Advertisement
Gas categories | ||||
Country | Gas | Minimum pressure [mbar] | Nominal pressure [mbar] | Maximum pressure [mbar] |
FR, ES, PT, IT, SK, CZ, GB, AT | G20 | 17 | 20 | 25 |
FR, HU | G25 | 17 | 25 | 30 |
IT | G230 | 17 | 20 | 25 |
FR, ES, PT, IT, SK, CZ, GB, HU | G31 | 25 | 37 | 45 |
AT | G31 | 42,5 | 50 | 57,5 |
Configuration procedure before first commissioning
The first time you commission the boiler, you must carry out the following procedure (the text is in ENGLISH until the language selection request) as indicated in the sequence A-B-C in the figure below:
Display key | |
a | Date: day, month, year |
b | Day of the week |
c | Boiler pressure / Heating circuit |
d | Clock: hour and minute |
The list of configuration menus is as follows:
The procedure below must be followed to acces the list of configuration menus (refer to the "Symbol description" section:
C then
B to choose the menu you want;
B to confirm or
C to exit without saving.
If an anomaly occurs, the first item of data displayed is its code.
To display the boiler's information, select the «Info» menu key to confirm.
Boiler temperature | °C | Boiler flow-back temperature |
Outdoor temperature | °C | Outdoor temperature |
Min. outdoor temperature | °C | Minimum outdoor temperature value stored (with Outdoor Probe connected) |
Max. outdoor temperature | °C | Maximum outdoor temperature value stored (with Outdoor Probe connected) |
DHW temperature | °C | DHW temp (value read by the boiler's domestic circuit sensor) |
Collector temperature | °C | Instant collector probe temp. (with solar installation coupling) |
Heating circuit state (1,2,3) | On/Off" | Heating circuit operating mode (circuits: 1,2,3) |
DHW circuit state | Load | Domestic circuit operating mode |
Boiler state | On/Off" | Boiler operating mode |
Solar installation state | - | Indicates the solar operation (with solar installation integration) |
Customer service telephone | No. | xxxxxxxxxx |
To set the date and time, proceed as follows:
To select the language, proceed as follows:
The temperature is set by turning the B button to the right to increase the value and to the left
to reduce it and
to confirm.
The temperature to be set, for the heating circuit, may be:
Press the key and turn
to scroll through the following functions:
| then ![]() |
| then ![]() |
| then ![]() ![]() ![]() |
The boiler has 4 heating operatingfmodes: Comfort - Reduced - Automatic - Protection.
To program one of the operating modes, proceed as follows:
From the main menu regime
to confirm.
CASE 1: the control unit is installed in the boiler
Turn the button to set the boiler's start temperature.
OPERATING MODE DESCRIPTION
CASE 2: the control unit is attached to the wall
OPERATING MODE DESCRIPTION
While the boiler is operating in Automatic mode, turn button B to set the temperature temporarily. This modification remains valid until the next hourly range is changed.
The boiler's anti-freeze is always activated; the boiler starts up when the heating start temperature is under 5°C. This function is operational if the appliance is powered electrically and if there is gas.
Ambient temperature setting in reduced mode
To program the ambient temperature in Reduced mode, proceed as follows:
The comfort ambient temperature may be set not only using the A key in "Control Panel" section, but also by modifying the 710 parameter as indicated above.
This function enables users to choose the ambient temperature value to be programmed when they are going away for several days (for example during holidays). The minimum anti-freeze temperature or the Reduced mode temperature (program line 648) may be programmed. In program line 641 (Preselection), 8 programming levels named Period 1 (next 8 days to be programmed in on and off) are available. When the function is activated, the display shows the symbol
The following procedure activates the function and programs the hourly ranges:
WE RECOMMEND THAT YOU WRITE DOWN ALL THE PARAMETERS YOU CHANGE AT THE BACK OF THIS MANUAL.
Menu key | ||
1 | End user | 3 Specialist |
2 | Commissioning | 4 OEM |
The procedure for accessing the four menus to program the boiler is as follows:
Before accessing the programming, you must activate the Automatic operating mode (see "Accessing the Parameter Configuration Menus").
The hourly heating (CC1 hourly programming) and DHW (Hourly program 4 / DHW) programming is used to program the boiler's automatic operation during determined daily hourly ranges and during the days of the week. The example in the figure below refers to the daily hourly range 1 (below) where « a » is the operating period at comfort temperature and « b » is the operating period in Reduced mode. The boiler operating programming may be performed by groups of days or by individual days (every day from Monday to Sunday).
