AFRISO PrimoBox AZB 400 Series Operation And Installation Manual

Mixing units in cabinets

Advertisement

Quick Links

Operation and installation manual
PrimoBox AZB mixing units
400 and 500 series in cabinets
Read the manual before using the device
Pay attention to all information regarding safety
Keep the Operation and installation manual
954.001.002
AFRISO sp. z o.o.
Szałsza, ul. Kościelna 7
42-677 Czekanów
POLAND
Phone
+48 32 330 33 55
Fax
+48 32 330 33 51
zok@afriso.pl
www.afriso.pl

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the PrimoBox AZB 400 Series and is the answer not in the manual?

Questions and answers

Summary of Contents for AFRISO PrimoBox AZB 400 Series

  • Page 1 AFRISO sp. z o.o. Szałsza, ul. Kościelna 7 42-677 Czekanów POLAND Phone +48 32 330 33 55 +48 32 330 33 51 zok@afriso.pl www.afriso.pl Operation and installation manual PrimoBox AZB mixing units 400 and 500 series in cabinets  Read the manual before using the device ...
  • Page 2: Table Of Contents

    Table of Contents Explanations to the installation and operation manual ..........3 Safety messages and hazard categories ............. 3 Information on safety ....................3 Intended use....................3 Quality control ....................4 Qualification of personnel ................4 Modifications to the product ................. 4 Using additional parts and accessories ............
  • Page 3: Explanations To The Installation And Operation Manual

    Instruction manual 1 Explanations to the installation and operation manual Installation and operating instructions are an important part of the de- livery. That is why we recommend:  Read the installation and operating instruction before installing the device.  Keep the installation and operating instruction for the entire life of the device.
  • Page 4: Quality Control

    Instruction manual 2.2 Quality control Construction of mixing units PrimoBox AZB complies with the current state technical standards regarding safety. Each device is checked for safety before shipment.  The product should only be used if it is in a qualified technical condition.
  • Page 5: Product Description

    AFRISO sp. z o.o. makes every effort to ensure that the information materials do not contain errors. If errors or inaccuracies are found in the following installation and operation instructions, please contact: zok@afriso.pl, tel.
  • Page 6: Construction

    Instruction manual 3.1 Construction 1- shut-off valve with thermometer 2- Grundfos UPM3 AUTO 15-70 130 mm pump 3- zone 1 return pipe 4- zone 2 return pipe 5- rotary valve with ARM ProClick actuator 6- primary circuit return shut-off valve 7- primary circuit supply shut-off valve 8- automatic air vent 9- cabinet...
  • Page 7: Dimensions

    Instruction manual 3.2 Dimensions Fig. 2: Dimensions of the AZB mixing unit 3.3 Operation The AZB mixing unit is designed to divide the heating medium flow from the boiler circuit into two or three heating system circuits. The mixing unit allows the use of a much smaller number of fittings and pipes necessary to perform individual installation circuits, organizes and simplifies the entire installation.
  • Page 8 Instruction manual Shut-off valves with thermometers AZB mixing units are supplied with built-in shut-off valves to facilitate product maintenance. Check valves have been built into the shut-off valves. Space for temperature sensors has also been prepared. The valve knobs contain thermometers to control the temperature of the heating medium.
  • Page 9: Hydraulic Diagram Sample

    Instruction manual 3.4 Hydraulic diagram sample Fig. 4: PrimoBox AZB 555 hydraulic diagram PrimoBox AZB mixing units 400 and 500 series in a cabinets...
  • Page 10: Sample Application Diagrams

    Instruction manual 3.5 Sample application diagrams 1. AZB mixing unit 2. Installation controller 3. Underfloor heating circuit 4. Radiator circuit Fig. 5: Sample application diagram - 2 zones of underfloor heating system and a radiator system circuit 1. AZB mixing unit 2.
  • Page 11: Specification

    Instruction manual 4 Specification Table 1: Technical data of AZB 400 & 500 units Parameter / part Value / Description General specification Dimensions (W x H x D) 450 x 500 x 160mm 13 ÷ 22 kg Weight Circulation pumps Grundfos UPM 3 AUTO 15-70 130 mm Rotary mixing valve Kvs 3,6 with 3-point ARM ProClick...
  • Page 12: Flow And Available Pressure Diagrams

    Instruction manual 4.2 Flow and available pressure diagrams Fig. 7: Graph of flow rate and disposal pressure through a direct circuit Fig 8: Graph of flow rate and disposal pressure through a circuit with mixing valve PrimoBox AZB missing units 400 and 500 series in a cabinets...
  • Page 13: Transport And Storage

    Instruction manual 5 Transport and storage Possibility of damage to the device during improper transport. ATTENTION  Do not throw the device.  Protect against water, moisture, dirt and dust. Possibility of damage during incorrect storage. ATTENTION  Store the device in a dry and clean room. ...
  • Page 14: Flush Mounting

    Instruction manual Possible need for other dowels  ATTENTION It is necessary to verify that the dowels provided are suitable for the selected wall.  If the dowels provided are not suitable for the selected wall, replace them with others. ...
  • Page 15: Hydraulic Connections

    Instruction manual 6.3 Hydraulic connections Before connecting the AZB mixing unit, flush the system thoroughly, paying special attention to removing residue from soldering, cutting pipes, etc. Make sure that the installation contains safety components necessary for proper and safe functioning. We recommend installing strainers before inlet connections.
  • Page 16: Electrical Connections

    Instruction manual 6.4 Electrical connections  Make sure that the power supply has been disconnected and protected against accidental switching on. Safety regulations and other relevant accident prevention regulations must be observed. You should also comply with all applicable national laws.
  • Page 17 Instruction manual Depending on the version, it is necessary to make additional connections between pumps and electric actuators with the controller or controllers. In this case, make an electrical connection of the controller with the AZB mixing unit according to the diagram (Fig. 12). housing Fig.
  • Page 18: Assembly And Disassembly Of Arm Proclick Actuators

    Instruction manual 7 Assembly and disassembly of ARM ProClick actuators The PrimoBox AZB unit is equipped with ARM ProClick electric actu- ators. They can be easily disassembled and reassembled. The ARM ProClick actuators are removed from the valve by pressing the button on the side of the actuator housing and pulling the actuator towards you.
  • Page 19: Switching The Actuator To Manual Operation

    10 Warranty The manufacturer’s warranty for this product is 36 months after the date of purchase from AFRISO sp. z o.o.. In case of any alteration in the prod- uct or usage against this instruction manual, the warranty becomes void.