PS-2LSP Series
Liquid Static Pressure Transmitters, Nema 4X
Product Description
The PS-2LSP Series transmitter is designed with a single remote sensor that enables it to accept high pressure in several ranges up to 500
PSI, 35 Bar or 3500 kPa. All models can handle overload pressure 2X the maximum full-scale range and burst pressure is 5X the maximum
full-scale range.
Features include field selectable pressure ranges and output signal types, output reversal and slow-dampening for the most flexible
applications. The output signal is factory calibrated and temperature compensated for the highest start-up accuracy.
Ensure that the maximum individual port pressure does not exceed the highest pressure range of the unit. For example, the
highest individual port pressure on a PS-2LSP0100P Range Code is 100 PSI. Exceeding this may damage the sensors and
give erroneous readings. See Figure 13 for ratings.
General Installation Requirements
For proper installation and subsequent operation of each device, pay special attention to the following recommendations:
-
Upon unpacking the product, inspect the contents of the carton for shipping damages. Do not install damaged device.
-
Avoid areas where corroding, deteriorating or explosive vapors, fumes or gases may be present.
-
Ensure that all equipment is installed according to local, regional, and national regulations.
Personal injury or loss of life may occur if you do not follow a procedure as specified.
Equipment damage or loss of data may occur if you do not follow a procedure as specified.
Take reasonable precautions to prevent electrostatic discharges to the controller when installing, servicing or operating the
controller. Discharge accumulated static electricity by touching one's hand to a well-grounded object before working with
the controller.
H a r d w a r e I n s t a l l a t i o n G u i d e
Figure 1: PS-2LSP Series

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PS-2LSP Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Distech Controls PS-2LSP Series

  • Page 1 Product Description The PS-2LSP Series transmitter is designed with a single remote sensor that enables it to accept high pressure in several ranges up to 500 PSI, 35 Bar or 3500 kPa. All models can handle overload pressure 2X the maximum full-scale range and burst pressure is 5X the maximum full-scale range.
  • Page 2: Mounting Instructions

    Mounting Instructions The transmitter mounts on a vertical surface using the two integrated mounting holes. The remote sensor cable connection should be located on the bottom of the enclosure. The two mounting holes will facilitate a #10 size screw (not supplied). See Figure 2. Figure 2: Mounting Ensure there is enough space around the unit to make the electrical connections and that it is within an acceptable distance for the length of remote sensor cable.
  • Page 3 Figure 5: Connecting Two security screws are provided which can be installed to help secure the cover once settings and wiring connections are complete. See Figure 6. Figure 6: Closing 3/10...
  • Page 4 Plumbing The S/S pressure sensor incorporates 1/4” NPT male threads for connection to the pipe being monitored. See Figure 7. Figure 7: Connecting the pressure sensors Do not allow material to fall into the pressure ports as contamination could damage the sensors. It is recommended to use Teflon tape to prevent leaks.
  • Page 5: Output Selection

    Configuration Most configuration is done using User Menu setting with LCD and push buttons on the PCB. See User Menu section for details. The transmitter must not have power applied during set up or when making changes to the output signal. Output Selection The transmitter comes with user-selectable outputs of 4-20 mA, 0-5 Vdc and 0-10 Vdc.
  • Page 6 Wiring • Deactivate the 24 Vac/dc power supply until all connections are made to the device to prevent electrical shock or equipment damage. • Use 14-22 AWG shielded wiring for all connections and do not locate the device wires in the same conduit with wiring used to supply inductive loads such as motors.
  • Page 7 Start Up Upon applying power to the device, it will enter the start-up mode. The LCD will display the current operating settings for 2 seconds each. Software Version 1.00 Model Pressure Range P Range 50PSI The Output Type Output 4-20mA At the end of start-up mode the device will enter normal mode displaying pressure read from sensors.
  • Page 8: Operation

    Figure 13: Pressure Range Operation During normal mode the device reads the pressure sensor and calculates the pressure value depending on the device model range and the selected pressure range. The pressure value is then displayed on the LCD and set as the output value for the analog output. The output value is updated once per second.
  • Page 9: Specifications

    Specifications 24 Vac/dc ± 10% (non-isolated half-wave rectified) Power Supply Consumption 75 mA max @ 24 Vdc 4-20 mA sourcing, 0-5/0-10 Vdc (switch-selectable) Output Signal 500 ohms max for current output Output Drive 10K ohms min for voltage output Reverse-voltage-protected, transient protected Protection Circuitry 35 x 15 mm (1.4 x 0.6"), 2-line x 8-character ±...
  • Page 10 ©, Distech Controls Inc. 2021 All rights reserved. While all efforts have been made to verify the accuracy of information in this manual, Distech Controls is not responsible for damages or claims arising from the use of this manual. Persons using this manual are assumed to be trained HVAC specialist / installers and are responsible for using the correct wiring procedures and maintaining safe working conditions with fail-safe environments.