Preset weekly intervals
(Program line 500 for the heating and 560 for the DHW)
Preset daily hourly ranges
(Program line 514 for the heating and 574 for the DHW)
This function is used to program one of the 3 weekly intervals availabe, each with three preset daily hourly ranges to switch the boiler on and off, which may be modified by the user - program program 501...506. The intervals are the following: Mon-Sun (default value) / Mon-Fri / Sat-Sun.
If the installation is divided into zones, with each one controlled by its control unit/room thermostat, each zone must be programmed separately on each device.
All of the daily boiler switch on/off phases may be modified by the user. For each day selected, 3 preset hourly ranges are available, as stated in the summary table at the end of this chapter.
(Heating/DHW)
After performing the hourly programming using the preset programs, you can modify the periods of the three hourly ranges - program lines 501...506 for the heating and 561...566 for the DHW, as described below.
Heating circuit programming modification procedure
DHW circuit programming modification procedure
The procedure to activate the hourly programming for the domestic hot water is the same as for the hourly programming for the heating. The only difference is with the name of the menu Hourly program 4 / DHW and the program lines to be programmed 560 (Day selection). To deactivate this function, you must run the procedure described below in the «Restoring the original default programming» section.
Summary table | ||||
Groups of days | Program line 514 (heating) - 574 (DHW) | |||
Preset programs | Preset programs | |||
On 1 - Off 1 | On 2 - Off 2 | On 3 - Off 3 | ||
Mon-Sun | 06:00 - 08:00 | 11:00 - 13:00 | 17:00 - 23:00 | |
Mon-Fri | 06:00 - 08:00 | 17:00 - 23:00 | ||
Sat-Sun | 06:00 - 23:00 | |||
Individual days | Prog. lines 501 502 503 504 505 506 (heating) - 561 562 563 564 565 566 (DHW) | |||
Day interval | Preset programs | |||
On 1 - Off 1 | On 2 - Off 2 | On 3 - Off 3 | ||
Monday-Tuesday- Wednesday Thursday-Friday | 06:00 - 08:00 | 11:00 - 13:00 | 17:00 - 23:00 |
To facilitate programming, the existing programs may be copied to the other days of the week. The procedure is as follows:
Copying a program to another day
After programming the hourly range for a set day, it may be copied to one or more days of the week.
The parameter in brackets « ( ) » refers to the hourly programing in DHW
Restoring the original programming (default)
The weekly programming may be deleted and the comfort heating activated (the value which will be programmed is 00-24, identical for all the days of the week).
When the main menu is displayed once the procedure is complete, you will note that the daily programming bar changes. The heating is still active for 24 hours. To reprogram the boiler, you must repeat the procedure described in "Operating modes" section
In order to prevent unauthorised people from programming, it is possible to lock all the functions associated with the C key.
This unlocking phase is temporary, it lasts 1 minute, then the unlocking is reactivated automatically. To deactivate the function permanently, you must activate the temporary unlocking procedure then Off in the program line 27 (Programming locking) and
to confirm the unlocking.
To shut down the boiler, you must cut the electricity supply to the appliance by pressing the two-pole switch. When the «Protection mode» operation is activated, the boiler remains off but the electrical circuits are still powered up and the anti-freeze function is activated
The errors on the display are identified by the symbol, the information displayed is:
If an error occurs, to display the main menu, The symbol
remains on the display to indicate that the appliance has an error; after one minute, the display shows the error page again, as indicated in the figure.
Error reset
The errors may be reset AUTOMATICALLY, MANUALLY or require the APPROVED TECHNICAL ASSISTANCE SERVICE. Below are the different commands in detail:
AUTOMATIC
If the flashing symbol appears on teh display, the error is reset automatically (temporary error) as soon as the element which caused it stops.
Often, errors of this type are generated by water outlet/return temperatures that are too high in the boiler, then they are reset automatically as soon as the temperature falls below the critical value. If the same error is repeated frequently and/or it is not automatically restet by the boiler, contact the approved Technical Assistance Service.
MANUAL
To reset the error manually when the corresponding code appears « Yes »
to confirm. The error code disappears after a few seconds.
