024.1 | EN...
Subnet mask of Wi-Fi module. Use this menu to enter Subnet mask if DHCP is disabled. 6.2.14.10.9. GATEWAY ADDRESS MENU » SETTINGS » WI-FI MODULE » GATEWAY ADDRESS Gateway IP address of Wi-Fi module. Use this menu to enter Gateway IP address if DHCP is disabled. | EN ST-SA-CONTROL v2024.1...
MENU » SETTINGS » WI-FI MODULE » DNS ADDRESS DNS IP address of Wi-Fi module. Use this menu to enter DNS IP address if DHCP is disabled. 6.2.14.10.11. MAC ADDRESS MENU » SETTINGS » WI-FI MODULE » MAC ADDRESS MAC address of Wi-Fi module. ST-SA-CONTROL v2024.1 | EN...
MENU » SETTINGS » WI-FI MODULE » MODULE VERSION Software version of Wi-Fi module. 6.2.14.10.13. SOFTWARE UPDATE MENU » SETTINGS » WI-FI MODULE » SOFTWARE UPDATE Use this function to update Wi-Fi module software. ST-SA-Control must be online to use this function. | EN ST-SA-CONTROL v2024.1...
After changing settings, do not forget to save settings in MENU » ADJUSTER » SAVE SETTINGS. ICON LABEL ICON LABEL 1 AIRFLOW 5 SENSORS CORRECTION 2 6 SAVE SETTINGS 3 MANUAL CONTROL 7 LOGOUT 4 STATUS ST-SA-CONTROL v2024.1 | EN...
RECIRCULATION DAMPER OTHER 6.2.15.3.1. BLOCK VENTILATION CONTROL MENU » ADJUSTER » MANUAL CONTROL » BLOCK VENTILATION CONTROL LABEL DESCRIPTION Options: BLOCK VENTILATION • DISABLED CONTROL • ENABLED 6.2.15.3.2. HEATERS MENU » ADJUSTER » MANUAL CONTROL » HEATERS | EN ST-SA-CONTROL v2024.1...
SUPPLY/EXTRACT DAMPER 5 FIRE DAMPER 14 DX COOLER 6 STATUS INDICATION 15 SENSORS 7 OTHER 16 HEAT EXCHANGER 8 VERSION 17 HPC EXPANSION MODULE 9 HEATERS 6.2.15.4.1. TEMPERATURE SENSORS MENU » ADJUSTER » STATUS » TEMPERATURE SENSORS | EN ST-SA-CONTROL v2024.1...
Page 83
[ °C ] EXHAUST AIR [ °C ] HYDRONIC HEATER WATER [ °C ] HYDRONIC PREHEATER WATER [ °C ] HYDRONIC COOLER WATER [ °C ] CONTROL BOX [ °C ] AFTER HEAT EXCHANGER TEMPERATURE [ °C ] ST-SA-CONTROL v2024.1 | EN...
• ON Options: SUPPLY FILTER PRESSURE RELAY • INACTIVE • ACTIVE Options: EXTRACT FILTER PRESSURE RELAY • INACTIVE • ACTIVE Options: SUPPLY FAN WARNING • INACTIVE • ACTIVE Options: EXTRACT FAN WARNING • INACTIVE • ACTIVE | EN ST-SA-CONTROL v2024.1...
• ON Options: INPUT: CLOSED • OFF • ON Options: FIRE PROTECTION INPUT • OFF • ON Options: FIRE DAMPER TESTING • INACTIVE • ACTIVE 6.2.15.4.6. STATUS INDICATION MENU » ADJUSTER » STATUS » STATUS INDICATION | EN ST-SA-CONTROL v2024.1...
• OFF • ON Options: FANS SPEED SWITCH • OFF • ON Options: CONTROLLER CABINET HEATING • INACTIVE • ACTIVE Options: FIRE PLACE PROTECTION • INACTIVE • ACTIVE 6.2.15.4.8. VERSION MENU » ADJUSTER » STATUS » VERSION ST-SA-CONTROL v2024.1 | EN...
