CoollogiC TouCh ConTrol SySTem – iom Table of Contents Introduction Menu Navigation Physical Dimensions Network Setup Communications Wiring Appendix A: CoolLogic Touch BAS Points List Configuration Appendix B: Module Physical Inputs and Outputs Bank Standard Alarm Function Wiring Diagram: Indoor/Outdoor Rated Panel Standard Features Warranty Menu Hierarchy...
CoollogiC TouCh ConTrol SySTem – iom Introduction GENERAL DESCRIPTION FEATURES The CoolLogic Touch Control System provides chilled Supports up to 12 dual-compressor modules and hot water temperature control algorithms Supports water-to-water, air-to-water banks maintaining precise temperature control for cooling, Supports Cooling only, Heating only, Heat heating, heat recovery, and simultaneous heating Recovery Only, SHC Heat Pump, SHC Heat and cooling applications.
CoollogiC TouCh ConTrol SySTem – iom Actual area is 7.25” w x 8.875”h Physical Dimensions Guides indicate .125” bleed all around Outdoor Indoor 24-1/2 24-25/32 30-3/8 The Outdoor CoolLogic Touch The Indoor CoolLogic Touch Control Panel is 80 lbs Control Panel is 75 lbs 10-7/8 11-7/32 PA G E : 4...
CoollogiC TouCh ConTrol SySTem – iom Communications Wiring COOLLOGIC TOUCh Figure 1: CoolLogic Touch Control System CONTROL SYSTEm WIRING A separate 115V power supply is required to power the CoolLogic Touch Control System. Communication between the CoolLogic Touch Control System and chiller modules requires a Shielded, twisted Pair (STP) Cat 6 or higher Ethernet cable home run connection.
CoollogiC TouCh ConTrol SySTem – iom Communications Wiring AVOIDING NOISE ShIELDED CAT 6 EThERNET CABLE Avoid running communication wires or sensor input Shielded, twisted pair (STP) category 6 (Cat 6) wires next to AC power wires or the controller’s relay Ethernet cable is a twisted-pair cable comprised of output wires.
CoollogiC TouCh ConTrol SySTem – iom Configuration CONFIGURE ThE CONTROLLER The default CoolLogic Touch bank control device instance is 516800. Any variance from this device Turn off the CoolLogic Touch Control System’s power number cannot be used without ClimaCool Custom Programming.
CoollogiC TouCh ConTrol SySTem – iom Configuration START ThE ChILLER SYSTEm SETUP mENU When power is first applied to the CoolLogic Touch Chiller system operation is determined by the values Control System, an initialization period occurs. assigned to the system variables, as predominantly The display shows the Home screen (Figure 8).
Page 9
CoollogiC TouCh ConTrol SySTem – iom Configuration Chiller Control Source: selects the start/stop Module used as N+1 or N+2: when there is cooling method the chiller bank uses. or heating capacity limiting, this option assigns the module number that is taken out of rotation. If no –...
CoollogiC TouCh ConTrol SySTem – iom Configuration SYSTEm SETUP SUBmENU SERVICE mENU Find the following submenu items on the System Use the options in the Service menu for diagnostics Setup page: and calibration. Cool & Heat Setpoints: sets the desired chilled and Select Trends to select and view trended data.
CoollogiC TouCh ConTrol SySTem – iom Configuration POWER UP ThE ChILLER BANK Clearing Alarms To clear an active alarm, Select “Alarms” from the Remove the Lock out/Tag out devices from the navigation menu then select the Trash Can Icon line-powered disconnect switch. 2.
CoollogiC TouCh ConTrol SySTem – iom Bank Standard Alarm Function LOOP DEFINITIONS The following are potential causes for the No Modules Available alarm: Loop 1 – Chilled water loop for all applications, Hot Failure of the entire bank or all modules water loop for standard Heat Pumps Loss of communications Loop 2 –...
CoollogiC TouCh ConTrol SySTem – iom Standard Features WATER FLOW SENSORS ALARm OUTPUT The CoolLogic Touch Control System has inputs for The relay output contact is closed whenever an differential pressure (DP) sensors, which measure and active latching or non-latching alarm condition is display pressure drops across the T water headers.
Page 14
CoollogiC TouCh ConTrol SySTem – iom Standard Features COmPRESSOR mINImUm OFF DELAY The minimum amount of time the compressor remains off after being disengaged. The default minimum off delay is 300 seconds. COmPRESSOR mINImUm ON DELAY The minimum amount of time the compressor remains on after being disengaged.
CoollogiC TouCh ConTrol SySTem – iom Menu Hierarchy Figure 14: User Access - Home Screen (Example) Tap any module to see its respective information and status (2) Previous (1) Modules populate this area as they are added Status (3) System Setup (4) Service Menu (5) Alarm Menu (6) COOLLOGIC TOUCh mENU...
CoollogiC TouCh ConTrol SySTem – iom Actual area is 7.25” w x 8.875”h Menu Navigation Guides indicate .125” bleed all around Home screen Module Info Module Info screen Alarms Module Status System Setup Service Menu Cool & Heat Setpoints Controller Con guration Module Con guration Free Cooling Settings PA G E : 1 6...
CoollogiC TouCh ConTrol SySTem – iom Network Setup CONNECTION TYPE DEVICE INSTANCE OF COOLLOGIC TOUCh CONTROL SYSTEm The default CONNECTION TYPE for the BACnet over ETHERNET to the WEB PORTAL is a shielded Cat 6 The CoolLogic Touch LS-1628u Control System is cable via an RJ-45 connector.