REQUEST FOR INTERVENTION FROM THE APPROVED TECHNICAL ASSISTANCE SERVICE
If the display shows the symbol and the
symbol, you must contact the APPROVED TECHNICAL ASSISTANCE SERVICE. Before calling, we recommend that you note down the code(s), error(s) and a brief description.
If the error code displayed is not on the list or when an error occurs with a certain frequency, we recommend that you contact the APPROVED TECHNICAL ASSISTANCE SERVICE.
Error table | |||
(A) | (C) | (A) | (C) |
![]() | Error description | ![]() | Error description |
10 | Outdoor probe sensor | 125 | Safety disconnection due to lack of circulation (check made by a temperature sensor) |
20 | NTC flow-back sensor | 128 | Flame extinguishing |
28 | Flue gas NTC sensor | 130 | Disconnection by flue gas NTC probe for overheating |
40 | NTC return sensor | 133 | Ignition fault (4 attempts) |
50 | DHW sensor (only for heating only model with hot water tank) | 151 | Internal heating board error |
52 | Solar DHW sensor (for integration of a solar installation) | 152 | General configuration error |
73 | Solar collector sensor (for integration of a solar installation) | 160 | Fan operating error |
83 | Communication problem between boiler board and control unit. Probable short-circuit on the heating | 171 | ACI board fault |
84 | Address conflict between several control units (internal anomaly) | 321 | DHW NTC sensor damaged |
109 | Presence of air in the boiler circuit (temporary anomaly) | 343 | General solar installation configuration error (for integration of a solar installation) |
110 | Disconnection of the safety thermostat due to overheating (pump blocked or air in the heating circuit) | 384 | Incorrect light (interfering flame - internal anomaly) |
111 | Disconnection of the safety thermostat due to overheating | 385 | Supply voltage too low |
117 | Hydraulic circuit pressure too high | 386 | Fan speed threshold not reached |
118 | Hydraulic circuit pressure too low | 430 | Safety disconnection due to lack of circulation (check made by a pressure sensor) |
The functions available are:
The procedure to follow to activate these functions is
Example: turn button B to activate the CALIBRATION function (program line 304), press button B, the function is now operational and preset to 100 % (the boiler reaches the maximum thermal power). Press the button and turn it to set the desired power level as a percentage (0% corresponds to the reduced thermal power)
To interrupt the function manually, repeat the procedure described above, when the function deactivated the display shows «Off».
Drain function
This function is used to facilitate the elimination of air inside the heating circuit when the boiler is installed or after primary circuit water drainage maintenance operations. The electronic board will activate an on/off cycle for the pump lasting 10 minutes. The function will stop automatically at the end of the cycle.
To interrupt the function manually, repeat the procedure described above, when the function is deactivated the display shows «Off».
This unit is designed in accordance with European standards and directives and in particular with the following elements:
The annual servicing must be carried out in accordance with the decree of 15th September 2009 relative to the annual servicing of boilers whose nominal power is between 4 and 400 kW. The professional must deliver a certificate to the end user.
ErP technical parameters
BAXI - Power | 1.32 | 32 Combi 160 | 32 Solar 220 | ||
Condensing boiler | Yes | Yes | Yes | ||
Low-temperature boiler(1) | No | No | No | ||
B1 boiler | No | No | No | ||
Cogeneration space heater | No | No | No | ||
Combination heater | No | Yes | Yes | ||
Rated heat output | Prated | kW | 32 | 32 | 32 |
Useful heat output at rated heat output and high temperature regime(2) | P4 | kW | 32 | 32 | 32 |
Useful heat output at 30% of rated heat output and low temperature regime(1) | P1 | kW | 5,5 | 5,5 | 5,5 |
Seasonal space heating energy efficiency | ηs | % | 92 | 92 | 92 |
Useful efficiency at rated heat output and high temperature regime(2) | η4 | % | 87,9 | 87,9 | 87,9 |
Useful efficiency at 30% of rated heat output and low temperature regime(1) | η1 | % | 97,3 | 97,3 | 97,3 |
Auxiliary electricity consumption | |||||
Full load | elmax | kW | 0,075 | 0,075 | 0,075 |
Part load | elmin | kW | 0,015 | 0,015 | 0,015 |
Standby mode | PSB | kW | 0,004 | 0,004 | 0,004 |
Other items | |||||
Standby heat loss | Pstby | kW | 0,081 | 0,081 | 0,081 |
