28
Setting the function
Select the mode/function/option/value using '▶', '◀' Button and con-
firm that using the '●' button after DIP switch No.5 is turned on.
5, 6, 8 Ton
7-Segment
SW01C
SW01D
( :confirm)
(reset)
SW02C
SW04C
( :backward)
(x:cancel)
SW03C
DIP-SWITCH
( :forward)
Mode
Function
Content Display1
Content
Display2
Content
áâ
Cool & Heat Selector
oFF
High Static Pressure
áã
oFF
Compensation mode
Night Low Noise
áä
oFF
mode
áæ
ODU address setting
-
Snow removal &
áç
oFF
rapid defrost
Airflow Adjusting for
áè
IDU (Heating capacity
oFF
à
up)
Target Pressure Ad-
áé
oFF
justing
High Efficiency Mode
áê
oFF
(Cooling Operation)
Compressor Max.
áâã
0
Frequency Limit
ODU Fan Max. RPM
áâä
0
Limit mode
Smart Load Control
áâå
oFF
Mode setting
Priority Heating Oper-
áãæ
oFF on/oFF
ation
* Functions save in EEPROM will be kept continuously, though the
system power was reset.
* DIP switch 3 can be OFF except when installing the only 4 series in-
door units (named ARNU***4).
2, 3, 4, 4.4 Ton
DIP-SW01 7 - Segment
SW04C
(x: cancel)
SW03C
(
: forward)
SW02C
(
: backward)
SW01C
(
: confirm)
SW01D (reset)
Option
Value
Action
Display3 Content Display4 Implement Display5
oP1
Selected
Change the
-
-
Blank
~oP2
the option
set value
oP1
Selected
Change the
-
-
Blank
~oP3
the option
set value
oP1
Selected
Change the
-
-
Blank
~oP15
the option
set value
Set the
Change the
-
-
0~254
Blank
value
set value
oP1
Selected
Change the
-
-
Blank
~oP3
the option
set value
Selected
Change the
on
-
-
Blank
the option
set value
oP1
Selected
Change the
-
-
Blank
~oP6
the option
set value
Selected
Change the
on
-
-
Blank
the option
set value
Selected
Change the
5~180
-
-
Blank
the option
set value
400
Selected
Change the
-
-
Blank
~1 200
the option
set value
oP1
Selected
Change the
-
-
Blank
~oP3
the option
set value
Selected
Change the
-
-
Blank
the option
set value
CAUTION
!
• To perform the otional funtion should be sure that All the IDU is off
mode, unless the function will not be performed.
Group Number setting
Group Number setting for Indoor Units
- Confirm the power of whole system(Indoor Unit, Outdoor Unit) is
OFF, otherwise turn off.
- The communication cables connected to CEN.A and CEN.B terminal
should be connected to central control of Outdoor Unit with care for
their polarity (A-A, B-B ).
- Turn the whole system on.
- Set the group and Indoor Unit number with a wired remote control.
- To control several sets of Indoor Units into a group, set the group ID
from 0 to F for this purpose.
Outdoor Units (External PCB)
SODU.B SODU.A
IDU.B
IDU.A
Remark
Save in
EEPROM
Save in
EEPROM
Example) Group number setting
Save in
EEPROM
1 F
Save in
Group Indoor unit
EEPROM
st
Save in
1
number indicate the group number
EEPROM
2nd number point out indoor unit number
Save in
Group recognizing the central controller
EEPROM
Save in
EEPROM
Save in
EEPROM
Save in
EEPROM
Save in
EEPROM
Save in
EEPROM
Save in
EEPROM
Cool & Heat selector (Fn 1)
Mode setting method
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn1" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","oP1","oP2" Push the '●' button
Cool & Heat Selection mode is set
CEN.B
CEN.A
DRY1
DRY2
GND
B(D)
A(C)
No.0 group (00~0F)
No.1 group (10~1F)
No.2 group (20~2F)
No.3 group (30~3F)
No.4 group (40~4F)
No.5 group (50~5F)
No.6 group (60~6F)
No.7 group (70~7F)
No.8 group (80~8F)
No.9 group (90~9F)
No. A group (A0~AF)
No. B group (B0~BF)
No. C group (C0~CF)
No. D group (D0~DF)
No. E group (E0~EF)
No. F group (F0~FF)