Options: PREHEATER MANUAL PROTECTION • OFF • ON Options: PREHEATER AUTOMATIC PROTECTION • OFF • ON Options: PREHEATER CIRCULATION PUMP PROTECTION • OFF • ON 6.2.15.4.11. BYPASS DAMPER MENU » ADJUSTER » STATUS » BYPASS DAMPER | EN ST-SA-CONTROL v2024.1...
• ACTIVE Options: POWER LINE • INACTIVE • ACTIVE Options: DEFROST INPUT • INACTIVE • ACTIVE Options: DX COOLER DEFROST • INACTIVE OUTPUT • ACTIVE DX COOLER CONTROL Range: [ 0 .. 100 % ] OUTPUT | EN ST-SA-CONTROL v2024.1...
• FAILURE • OK Options: HYDRONIC PREHEATER WATER • FAILURE • OK Options: HYDRONIC COOLER WATER • FAILURE • OK Options: CONTROL BOX • FAILURE • OK Options: AFTER HEAT EXCHANGER TEMPERATURE • FAILURE • OK ST-SA-CONTROL v2024.1 | EN...
• ACTIVE Options: SEGMENT DAMPER 3 • INACTIVE • ACTIVE Options: TOO HIGH CONDENSATION LEVEL • INACTIVE • ACTIVE PRESSURE [ Pa ] 6.2.15.4.17. HPC EXPANSION MODULE MENU » ADJUSTER » STATUS » HPC EXPANSION MODULE | EN ST-SA-CONTROL v2024.1...
Page 93
Options: RHPC ANY HYDRONIC HEATER INST. • INACTIVE • ACTIVE Options: COIL REMOTE STOP VENTILATION • INACTIVE • ACTIVE Options: COIL REMOTE PREPARING • INACTIVE • ACTIVE RHPC HEATING POWER RHPC PREHEATING POWER RHPC COOLING POWER ST-SA-CONTROL v2024.1 | EN...
MENU » ADJUSTER » LOGOUT 6.2.16. SERVICE MENU » SERVICE For detailed information about particular functions check the MCB manual. After changing settings, do not forget to save settings in MENU » SERVICE » SAVE SETTINGS. ST-SA-CONTROL v2024.1 | EN...
Page 96
ICON LABEL ICON LABEL 1 MAIN 8 SENSORS 2 FANS 9 COMMUNICATION 3 DAMPERS 10 RESTORE DEFAULTS 4 HEAT EXCHANGER 11 SAVE SETTINGS 5 HEATERS 12 RESTART AHU 6 COOLERS 13 LOGOUT 7 DIGITAL INPUTS | EN ST-SA-CONTROL v2024.1...
2 AIR TEMPERATURE CONTROL 8 FIRE PROTECTION 2 AIR TEMPERATURE CONTROLLER CABINET 3 9 PROTECTION HEATING 4 SYSTEM MODE SWITCH 10 REDUCTION FUNCTION 5 FANS SPEED SWITCH 11 COOKING HOOD 6 AIR FILTERS PROTECTION 12 CALIBRATIONS ST-SA-CONTROL v2024.1 | EN...
SUPPLY TEMPERATURE Range: [ 20 .. 60 °C ] HIGH LIMIT SUPPLY TEMPERATURE Range: [ 0 .. 1000 SECONDS ] LIMIT TIMEOUT Options: SUPPLY TEMPERATURE • NONE LIMIT ALARM ACTION • SHOW WARNING • STOP SYSTEM | EN ST-SA-CONTROL v2024.1...
• SUPPLY AIR • EXTRACT AIR • BOTH Options: FILTERS TIMER LIMIT • DISABLED • ENABLED FILTERS TIMER LIMIT Range: [ 1 .. 365 DAY] 6.2.16.1.7. FIRE PROTECTION 1 MENU » SERVICE » MAIN » FIRE PROTECTION 1 | EN ST-SA-CONTROL v2024.1...
