Standard response pendent sprinkler (k19.6)

Advertisement

Quick Links

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com
Visit the VIking website for the latest edition of this technical data page www.vikinggroupinc.com
1. DESCRIPTION
Viking Standard Response Control Mode Specific Application (CMSA) Pendent
Sprinkler VK592 is a thermosensitive fusible element type spray sprinkler. With a
19.6 nominal K-Factor, the sprinkler provides greater flows at lower pressures than
sprinklers with smaller K-Factors. This feature allows reduced pipe sizing for hydrauli-
cally calculated sprinkler systems, and provides the higher densities required to allow
an increase in the hazard classification of an occupancy. Viking Standard Response
Sprinkler VK592 was subjected to full-scale high piled storage fire testing and is UL
Listed, FM Approved, and VdS Approved for use in protecting high-piled storage.
Viking Sprinkler VK592 is intended to protect Class I-IV commodities and plastic and
rubber commodities (cartoned, unexpanded only) stored palletized, solid piled, bin
boxes, shelf storage, and single, double, multiple row, and portable open rack storage
(no open-top containers or solid shelves). Sprinkler VK592 may also be used to protect
on-floor storage of idle wood pallets. Refer to Approval Chart 1 and Design Criteria
on pages 3-4 for UL Listing requirements, and refer to Approval Chart 2 and Design
Criteria on page 8 for FM Approval requirements that must be followed.
NOTE: Sprinkler VK592 is NOT approved for protecting expanded plastics, exposed
unexpanded plastics, rolled paper, baled cotton, aerosols, or rubber tires.
2. LISTINGS AND APPROVALS
UL Listed: Category VNIV
FM Approved: Class 2036
VdS Approved: Certificate G4080016
Refer to Approval Chart 1 and Design Criteria on pages 3-4 for UL Listing requirements, for the U.S. and Canada, and refer
to Approval Chart 2 and Design Criteria on page 8 for FM Approval requirements that must be followed.
3. TECHNICAL DATA
Specifications:
Available since 2008.
Maximum Working Pressure: 175 psi (12 bar). Factory tested hydrostatically to 500 psi (34.5 bar).
Thread size: Base Part No. 14243: 1" NPT, Part No. 15468: 25 mm BSPT
Nominal K-Factor: 19.6 U.S. (282.6 metric
* Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
Overall Length: 3-3/16" (81 mm)
Covered by one or more of the following patents: US5,829,532; US6,059,044; US6,336,509; US6,502,643; US6,868,917
Material Standards:
Sprinkler Frame: Brass UNS-C84400
Deflector: Phosphor Bronze UNS-C51000
Seat and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400
Compression Screw: Stainless Steel UNS-S31603
Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon Tape
Trigger and Support: Stainless Steel UNS-S31600
Fusible Element Assembly: Phosphor Bronze UNS-C51000, polyurethane coated
Ordering Information: (Also refer to the current Viking price list.)
Order Standard Response Control Mode Specific Application Pendent Sprinkler VK592 by adding the appropriate suffix for the
sprinkler temperature rating to the sprinkler base part number.
Finish Suffix: Brass = A
Temperature Suffix: 160 °F (71 °C) = C, 205 °F (96 °C) = E
For example, sprinkler VK592 with a Brass finish, with 1" NPT threads, and a 160 °F (71 °C) temperature rating = Part No. 14243AC.
Available Finishes And Temperature Ratings: Refer to Table 1.
Accessories: (Also refer to the "Sprinkler Accessories" section of the Viking data book.)
Form No. F_033108
12.15.2021 Rev 21.2
TECHNICAL DATA
)
*
STANDARD RESPONSE
PENDENT SPRINKLER
VK592 (K19.6)
(CONTROL MODE SPECIFIC APPLICA-
Replaces Form No. F_033108 Rev 21.1
(Revised UL image.)
Page 1 of 8

Advertisement

loading
Need help?

Need help?

Do you have a question about the VK592 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Viking VK592

  • Page 1 Temperature Suffix: 160 °F (71 °C) = C, 205 °F (96 °C) = E For example, sprinkler VK592 with a Brass finish, with 1” NPT threads, and a 160 °F (71 °C) temperature rating = Part No. 14243AC. Available Finishes And Temperature Ratings: Refer to Table 1.
  • Page 2 Refer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Model VK592 Sprinkler is available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation.
  • Page 3 UL Listing Requirements: (NOTE: The FM Approval requirements differ from UL and/or NFPA criteria. Refer to page 8 for FM requirements.) Design Criteria: Sprinkler VK592 is UL Listed for use in the U.S. and Canada for High Piled Storage Occupancies with the minimum operating pres- sures as indicated in Tables 3-9 on pages 5-6.
  • Page 4 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the VIking website for the latest edition of this technical data page www.vikinggroupinc.com UL Listing Requirements (continued): • The distance between sprinklers doesn’t exceed 12 ft (3.7 m).
  • Page 5 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the VIking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 2: UL-PROTECTION AREAS AND MAXIMUM SPACING OF VK592 SPRINKLERS Ceiling/Roof Heights up to 40 ft (12.2 m)
  • Page 6 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the VIking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 6: UL DESIGN CRITERIA - SINGLE-, DOUBLE-, AND MULTIPLE-ROW RACK STORAGE (WITHOUT SOLID SHELVES) OF CLASS I-IV COMMODITIES STORED OVER 25 ft (7.6 m) HIGH...
  • Page 7 The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Visit the VIking website for the latest edition of this technical data page www.vikinggroupinc.com TABLE 10: POSITIONING SPRINKLER VK592 TO AVOID...
  • Page 8 • 2-0 and 8-9). 2. Sprinkler VK592 is also FM Approved as a standard response pendent Non-Storage sprinkler as indicated in the FM Approval Guide. • For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0).
  • Page 9 Refer to the appropriate technical data page and NFPA standards for complete care, handling, installation, and maintenance instructions. For additional product and system information Viking data pages and installation instructions are available on the Viking Web site at www.vikinggroupinc.com.
  • Page 10 * Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www. vikinggroupinc.com.
  • Page 11 • while ceiling finish work is being completed. Use only the designated Viking recessed sprinkler wrench (refer to the appropriate sprinkler data page) to install these sprinklers. NOTE: The protective cap is • temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed.
  • Page 12 Take care not to crack the wax coating on the units. • For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after •...
  • Page 13 For more information, go to www.P65Warnings.ca.gov 2. WARRANTY TERMS AND CONDITIONS For details of warranty, refer to Viking’s current list price schedule at www.vikinggroupinc.com or contact Viking directly. New Bulletin Form No. F_111218 18.11.15...