Download Print this page
Siemens SIMATIC ET 200MP IM 155-5 PN HF Manual

Siemens SIMATIC ET 200MP IM 155-5 PN HF Manual

Interface module
Hide thumbs Also See for SIMATIC ET 200MP IM 155-5 PN HF:

Advertisement

Quick Links

IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)

Advertisement

loading
Need help?

Need help?

Do you have a question about the SIMATIC ET 200MP IM 155-5 PN HF and is the answer not in the manual?

Questions and answers

Summary of Contents for Siemens SIMATIC ET 200MP IM 155-5 PN HF

  • Page 1 IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
  • Page 2 Preface Guide to documentation SIMATIC Product overview Wiring ET 200MP IM 155-5 PN HF Interface Module Parameter (6ES7155-5AA00-0AC0) Interrupts and diagnostic, error, and system alarms Equipment Manual Technical specifications Dimension drawing Response times 03/2020 A5E32840985-AC...
  • Page 3 Note the following: WARNING Siemens products may only be used for the applications described in the catalog and in the relevant technical documentation. If products and components from other manufacturers are used, these must be recommended or approved by Siemens. Proper transport, storage, installation, assembly, commissioning, operation and maintenance are required to ensure that the products operate safely and without any problems.
  • Page 4 Purpose of the documentation This manual supplements the system manual S7-1500, ET 200MP Automation system (https://support.industry.siemens.com/cs/ww/en/view/59191792). Functions that generally relate to the system are described in this manual. The information provided in this manual and in the system/function manuals supports you in commissioning the system.
  • Page 5 Siemens' products and solutions undergo continuous development to make them more secure. Siemens strongly recommends that product updates are applied as soon as they are available and that the latest product versions are used. Use of product versions that are no longer supported, and failure to apply the latest updates may increase customers' exposure to cyber threats.
  • Page 6 Table of contents Preface ..............................3 Guide to documentation .......................... 7 Product overview ..........................11 Properties ..........................11 Functions ..........................14 2.2.1 PROFINET IO ......................... 14 2.2.2 Configuration control (option handling) ................... 20 2.2.3 System redundancy on S7-400H .................... 20 Wiring ..............................
  • Page 7 S7-1500 and ET 200MP systems, e.g. diagnostics, communication, motion control, Web server, OPC UA. You can download the documentation free of charge from the Internet (https://support.industry.siemens.com/cs/ww/en/view/109742691). Changes and supplements to the manuals are documented in a Product Information. You can download the product information free of charge from the Internet (https://support.industry.siemens.com/cs/us/en/view/68052815).
  • Page 8 You must register once to use the full functionality of "mySupport". You can find "mySupport" on the Internet (https://support.industry.siemens.com/My/ww/en). "mySupport" - Documentation In the Documentation area in "mySupport" you can combine entire manuals or only parts of these to your own manual.
  • Page 9 Solutions are shown in interplay with multiple components in the system - separated from the focus on individual products. You will find the application examples on the Internet (https://support.industry.siemens.com/sc/ww/en/sc/2054). TIA Selection Tool With the TIA Selection Tool, you can select, configure and order devices for Totally Integrated Automation (TIA).
  • Page 10 You can find SIEMENS PRONETA on the Internet (https://support.industry.siemens.com/cs/ww/en/view/67460624). SINETPLAN SINETPLAN, the Siemens Network Planner, supports you in planning automation systems and networks based on PROFINET. The tool facilitates professional and predictive dimensioning of your PROFINET installation as early as in the planning stage. In addition, SINETPLAN supports you during network optimization and helps you to exploit network resources optimally and to plan reserves.
  • Page 11 Product overview Properties Order number 6ES7155-5AA00-0AC0 View of the module Figure 2-1 View of the IM 155-5 PN HF interface module IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...