Range: [ 0 .. 3000 ppm ] FROM SET POINT 6.2.16.1.11. COOKING HOOD MENU » SERVICE » MAIN » COOKING HOOD LABEL DESCRIPTION Options: SHOW ALARMS ON • DISABLED COOKING HOOD • ENABLED 6.2.16.1.12. CALIBRATIONS MENU » SERVICE » MAIN » CALIBRATIONS | EN ST-SA-CONTROL v2024.1...
• ACTIVATE 6.2.16.2. FANS MENU » SERVICE » FANS ICON LABEL ICON LABEL 1 FANS SPEED CONTROL 3 FANS PROTECTION 2 FANS VOLTAGE 6.2.16.2.1. FANS SPEED CONTROL MENU » SERVICE » FANS » FANS SPEED CONTROL ST-SA-CONTROL v2024.1 | EN...
EXTRACT AIR FAN CONTROL • DISABLED BY SUPPLY AIR FAN • ENABLED EXTRACT FAN SPEED FROM SUPPLY FAN SPEED Range: [ -100 .. 100 % ] DIFFERENCE 6.2.16.2.2. FANS VOLTAGE MENU » SERVICE » FANS » FANS VOLTAGE | EN ST-SA-CONTROL v2024.1...
Range: [ 1 .. 225 SECONDS ] 6.2.16.3.3. FIRE DAMPER MENU » SERVICE » DAMPERS » FIRE DAMPER LABEL DESCRIPTION Options: • NONE TYPE • ONE SWITCH • TWO SWITCH OPEN TIME Range: [ 0 .. 225 SECONDS ] | EN ST-SA-CONTROL v2024.1...
DO FIRE DAMPER TEST • DISABLED • ENABLED 6.2.16.4. HEAT EXCHANGER MENU » SERVICE » HEAT EXCHANGER ICON LABEL ICON LABEL 1 TYPE 2 FROST PROTECTION 6.2.16.4.1. TYPE MENU » SERVICE » HEAT EXCHANGER » TYPE ST-SA-CONTROL v2024.1 | EN...
Page 112
Range: [ 0 .. 225 SECONDS ] Options: • ONE DAMPER DAMPER TYPE • TWO SEGMENTS • THREE SEGMENTS • REMOTE CONTROLLER Options: TYPE • 0-10VDC • ON/OFF OUTPUT THRESHOLD Range: [ 0 .. 100 % ] | EN ST-SA-CONTROL v2024.1...
MENU » SERVICE » HEAT EXCHANGER » FROST PROTECTION » DEACTIVATION LABEL DESCRIPTION ANTIFROST DEACTIVATION Range: [ 0 .. 10 °C ] T. DIFFERENCE 6.2.16.4.2.3. PROTECTIONS MENU » SERVICE » HEAT EXCHANGER » FROST PROTECTION » PROTECTIONS | EN ST-SA-CONTROL v2024.1...
Page 115
• DISBALANCE • SLOW DOWN BY EXH. T. • ENABLED Options: USE RECIRCULATION • DISABLED • ENABLED OUTDOOR AIR Options: TEMPERATURE SENSOR • NO BEFORE PREHEATER • YES Options: USE BYPASS DAMPER/ • DISABLED ROTOR • ENABLED ST-SA-CONTROL v2024.1 | EN...
MENU » SERVICE » HEATERS » CONTROL POSITION LABEL DESCRIPTION Options: CONTROL POSITION • HEATER ON BASIC • PREHEATER ON BASIC 6.2.16.6. COOLERS MENU » SERVICE » COOLERS ICON LABEL ICON LABEL 1 HYDRONIC COOLER 2 DX COOLER | EN ST-SA-CONTROL v2024.1...
1 EXTERNAL CONTROL 5 FILTERS PRESSURE RELAY 2 FANS PROTECTION 6 FIRE DAMPER 3 HEATER PROTECTION HEAT EXCHANGER 4 COOLER PROTECTION 8 PREHEATER PROTECTION 6.2.16.7.1. EXTERNAL CONTROL MENU » SERVICE » DIGITAL INPUTS » EXTERNAL CONTROL | EN ST-SA-CONTROL v2024.1...
