Introduction General Description WARNING/ADVERTISSEMENT The CoolLogic Touch Control System provides leaving Disconnect power supply(ies) Debrancher avant d’entreprendre chilled and hot water liquid temperature control algorithms before servicing. Refer servicing le dépannage de l’appareil. which maintain precise temperature control for cooling, to qualified service personnel.
Communications Wiring CoolLogic Touch Control System Wiring Field Connections to the Modules The CoolLogic Touch Control Panel (see Figure 1) connects A separate 115 volt power supply is required to power the to the modules using the embedded ARC156 networking CoolLogic Touch Control Panel.
Page 5
Communications Wiring Avoiding Noise ARC 156 Wiring Specifications Avoid running communication wires or sensor input wires The table below lists the specifications for ARC156 wiring. next to AC power wires or the controller’s relay output The wire jacket and UL temperature rating specifications wires.
Configuration – CoolLogic Touch Control System Configuring the CoolLogic Touch Controller CoolLogic Touch Control System Operator Interface Turn off the CoolLogic Touch Controller’s power The CoolLogic Touch Control System offers an easy-to-use Using the rotary switches, set the CoolLogic Touch operator interface touch screen (Figure 5) which includes a Controller’s address .
Page 7
Configuration – CoolLogic Touch Control System Starting the Chiller Setup Menu When power is first applied to the CoolLogic Touch Control Chiller system operation is determined by the values assigned Panel, a 45 second initialization period will occur. The display to the system variables, as predominantly found in the Setup will show the home screen (Figure 7) .
Page 8
Configuration – CoolLogic Touch Control System Alarm Menu To Power Down Chiller Bank Up to 100 of the most recent occurrences stored with date Locate CoolLogic Touch Panel for the particular bank to and time . Access to this log is available through the keypad . be disabled .
Page 9
Configuration – CoolLogic Touch Control System Recommended for Extended Bank Shutdown Remove the command for “Remote Chiller Enable” using the BAS System or hard wire connection . Turn off the switch on the front of the CoolLogic Touch Control Panel Leave main power ON to the CoolLogic Touch Controller .
Standard Alarm Functions High Pressure Cutout High Leaving Condenser Water Temperature - This requires resetting both the module’s manual reset high Above 138° F pressure control switch and the CoolLogic Touch Control The CoolLogic Touch Control Panel will auto reset after the Panel’s software reset to resume operation.
Standard Features Chilled Water Flow Sensor menus . If the chiller is operating and it receives a chilled water reset command, the leaving chilled water temperature setting The CoolLogic Touch Control Panel has an input for a will be allowed to ramp toward the new setting at a rate of differential pressure sensor, which measures and displays 2°F every seven minutes .
Page 12
Standard Features Chilled Water Temperature Sensor Connections LonWorks LonTalk Communications ® Chilled water temperature monitoring (entering and leaving) Interface Option is a standard feature of the CoolLogic Touch Control System . It The CoolLogic Touch Control Panel provides an optional is accomplished by using a factory supplied pair of sensors and LonTalk communication interface between the chiller and...
Startup and Warranty Form CoolLogic CoolLogic Touch Module Size Selector Controller Page 1 of 3 Project Name: Start-Up Date: Chiller # Bank # System Setup Module 1 Size ......... . Module 2 Size .
Page 14
Startup and Warranty Form Page 2 of 3 Refrigeration Temp and Press Chiller # Bank # Cool PID Setup Discharge Pressure Available ....Suction Pressure Available .
Page 15
Startup and Warranty Form Page 3 of 3 Chiller # Bank # Router MAC Address IP Network # ..... __ __ __ __ __ MS/TP Network # .
CoolLogic Touch Screen Menu Hierarchy User Access – Home Screen (Example Only) Tap any module to CoolLogic Controller see its respective Level Configuration Previous information and status Module Level Configuration Modules populate screen as they are added Status (4) Alarm Menu (3) System Setup (2) Service Menu (7) CoolLogic Touch Menu...
Status User Access Home Module Level Module Info Configuration CoolLogic Controller Status Level Configuration System Setup Alarms Service Menu www.climacoolcorp.com...
Service User Access Service Menu Configure DPT Calibrate & Lock Device Temps Configure Low Alarm Lockout Ambient Heat Reset Reset Comp Diagnostic Manual Run times & Cycles Mode (FN7) www.climacoolcorp.com...
CoolLogic Touch Control System Network Setup Connection Type Device Instance of CoolLogic Touch Controller The default CONNECTION TYPE for the BACnet over The device instance number for the CoolLogic Touch ETHERNET to the WEB PORTAL is a CAT5 Cable via an Controller is 516800.
Appendix A Physical Hardwire Inputs and Outputs The CoolLogic Touch Control Panel with I/O Pro 8/12U - Quick Reference Guide Input Points Input # Description Input Type Bank Chilled Water Outlet Temperature AI - Thermistor/RTD Bank Chilled Water Entering Temperature AI - Thermistor/RTD Bank Condenser Water Outlet Temperature AI - Thermistor/RTD...
Page 30
15 S . Virginia Oklahoma City, OK 73106 Phone: 405.815.3000 Fax: 405.815.3052 www .climacoolcorp .com ClimaCool works continually to improve its products. As a result, the design and specifications of each product at the time for order may be changed without notice and may not be as described herein.