  • Page 12 – PROFINET IO connection using RJ45 bus connector – Pulling and plugging I/O modules on the active backplane bus (multi hot swapping) You can find additional information, in the Active backplane bus (https://support.industry.siemens.com/cs/ww/en/view/109769815)Equipment Manual. ● Supported functions (Page 14) Maximum configuration ●...
  • Page 13 Product overview 2.1 Properties The actual gross data length for input and output data depends on the number and type of I/O modules used and is calculated as follows: ● Actual gross data length = net data length + number of I/O submodules (without user data, input or output data) + number of I/O modules (input and output data) + 4 bytes for interface module + 1 byte for active backplane bus The result of the actual gross data length calculation applies to both input and output data.
  • Page 14 Product overview 2.2 Functions Functions 2.2.1 PROFINET IO Introduction The interface module supports the following PROFINET IO functions: ● Integrated switch with 2 ports ● Supported Ethernet services: ping, arp, SNMP, LLDP ● Port diagnostics ● Deactivating ports ● Isochronous real-time communication (IRT) ●...
  • Page 15 Docking station • The usability of the PROFINET IO functions depends on the configuration software (Siemens and/or third party). Below, the usability of the PROFINET IO functions is described for STEP 7 only. No validity check of Shared Device projects...
  • Page 16 You can find additional information on configuration of synchronized PROFINET devices in sync domains in the STEP 7 online help and ● As of STEP 7 V12, in the PROFINET with STEP 7 (http://support.automation.siemens.com/WW/view/en/49948856) function manual ● As of STEP 7 V5.5, in the PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) manual...
  • Page 17 You can find additional information in the STEP 7 online help and ● As of STEP 7 V12, in the PROFINET with STEP 7 (http://support.automation.siemens.com/WW/view/en/49948856) function manual ● As of STEP 7 V5.5, in the PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) manual...
  • Page 18 You can find additional information in the STEP 7 online help and ● As of STEP 7 V12, in the PROFINET with STEP 7 (http://support.automation.siemens.com/WW/view/en/49948856) function manual ● As of STEP 7 V5.5, in the PROFINET System Description (http://support.automation.siemens.com/WW/view/en/19292127) manual Shared Device IO device that makes its data available to up to four IO controllers.
  • Page 19 You can find additional information in the STEP 7 online help and ● As of STEP 7 V12, in the PROFINET with STEP 7 (http://support.automation.siemens.com/WW/view/en/49948856) function manual System redundancy S2 An IO device with S2 system redundancy supports redundant ARs.
  • Page 20 Reference You can find more information ● In chapter Configuration control (option handling) (Page 25) ● On the Internet (http://support.automation.siemens.com/WW/view/en/29430270) ● In the STEP 7 online help. 2.2.3 System redundancy on S7-400H Interface to H-CPUs with system redundancy When system redundancy is used, you can connect the IM 155-5 PN HF (6ES7155-5AA00- 0AC0) interface module to CPUs 41x-5H PN/DP (version 6.0 or higher) of the S7-400.
  • Page 21 Ground Additional information You can find additional information on connecting the interface module and on accessories (RJ45 bus connector) in the system manual S7-1500, ET 200MP Automation system (https://support.industry.siemens.com/cs/ww/en/view/59191792). IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...
  • Page 22 Wiring 3.2 Block diagram Block diagram Block diagram ① Electronics 24 V DC supply voltage ② PROFINET 2-port switch Ground ③ Backplane bus interface RUN LED (green) ④ Internal supply voltage ERROR LED (red) X80 24 V DC Infeed of supply voltage MAINT LED (yellow) PN X1 P1 PROFINET interface X1 port 1...
  • Page 23 Parameter Parameters Table 4- 1 Parameters for IM 155-5 PN HF interface module Parameters Value range Default setting Efficiency range Connection to supply voltage Connection/No con- Connection ET 200MP nection Configuration control Disable/enable Disable ET 200MP Description of parameters 4.2.1 Connection to supply voltage L+ Parameter "Connection to supply voltage L+"...