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table 1: CoolLogic Touch BAS Points List Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name Alarm Output Status alarm_output_stat SWST_HI loop2in_hi_alrm BAS Cool SWST_LO loop2in_lo_alrm...
Page 19
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M5 C2 Status m5_c2_stat M7 Position mod7_position M5 Used m5_used M8 Position mod8_position...
Page 20
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M11 C2 Defrost HWRT_LO loop3out_lo_alrm m11_c2_defrost_stat Command Status L3 Outlet OOR loop3out_oor_alrm M12 C1 Defrost...
Page 21
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name Open Header M7 Calc C1 open_hdr_bypass_defrost m7_c1_suc_superheat Bypass In Defrost Suc Superheat BAS SHC M7 C1 Cooling...
Page 22
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M7 C2 Discharge m7_c2_discharge_ M11 C2 Air Coil m11_aclt2_oor Temp OOR temperature_oor...
Page 23
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name m5_loop2_leaving_ M1 Low Outdoor M5 L2 LWT OOR m1_lo_oat_alarm water_temp_oor Air Temp Alarm...
Page 24
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M12 C1 M11 C1 Suction m11_c1_suction_ m12_c1_vfd_gen_alarm VFD General Alarm Temp OOR temperature_oor M12 C2...
Page 25
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M12 L1 Entering M11 C2 Liquid Line m12_loop1_entering_oor m11_c2_ll_temp_oor Temp OOR Temp OOR...
Page 26
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M1 C 1 EEV Comm m1_c1_eev_comm_loss_ M1 C2 Liquid Line m1_c2_liquid_line_ Loss Alarm alarm...
Page 27
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M6 C1 Liquid M3 C1 Heating m6_c1_liq_pres_oor m3_c1_ht_ll_temp Pressure OOR Liquid Line Temp m9_manager_lockout_...
Page 28
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M2 C2 Low Suction m2_c2_low_suc_pres_ M8 Manager m8_manager_lockout_ Pressure Alarm Lockout alrm...
Page 29
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M8 C1 VFD M2 C2 High m8_c1_vfd_gen_alarm m2_c2_hi_disc_tmp General Alarm Discharge Temp M6 C1 Hi Discharge...
Page 30
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M7 C1 Discharge m7_c1_discharge_ Communications m7_comm_lost Pressure OOR pressure_oor Alarm M7 Phase Loss...
Page 31
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M1 C2 Liquid Line M6 MFlow Alarm m6_module_flow_alarm m1_c2_ll_temp_oor Temp OOR M3 C1 Discharge...
Page 32
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M8 C1 Discharge M12 C1 m8_c1_disc_pres m12_c1_disc_pres Pressure Discharge Pressure M8 C1 Suction M11 Calc C1...
Page 33
CoollogiC TouCh ConTrol SySTem – iom Appendix A: CoolLogic Touch BAS Points List Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name M5 C1 Low Suction M3 C1 1004 m5_c1_low_suc_pres_alm m3_c1_xlow_suc_pres_ Pressure Alarm 1034...
CoollogiC TouCh ConTrol SySTem – iom Appendix B: Module Physical Inputs and Outputs Table 2: Module Physical Inputs and Outputs Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name Calc C1 2000 EEV C1 Manual EN bbvp_eev_c1_man_en BAV 2035 c1_suc_superheat...
Page 35
CoollogiC TouCh ConTrol SySTem – iom Appendix B: Module Physical Inputs and Outputs Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name Reset All Module 2104 C1 Demand Defrost c1_demand_defrost 2069 reset_alarms Alarms...
Page 36
CoollogiC TouCh ConTrol SySTem – iom Appendix B: Module Physical Inputs and Outputs Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name 2139 C1 Discharge Temp c1_disc_temp 2173 C1 Comp-Off Delay c1_minimum_off 2140 C2 Discharge Temp...
Page 37
CoollogiC TouCh ConTrol SySTem – iom Appendix B: Module Physical Inputs and Outputs Table continued from previous page Object Object Read/ Read/ Reference Name Reference Name Write Write Type Name Type Name L2 Evap 2-Way Isolation BAV 2206 loop2_evap_mwv2_stat 2225 isolation_valve2_alarm MWV 2 Status Valve 2 Alarm...
CoollogiC TouCh ConTrol SySTem – iom Wiring Diagram: Indoor/Outdoor Rated Panel Wiring diagram continued on next page PA G E : 3 8 r e v i s e d : J a n u a r y 2 7, 2 0 2 5 w w w.
Page 39
CoollogiC TouCh ConTrol SySTem – iom Wiring Diagram: Indoor/Outdoor Rated Panel Wiring diagram continued from previous page w w w. c l i m a c o o l c o r p . c o m r e v i s e d : J a n u a r y 2 7, 2 0 2 5 PA G E : 3 9...
CoollogiC TouCh ConTrol SySTem – iom Revision History Date Section Description Updated Name “CLT Bank Controller” to “CLT Control System”, Updated references of Modular chiller systems, UW and UA Updated screen examples and names of some screens Updated requirements for Cat 5e to Shielded, twisted pair (or STP) Cat 6 Updated Rotary Switch position to accomodate shielded Cat 6 selection.