Ignition burner power consumption | Pign | kW | - | - | - |
Annual energy consumption | QHE | GJ | 100 | 100 | 100 |
Sound power level, indoors | LWA | dB | 56 | 56 | 56 |
Emissions of nitrogen oxides | NOx | mg/kWh | 28 | 28 | 28 |
Domestic hot water parameters | |||||
Declared load profile | XL | XL | |||
Daily electricity consumption | Qelec | kWh | 0,287 | 0,317 | |
Annual electricity consumption | AEC | kWh | 63 | 70 | |
Water heating energy efficiency | ηwh | % | 82 | 83 | |
Daily fuel consumption | Qfuel | kWh | 23,681 | 23,105 | |
Annual fuel consumption | AFC | GJ | 18 | 18 | |
(1) Low temperature means for condensing boilers 30°C, for low temperature boilers 37°C and for other heaters 50°C return temperature (at heater inlet). (2) High temperature regime means 60°C return temperature at heater inlet and 80°C feed temperature at heater outlet. |
BAXI - Power | 1.32 | 32 Combi 160 | 32 Solar 220 | |
Space heating - Temperature application | Medium | Medium | Medium | |
Water heating - Declared load profile | XL | XL | ||
Seasonal space heating energy efficiency class | ![]() | ![]() | ![]() | |
Water heating energy efficiency class | ![]() | ![]() | ||
Rated heat output (Prated or Psup) | kW | 32 | 32 | 32 |
Space heating - Annual energy consumption | GJ | 100 | 100 | 100 |
Space heating - Annual energy consumption | kWh(1) GJ(2) | 63 18 | 70 18 | |
Seasonal space heating energy efficiency | % | 92 | 92 | 92 |
Water heating energy efficiency | % | 82 | 83 | |
Sound power level LWA Indoors | dB | 56 | 56 | 56 |
(1) Electricity (2) Fuel |
The energy ef ciency of the package of products provided for in this che may not correspond to its actual energy ef ciency once installed in a building, as this efficiency is influenced by further factors such as heat loss in the distribution system and the dimensioning of the products in relation to building size and characteristics.
Psup / (Prated + Psup)(1)(2) | II, package without hot water storage tank | II, package with hot water storage tank |
0 | 0 | 0 |
0,1 | 0,30 | 0,37 |
0,2 | 0,55 | 0,70 |
0,3 | 0,75 | 0,85 |
0,4 | 0,85 | 0,94 |
0,5 | 0,95 | 0,98 |
0,6 | 0,98 | 1,00 |
> 0,7 | 1,00 | 1,00 |
(1) The intermediate values are calculated by linear interpolation betw een the two adjacent values. (2) Prated is related to the preferential space heater or combination heater. |
If any smoke is given off:
Do not touch the flue gas ducts. Depending on the unit's settings, the flue gas duct temperature may exceed 60°C.
Do not touch the radiators for any lengthy periods of time. Depending on the unit's settings, the radiator temperature may reach 85°C.
Be careful with domestic hot water. Depending on the unit's settings, the domestic hot water temperature may reach 65°C.
Do not leave the unit without servicing. Contact a qualified professional or subscribe to a maintenance contract for the unit's annual servicing.
This unit is not intended to be used by people (including children) whose physical, sensory or mental capacities are reduced or by people who do not have any experience or knowledge of the unit, unless they are monitored or have been provided with prior instructions on the use of the unit by someone who is responsible for their safety. Children should be supervised to ensure they do not play with the unit.
Only qualified professionals are authorised to work on the unit and the installation.
Comment
Check regularly that the installation is full of water and under pressure (minimum pressure 0.5 bars, recommended pressure between 1.5 and 2.0 bars).
Comment
Ensure that the unit is accessible at all times.
Comment
Never remove or cover the information labels and plates on the unit. The information plates and labels must be legible for the unit's full lifetime.
Do not store explosive or easily-flammable materials in the boiler room or near the boiler, even temporarily.
Use Antifreeze mode rather than power down the unit to carry out the following functions:
This unit has been designed according to European standards and directives and in particular is equipped with the following elements:
It is forbidden to deactivate this safety device.
36061 Bassano del Grappa (VI) - ITALIA
Via Trozzetti, 20
Customer service: tel. +39 0424-517800 – Telefax +39 0424-38089
www.baxi.it
Here you can download full pdf version of manual, it may contain additional safety instructions, warranty information, FCC rules, etc.
Advertisement
Need help?
Do you have a question about the Power and is the answer not in the manual?
Questions and answers