  • Page 24 Reference See the section on the power budget and the forming of power segments in the system manual S7-1500, ET 200MP Automation system (https://support.industry.siemens.com/cs/ww/en/view/59191792). Requirement In order to generate diagnostics, the IM 155-5 PN HF interface module parameters must have been assigned once.
  • Page 25 Parameter 4.3 Configuration control (option handling) 4.2.2 Configuration control (option handling) "Configuration control" parameter You can use this parameter to enable the configuration control function in the ET 200MP Distributed I/O System. Note If you configure the enable, the ET 200MP distributed I/O system requires a control data record 196 from the user program in order for the ET 200MP distributed I/O system to operate the I/O modules.
  • Page 26 Parameter 4.3 Configuration control (option handling) Rules: Arrangement of the modules The following table shows the slot number assignment: Table 4- 2 Assignment of slot numbers Slot Modules Note Power supply module (optional) Before the interface module Interface module Interface module (slot 1) is not an ele- ment of the configuration control, but rather controls this 2 - 31...
  • Page 27 (Page 11) and the section on the power budget in the system manual S7-1500, ET 200MP Automation system (https://support.industry.siemens.com/cs/ww/en/view/59191792). Particularly for a power supply (PS) module on slot 0, we recommend that you avoid reconfiguration.
  • Page 28 Parameter 4.3 Configuration control (option handling) Combination of configuration control and Shared Device The configuration control function in a Shared Device is therefore only for the modules of the IO controller that has subscribed to the interface module. Modules that are assigned to another IO controller or not assigned at all cannot be specified as real slots (Shared Device on module level).
  • Page 29 Parameter 4.3 Configuration control (option handling) 4.3.2 Feedback data record Feedback data record The feedback data record provides information on the accuracy of the module assignment and gives you the chance to detect assignment errors in the control data record. The feedback data record is mapped by a separate data record 197.
  • Page 30 Parameter 4.3 Configuration control (option handling) Error messages The following error messages are returned if an error occurs during reading of the feedback data record: Table 4- 7 Error messages Error code Meaning 80B1 Invalid length 80B5 Configuration control not configured 80B8 Parameter error IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
  • Page 31 Parameter 4.3 Configuration control (option handling) 4.3.3 Configure configuration control without empty slots Operating principle The modules actually not required do not exist. The configuration is pushed together to the left in the direction of IM 155-5 PN HF. Figure 4-1 Configure configuration control without empty slots IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...
  • Page 32 Parameter 4.3 Configuration control (option handling) Data record of the example The following table shows the structure of the control data record for the above example. Table 4- 8 Data record for example "Configure configuration control without empty slots" Byte Element Code Explanation...
  • Page 33 Parameter 4.3 Configuration control (option handling) 4.3.4 Extending the configuration Operating principle You can add modules at the end of the configuration with this procedure. The configured configuration can also be extended from the center based on freely selectable slot assignment.
  • Page 34 Parameter 4.3 Configuration control (option handling) Data record of the example The following table shows the structure of the control data record for the above example. Table 4- 9 Data record for example "Extending the configuration" Byte Element Code Explanation Block length Header Block ID...
  • Page 35 Parameter 4.3 Configuration control (option handling) 4.3.5 Combining configurations Operating principle You can combine the different procedures with configuration control. Figure 4-3 Combining configurations IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...
