1 Overview
This document provides guidance to connect, install and communicate to a HART device using the GW HART USB
MODEM.
This document assumes the user understands basic electrical concepts included 4-20 mA signals, control wiring, HART
communication, etc.
2 Download and installation
Download the latest drivers from http://www.phoenixcontact.net/qr/1003824/softw. Unzip the folder and run the Setup
utility following the onscreen instructions. The Setup utility installs the USB driver, the DTM files, and a GW HART USB
MODEM test utility tool.
3 Connecting the GW USB HART MODEM
Insert the USB connector into an open USB Type A port on the PC after the USB driver has been installed. Carefully
connect the mini-hook test leads to the HART device. Most HART devices have test loop connectors for this purpose.
Position the test leads so they cannot touch and cause a short circuit.
Make sure you always use the latest documentation.
It can be downloaded at:
© PHOENIX CONTACT 2019-08-19
Type-Description
GW HART USB MODEM
www.phoenixcontact.net/products
Description
USB HART modem
HART device
Windows® PC

Advertisement

loading
Need help?

Need help?

Do you have a question about the GW HART USB MODEM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Phoenix Contact GW HART USB MODEM

  • Page 1 GW HART USB MODEM installation Using the GW HART USB MODEM test utility and PACTware Quick Reference Guide QRG_915_EN_01_USB-HART-modem-installation.docx © PHOENIX CONTACT 2019-08-19 Pos. Qty. Order-No. Type-Description Description 1003824 GW HART USB MODEM USB HART modem HART device Windows® PC...
  • Page 2 The GW HART USB MODEM test utility provides a convenient way to verify the communication between the GW HART USB MODEM and the HART device. Open the GW HART USB MODEM test utility by accessing the shortcut in the start menu or navigate to the utility in the C:\Program Files (x86)\Phoenix Contact\GW HART USB MODEM Driver 64bit\bin directory.
  • Page 3 Figure 3: GW HART USB Test program If the HART device is not displayed after a scan, verify that the wiring is correct, and the GW HART USB MODEM is connected across the external 250 Ω resistor or the HART device. Alternatively, the HART address may be set to greater than 15 and will not appear during a scan.
  • Page 4 GW HART USB MODEM installation Select the GW HART USB MODEM from the Device for window and click the OK button. Figure 5: Device for window Connect to the GW HART USB MODEM by clicking the Connect icon. Figure 6: Connect QRG_915_EN_01_USB-HART-modem-installation.docx...
  • Page 5 GW HART USB MODEM installation Right click on the GW HART USB MODEM in the Project window and select Topology Scan. Figure 7: Open Topology Scan QRG_915_EN_01_USB-HART-modem-installation.docx PHOENIX CONTACT...
  • Page 6 GW HART USB MODEM installation The Topology Scan window will appear. Click the arrow button to begin scanning for HART devices. The GW HART USB MODEM will scan for HART devices address between 0 and 63. Figure 8: Initiate Topology Scan When the scan is complete, the Topology Scan will suggest the DTM that best represents the discovered HART device.
  • Page 7 In the Project tree, click on the newly added HART device and click the connect button. Double click on the HART device and the DTM will open. Configure the appropriate settings using the Menu/Variable window. The configuration options are dependent on the device manufacturer. Figure 10: Online parameterization PHOENIX CONTACT GmbH & Co. KG • 32825 Blomberg • Germany www.phoenixcontact.com...

This manual is also suitable for:

1003824