MENU » SERVICE » DIGITAL INPUTS » FANS PROTECTION LABEL DESCRIPTION Options: SUPPLY FAN PROTECTION • NO • NC Options: SUPPLY FAN WARNING • NO • NC Options: EXTRACT FAN PROTECTION • NO • NC Options: EXTRACT FAN WARNING • NO • NC ST-SA-CONTROL v2024.1 | EN...
• NC Options: EXTRACT AIR FILTER • NO • NC 6.2.16.7.6. FIRE DAMPER MENU » SERVICE » DIGITAL INPUTS » FIRE DAMPER LABEL DESCRIPTION Options: OPENED • NO • NC Options: CLOSED • NO • NC | EN ST-SA-CONTROL v2024.1...
Page 125
PREHEATER AUTOMATIC • NO PROTECTION • NC Options: PREHEATER CIRCULATION • NO PUMP PROTECTION INPUT • NC 6.2.16.8. SENSORS MENU » SERVICE » SENSORS ICON LABEL ICON LABEL 1 0-10VDC SENSORS 3 PRESSURE 2 TEMPERATURE SENSORS ST-SA-CONTROL v2024.1 | EN...
Page 128
ICON LABEL ICON LABEL HYDRONIC PREHEATER 1 SUPPLY AIR 6 WATER 2 EXTRACT AIR HYDRONIC COOLER WATER CONTROLLER CABINET 3 EXHAUST AIR 8 TEMPERATURE AFTER HEAT EXCHANGER 4 OUTDOOR AIR 9 TEMPERATURE 5 HYDRONIC HEATER WATER | EN ST-SA-CONTROL v2024.1...
Page 138
MENU » SERVICE » RESTORE DEFAULTS LABEL DESCRIPTION Options: RESTORE DEFAULTS • NO ACTION • RESTORE 6.2.16.11. SAVE SETTINGS MENU » SERVICE » SAVE SETTINGS LABEL DESCRIPTION Options: SAVE CHANGES TO EEPROM • NO ACTION • SAVE | EN ST-SA-CONTROL v2024.1...
Page 139
6.2.16.12. RESTART AHU MENU » SERVICE » RESTART AHU LABEL DESCRIPTION Options: RESTART AHU • NO ACTION • RESTART 6.2.16.13. LOGOUT MENU » SERVICE » LOGOUT 6.2.17. ABOUT MENU » ABOUT ST-SA-CONTROL v2024.1 | EN...
Page 140
• Follow local regulations regarding disposal of the equipment. • Bring the equipment to a recycling area or container in order to minimize the effect on the environment and public health. • For further information on recycling, please contact the seller or the supplier. | EN ST-SA-CONTROL v2024.1...
Directive 2009/125/EC establishing a framework for the setting of ecodesign requirements for energy‐related products, • the regulation by the Ministry of Economy of May 8, 2013 concerning the essential requirements as regards the restriction of the use of certain hazardous substances in electrical and electronic equipment, implementing provisions of RoHS directive 2011/65/EU. For compliance assessment, harmonized standards were used: PN‐EN 60730‐2‐9:2011, PN‐EN 60730‐1:2016‐10. Wieprz, 20.05.2019 ST-SA-CONTROL v2024.1 | EN...
3.4. when the unit was used not for its original purpose. 3.5. Company SALDA UAB is not responsible for potential loss of property or personal injury in cases where the Air Handling unit is manufactured without the control system and the control system is installed by the client or the third parties.
Page 143
The manufacturer reserves the right to refuse provision of free warranty servicing in cases when the warranty condi- tions listed below are disregarded. ST-SA-CONTROL v2024.1 | EN...
Page 144
Look at the product label. NOTE. The customer shall be required to complete the Product Maintenance Table. LINKS TO OTHER DOCUMENTS MCB MANUAL MINIMCB MANUAL MB-GATEWAY QUICK LAUNCH GUIDE https://select.salda.lt/file/mcb-en https://select.salda.lt/file/ https://select.salda.lt/file/ minimcb-en mbgatewayen Ragainės g. 100 +370 41 540 415 Šiauliai LT-78109, LITHUANIA...