  • Page 36 Parameter 4.3 Configuration control (option handling) Data record of the example The following table shows the structure of the control data record for the above example. Table 4- 10 Data record for example "Combining configurations" Byte Element Code configura- Code configura- Explanation tion 1 tion 2...
  • Page 37 Interrupts and diagnostic, error, and system alarms Status and error displays Introduction Diagnostics by means of LED display is an initial tool for error localization. To narrow down the error, you usually evaluate the display of the CPU, the display of the module status in STEP 7 or the diagnostics buffer of the CPU.
  • Page 38 Interrupts and diagnostic, error, and system alarms 5.1 Status and error displays Meaning of the LEDs RUN/ ERROR/ MAINT Table 5- 1 Meaning of the LEDs RUN/ ERROR/ MAINT LEDs Meaning Remedy ERROR MAINT Supply voltage not present or too low at Check the supply voltage or turn it on at the interface module interface module.
  • Page 39 Interrupts and diagnostic, error, and system alarms 5.1 Status and error displays Meaning of the LEDs P1 LINK/TX/RX, P2 LINK/TX/RX Table 5- 2 Meaning of the LEDs P1 LINK/TX/RX, P2 LINK/TX/RX LEDs Meaning Remedy P1 LINK/TX/RX, P2 LINK/TX/RX There is no Ethernet connection between the Check whether the bus cable to the switch/IO PROFINET interface of your PROFINET device controller is interrupted.
  • Page 40 S7-1500 CPU, to the S7-1500 CPU web server, to the HMI device and in STEP 7. For additional information on the system diagnostics, refer to the System diagnostics function manual (http://support.automation.siemens.com/WW/view/en/59192926). IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...
  • Page 41 Interrupts and diagnostic, error, and system alarms 5.2 Interrupts 5.2.1 Triggering of a diagnostic interrupt Triggering of a diagnostic interrupt For an incoming or outgoing event (e.g., wire break on a channel of an I/O module), the module triggers a diagnostic interrupt if this is configured accordingly in STEP 7 (TIA Portal). The CPU interrupts user program execution and executes the diagnostic interrupt OB.
  • Page 42 You can find the structure of the diagnostic data records and programming examples in the programming manual From PROFIBUS DP to PROFINET IO (http://support.automation.siemens.com/WW/view/en/19289930) and in the application example on the Internet (http://support.automation.siemens.com/WW/view/en/24000238). IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
  • Page 43 5.3 Alarms Causes of error and corrective measures The error causes and corrective measures of the diagnostic alarms are described in the manuals for the I/O modules (http://support.automation.siemens.com/WW/view/en/67296522/133300) in the Interrupts/Diagnostic alarms section. See also Channel diagnostics (Page 45) IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
  • Page 44 Interrupts and diagnostic, error, and system alarms 5.3 Alarms 5.3.2 Maintenance events Triggering of a maintenance event The PROFINET interface of the interface module supports the diagnostic concept and maintenance concept in PROFINET according to the IEC 61158-6-10 standard. The goal is to detect and remove potential problems as soon as possible.
  • Page 45 Interrupts and diagnostic, error, and system alarms 5.3 Alarms 5.3.3 Channel diagnostics Function Channel diagnostics provides information about channel faults in modules. Channel faults are mapped as channel diagnostics in IO diagnostic data records. The "RDREC" instruction is used to read the data record. Structure of the diagnostic data records ●...
  • Page 46 Error IM power supply: Power supply not active or power supply active Additional information You can find additional information on maximum configuration, power budget and power segments in the system manual S7-1500, ET 200MP Automation system (https://support.industry.siemens.com/cs/ww/en/view/59191792). Structure USI = W#16#0001 Table 5- 8 Structure of USI = W#16#0001...
  • Page 47 Interrupts and diagnostic, error, and system alarms 5.3 Alarms Structure USI = W#16#0002 Table 5- 9 Structure of the USI = W#16#0002 Data block name Contents Note Bytes W#16#0002 Manufacturer-specific diagnostics if the permitted number of power supply modules is exceeded Followed by 3 reserved bytes Reserved Reserved...
  • Page 48 Interrupts and diagnostic, error, and system alarms 5.3 Alarms USI structure = W#16#0005 Table 5- 12 USI structure = W#16#0005 Data block name Contents Note Bytes W#16#0005 Manufacturer-specific diagnostics if there is more than one bus master module (IM/CPU) Followed by 4 reserved bytes Reserved Reserved Reserved...
  • Page 49 Interrupts and diagnostic, error, and system alarms 5.3 Alarms USI structure = W#16#0007 Table 5- 14 USI structure = W#16#0007 Data block name Contents Note Bytes W#16#0007 Manufacturer-specific diagnostics if the configuration of the interface module power supply is different from the parameterized configuration Followed by 3 reserved bytes Reserved...
  • Page 50 Additional information You can find additional information on maximum configuration, power budget and power segments in the system manual S7-1500, ET 200MP Automation system (https://support.industry.siemens.com/cs/ww/en/view/59191792). See also: Status and error displays (Page 37) IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
  • Page 51 Interrupts and diagnostic, error, and system alarms 5.3 Alarms 5.3.5 STOP of the IO controller and recovery of the IO device STOP of the SIMATIC IO controller Diagnostics received from the IO device while the IO controller is in STOP state do not initiate a call of the corresponding OBs when the IO controller starts up.
  • Page 52 Technical specifications Technical specifications of the IM 155-5 PN HF The following table shows the technical specifications as of 03/2020. You will find a data sheet including daily updated technical specifications on the Internet (https://support.industry.siemens.com/cs/de/de/pv/6ES7155-5AA00-0AC0/td?dl=en). Article number 6ES7155-5AA00-0AC0 General information...
  • Page 53 Technical specifications Article number 6ES7155-5AA00-0AC0 Input current Current consumption (rated value) 0.2 A Current consumption, max. 1.2 A Inrush current, max. I²t 0.09 A²·s Power Infeed power to the backplane bus 14 W Power available from the backplane bus 2.3 W Power loss Power loss, typ.
  • Page 54 Technical specifications Article number 6ES7155-5AA00-0AC0 Autocrossing • Protocols PROFINET IO Device Services – Isochronous mode – Open IE communication – – PROFIenergy – Prioritized startup – Shared device – Number of IO Controllers with shared device, max. Redundancy mode • MRPD •...
  • Page 55 Technical specifications Article number 6ES7155-5AA00-0AC0 Yes; 2x green-yellow LEDs Connection display LINK TX/RX • Potential separation between backplane bus and electronics between PROFINET and all other circuits Yes; 1 500 V AC between supply and all other circuits Isolation Isolation tested with 707 V DC (type test) Ambient conditions Ambient temperature during operation...
  • Page 56 Dimension drawing The dimension drawing of the module on the mounting rail, as well as a dimension drawing with open front panel, are provided in the appendix. Always observe the specified dimensions for installation in cabinets, control rooms, etc. Dimension drawings of the IM 155-5 PN HF interface module Figure A-1 Dimension drawing of the IM 155-5 PN HF interface module, front and side views IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0)
  • Page 57 Dimension drawing Dimension drawing of the IM 155-5 PN HF interface module, side view with open front cover Figure A-2 Dimension drawing of the IM 155-5 PN HF interface module, side view with open front cover IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...
  • Page 58 Response times Response times of the ET 200MP Introduction The response time of the IM 155-5 PN HF is made up of: ● The update time configured for the IM as IO device. plus ● The backplane bus cycle time. Note Validity of the formula The following formula does not apply to Shared Device mode.
  • Page 59 Response times B.1 Response times of the ET 200MP Example configuration for the calculation of the backplane bus cycle time The following are used in the example: Table B- 1 Example configuration for the calculation of the backplane bus cycle time I/O module Output data Input data...
  • Page 60 510 μs + (500 μs x 1 + 500 μs) = 510 μs + 1000 μs = 1510 μs Reference Additional information about performance measurements is available on the Internet (http://support.automation.siemens.com/WW/view/en/34677186/136000&cspltfrm=0&cssw=0 &csbinh=5). IM 155-5 PN HF Interface Module (6ES7155-5AA00-0AC0) Equipment Manual, 03/2020, A5E32840985-AC...

This manual is also suitable for: