Summary of Contents for Panasonic Eco-POWER METER KW1M
Page 2
【KW1M】 Basic setting to measure by Eco-POWER METER When wiring the main unit and the current transformer (CT) and setting the basic setting after power on, you can measure the power The basic setting of MODE1 is necessary to measure. In order to use the other functions, the settings of the each parameter are necessary.
Copyright and trademark ● Panasonic Industry Co., Ltd. owns the copyright of this manual. ● We stiffly refuse the reproduction of without permission from this manual. ●Modbus Protocol is a communication protocol that the Modicon Inc. developed for PLC.
Page 4
Introduction Thank you very much indeed for purchasing “KW1M Eco-POWER METER”. In this manual, we explain the usage of “KW1M-H Eco-POWER METER” in detail. Please use it correctly after understanding the content enough.
Table of Contents Chapter 1 Unit’s Features and Structure ....................1 1.1 Unit’s Name and Model Numbers ......................1 1.1.1 Main unit ............................1 1.1.2 Option ............................. 1 1.2 Measurement items: AKW1111/AKW1111B (400VAC applicable type) ..........2 1.3 Measurement items: AKW1110/AKW1110B ................... 2 Chapter 2 Parts Name and Working ......................
Page 6
Chapter 7 Communication........................35 7.1 Communication Procedures ........................35 7.2 Communication timing ........................... 35 7.3 MEWTOCOL Communication ........................ 36 7.3.1 Overview of MEWTOCOL-COM (RS485) ..................36 7.3.2 Data Register List <AKW1111/AKW1111B (400AC applicable type)> ........37 7.3.3 Data Register List <AKW1110/AKW1110B> ................38 7.3.4 Error Codes ..........................
Cautions before using ■ Installation environment ◇Do not use the Unit in the following environments. ・Where the unit will be exposed to direct sunlight and where the ambient temperature is outside the range of -10 to 50 °C. ・Where the ambient humidity is outside the range of 30 to 85 % RH (at 20℃, non-condensing) and where condensation might occur by sudden temperature changes ・Where inflammable or corrosive gas might be produced ・Where the unit will be exposed to excessive airborne dust or metal particles...
Page 8
■ Power supply ・Connect a breaker to the voltage input part for safety reasons and to protect the device. The breaker that connects to the voltage input part must arrange at the position easily reached, and display shows it is the breaker of the equipment. ・Do not turn on the power supply or input until all wiring is completed.
KW1M Eco-POWER METER Chapter 1 Unit’s Features and Structure KW1M Eco-POWER METER is the suitable size wattmeter for installing in a control board. It measures electrical power, voltage, current and so on using AC voltage and AC current input. It also works ad an hour meter, which is measured power-on or power-off time. 1.1 Unit’s Name and Model Numbers 1.1.1 Main unit Measured voltage...
KW1M Eco-POWER METER Others Product name Model No Mounting rail AT8-DLA1 Fastening plate ATA4806 Mounting frame AKW1822 1.2 Measurement items: AKW1111/AKW1111B (400VAC applicable type) Item Unit Data range kWh/ 0.00 to 9999.99MWh Integral electric power (Active) (9-digit display) 0.00 to 9999999.99kWh Instantaneous electric power (Active) 0.00 to 9999.99 R-current...
KW1M Eco-POWER METER Chapter 2 Parts Name and Working 2.1 Parts Names ①MODE indicator Lighting when mode setting ②LOCK indicator Lighting while in lock mode ③OP. output indicator Lighting when pulse output ④Mode display Display mode in setting and measurement item with 16-seg ⑤Display each value With 7-seg ・Display each measured value...
KW1M Eco-POWER METER Chapter 3 Wiring 3.1 AKW1111/AKW1111B (400V AC applicable type) Be sure to wire correctly according to the terminal arrangement and wiring diagrams. After completing wiring, be sure to attach the terminal cover for safety reasons. 3.1.1 Terminal arrangement M3 screw Function Screw...
Page 13
KW1M Eco-POWER METER Single-phase three-wire / Three-phase three-wire system *Two current transformers are required. Do not wire ⑥ terminals. They are connected internal. Three-phase four-wire system *Three current transformers are required. ◆When measuring a load with exceed input voltage Voltage transformer (VT) is needed when you measure a load with over rated input voltage (440V). Use VT, those secondary rating is 110V.
KW1M Eco-POWER METER 3.2 AKW1110/AKW1110B Be sure to wire correctly according to the terminal arrangement and wiring diagrams. After completing wiring, be sure to attach the terminal cover for safety reasons. 3.2.1 Terminal arrangement Function Screw ① Power supply ② ③...
KW1M Eco-POWER METER 3.2.2 Wiring Diagrams Please connect a breaker (3 to 15A) to the voltage input part for safety reasons and to protect the device. Grounding the secondary side of VT (Voltage transformer) and CT (Current transformer) is not necessary with low-voltage circuit.
KW1M Eco-POWER METER 3.3 Caution for Wiring 1) Terminal fastening torque should be 0.5 to 0.6N・m for M3 screw and should be 1.0N・m for M3.5 screw. In case of using a crimping terminal, use it with insulating sleeve applicable to M3 screw or M3.5 screw.
KW1M Eco-POWER METER 3.4 How to attach the Current Transformer (CT) ・One current transformer (CT) is needed to measure 1P2W system. Two CTs are needed to measure a 1P3W/3P3W system. Three CTs are needed to measure a 3P4W system. Using all CT should be the same.
KW1M Eco-POWER METER Without Ammeter Power supply Breaker Shorted or resistor less than 0.1Ω Secondary current CT with 2nd current 5A Eco-POWER METER Dedicated CT for 5A Load 3.5 For input connection ・Contact input Use highly reliable metal plated contacts. Since the contact’s bounce time leads directly to error in the count value, use contacts with as short a bounce time as possible.
KW1M Eco-POWER METER (Fig.B) No Good example Operating power supply Operating power supply Measured voltage input Measured voltage input Insulated Input equipment Input equipment Auto transformer transformer (sensor etc.) (sensor etc.) (+) (+) (-) (-) Eco-POWER Eco-POWER METER METER Do not use an auto-transformer. Do not ground the secondary side.
KW1M Eco-POWER METER Recommended Cable Use the transmission cables shown below for Eco-POWER METER RS485 communication system. Conductor Insulator Cable Resistance Cable Applicable cable Size Material Thickness diameter (at 20℃) HITACHI 1.25 mm KPEV-S Max. Approx. (AWG16) Max.16.8Ω/km Polyethylene ×1P 0.5 mm 8.5 mm 1.25 mm...
KW1M Eco-POWER METER Chapter 4 Setting 4.1 Operation procedure AKW1111/AKW1111B (400VAC applicable type) 【Basic setting to measure】 When wiring Eco-POWER METER and CT and setting mode 1 after power on, Eco-POWER Meter can measure the electric power. In order to use the other functions, set mode2, 3 and 4 according to your use.
Page 22
KW1M Eco-POWER METER Mode 2…Mode for setting of each parameter for pulse measurement Mode 3…Mode for setting of each parameter for serial communication Mode 4…Mode for setting of each parameter for optional function Monitor (Display when power on) <MODE> Setting mode (Mode 1) (Mode 2) (Mode 3)
KW1M Eco-POWER METER 4.2 Operation procedure AKW1110/AKW1110B 【Basic setting to measure】 When wiring Eco-POWER METER and CT and setting mode 1 after power on, Eco-POWER Meter can measure the electric power. In order to use the other functions, set mode2, 3 and 4 according to your use.
Page 24
KW1M Eco-POWER METER Mode 3…Mode for setting of each parameter for serial communication Mode 4…Mode for setting of each parameter for optional function Monitor (Display when power on) <MODE> Setting mode (Mode 1) (Mode 3) (Mode 4) <SET> <SET> <SET> Refer to the previous Protocol setting mode Auto-off setting mode...
KW1M Eco-POWER METER 4.3 Setting Mode Explanation ■The value with under line is initial setting among each setting value. ☆Set before measurement. Press <MODE> and <SET> at a time, the setting will be initialized. 4.3.1 MODE1(Mode for setting each parameter for power measurement.) Phase/Wire system setting mode SYST Mode defines phase and wire system to measure.
Page 26
KW1M Eco-POWER METER Unit for pulse output setting mode PL-P Mode defines unit used for pulse output. It defines the unit of integral electric power for 1-pulse output. ・Select from 0.001/0.01/0.1/1/10/100kWh /AL-P/AL-C/AL-S/Cnt. *“AL-S” and “Cnt” are only for AKW1111/AKW1111B. When one of the “0.001/0.01/0.1/1/10/100” [kWh] is set, one pulse is output at reaching the setting value.
Page 28
KW1M Eco-POWER METER Current for time measurement setting mode Set ratio of current for time measurement using <ITEM/△><SHIFT/▽>. If you measure the current over 50.0%F.S., set to “50.0”. (1.0 to 100.0) ↓<SET> Cutoff current setting mode Set cutoff current ratio using <ITEM/△> <SHIFT/▽>. If you don’t measure the current under 10.0%F.S, set to “10.0”.
Page 29
KW1M Eco-POWER METER Stand-by alarm setting mode 2 *It is only when “AL-S” is selected on unit for pulse output setting mode. Set a time used for threshold value to judge stand-by power using <ITEM/△><SHIFT/▽>. ( 0 to 9999 min.) *It is only when “AL-S”...
KW1M Eco-POWER METER 4.3.2 MODE2 (Mode for setting of each parameter for pulse measurement) *Only AKW1111/AKW1111B (400VAC applicable type) Max. counting speed setting mode Mode defines max. counting speed. ・Select from 2kHz/30Hz Pre-scale setting mode PSCL Mode defines pre-scale value used for changing count value. ・It can be set the range of 0.001 to 100.000.
KW1M Eco-POWER METER 4.3.3 MODE3 (Mode for setting of each parameter for serial communication) Protocol setting mode PROT Mode defines communication protocol of main unit via serial communication (RS485). ・Select from MEWTOCOL / MODBUS(RTU). Station number setting mode Mode defines an individual station no. for each unit when two or more units communicate via serial communication (RS485).
Page 32
KW1M Eco-POWER METER Transmission speed setting mode Press <ITEM/△><SHIFT/▽> to change 19200 ⇔ 38400 ⇔ 2400 ⇔ 4800 ⇔ 9600. 19200bps 38400bps 2400bps 4800bps 9600bps ↓ <SET> Transmission format setting mode Press <ITEM/△><SHIFT/▽> to change 8bit-o ⇔ 7bit-n ⇔ 7bit-E ⇔ 7it-o ⇔ 8bit-n ⇔ 8bit-E. n: not available E: even number o: odd number...
KW1M Eco-POWER METER 4.3.4 MODE4 (Mode for setting of each parameter for optional function) Auto-off setting mode Display LCD turns off automatically when there is no key operation for a long time. ・Off time can be set the range of 0 to 99min. “0”...
KW1M Eco-POWER METER Chapter 5 Various Functions (Sample image is AKW1111/AKW1111B. AKW1110/AKW1110B displays same.) LOCK indicator 5.1 LOCK mode It is the mode makes all keys unable. Use when you want to fix one of the measurement displays (For all displays). In this mode, you can not input by any keys.
KW1M Eco-POWER METER 5.3 Counter function *only AKW1111/AKW1111B (400VAC applicable type) 5.3.1 Operation mode Maintain output hold count HOLD [Output] [Counting] possible ・・・ [Addition] n: Preset value (1) Output control is maintained after count-up completion and until reset. However counting is possible despite of count-up completion.
KW1M Eco-POWER METER Chapter 6 Display of each Value 6.1 Working of Monitor Display 【Power Monitoring Mode Display】 Integral electric power ↓<ITEM/△> Instantaneous electric power ↓<ITEM/△> Current → → S-current R-current T-current <SHIFT/▽> <SHIFT/▽> Press <SHIFT/▽> to shift R-A → S-A → T-A → R-A→・・・ ↓<ITEM/△>...
KW1M Eco-POWER METER 6.2 Power Monitoring mode (Sample image is AKW1111/AKW1111B. AKW1110/AKW1110B displays same.) Power on the unit and it displays the integral electric power. 6.2.1 Integral electric power ・It displays the integral electric power. Sample ・Integral electric power is measured and displayed from 0.00kWh to 9999.99MWh. ・The decimal point is changed automatically.
KW1M Eco-POWER METER 6.2.2 Instantaneous electric power ・It displays the Instantaneous electric power. Sample Instantaneous electric power (kW) 6.2.3 Current ・It displays the current value of the load. ・Press <SHIFT/▽> to change R-current and S-current (*), T-current. *only AKW1111/AKW1111B (400V AC applicable type) *Before start measuring, select phase and wire system according to the measured load.
KW1M Eco-POWER METER 6.2.4 Voltage ・It displays the voltage value of the load. ・Press <SHIFT/▽> to change voltage between R(RS)-voltage(*) and T(TS)-voltage. *only AKW1111/AKW1111B (400V AC applicable type) *Before start measuring, select phase and wire system according to the measured load. When it sets wrong, it doesn’t measure correctly.
KW1M Eco-POWER METER 6.2.5 Electricity Charge ・It displays the standard electricity charge for the integral electrical power. Sample *When the value exceeds ‘999999’, ‐ ‐ ‐ ‐ ‐ ‐」 「 will be displayed. 6.2.6 Carbon dioxide conversion value ・It displays the standard conversion value for the integral electrical power. Sample conversion value (kg-CO *When the value exceeds ‘999999’,...
KW1M Eco-POWER METER 6.2.8 Frequency *only AKW1111/AKW1111B ・It displays the frequency. Sample Frequency (Hz) 6.2.9 Hour meter ・It displays ON-time and OFF-time of the load. ・Press <SHIFT/▽> to change the load ON-time to load OFF-time. Sample ON-time (h) OFF-time (h) Blinking the decimal point during Blinking the decimal point during measurement of ON-time.
KW1M Eco-POWER METER How to Reset ON/OFF-time ・Hold down <SET>key and press <MODE>key makes ON-time or OFF-time clear. (ON-time and OFF-time are reset by each.) Reset <SET> <MODE> 6.2.10 Counter *only AKW1111/AKW1111B ・It displays present count value (pulse input value). Sample Prescale: 0.01 *After reaching the full scale (999999), the value reverts to 0 but continues to measure.
KW1M Eco-POWER METER Chapter 7 Communication 7.1 Communication Procedures Communication starts with command transmission from the host computer (hereafter Master) and ends with the response of Eco-POWER METER (hereafter Slave). Master Slave Command • Response with data When master sends reading command, slave responds with the Data corresponding set value or current status.
KW1M Eco-POWER METER 7.3 MEWTOCOL Communication 7.3.1 Overview of MEWTOCOL-COM (RS485) ◆Command and response functions The computer sends commands (instructions) to Eco-POWER METER, and receives responses in return. This enables the computer and Eco-POWER METER to converse with each other, so that various kinds of information can be obtained and provided.
KW1M Eco-POWER METER 7.3.2 Data Register List <AKW1111/AKW1111B (400AC applicable type)> Data register Name Unit Kind of data Range DT00054 Rate (CHG) 0.01 0 to 9999 Unsigned 16bit Conversion factor 0.001 DT00055 0 to 9999 Unsigned 16bit (CO2) kg-CO Rated A DT00060 CT type 5,50,100,250,400,600...
KW1M Eco-POWER METER 7.3.3 Data Register List <AKW1110/AKW1110B> Data register Name Unit Kind of data Range DT00054 Rate (CHG) 0.01 0 to 9999 Unsigned 16bit Conversion factor 0.001 DT00055 0 to 9999 Unsigned 16bit (CO2) kg-CO Rated A DT00060 CT type 5,50,100,250,400,600 Unsigned 16bit (rms)
KW1M Eco-POWER METER 7.3.4 Error Codes ◇Basic procedure errors Error code Error name Explanation ・A Bcc error occurred in the command data. Bcc error ・A command message was sent that does not fit the transmission Format error format. ・A command was sent that is not supported. No support error ・Delimiter with multiple frames was sent.
Page 48
KW1M Eco-POWER METER ◆[MD]: Register or Reset data monitored (Registers the data to be monitored.) *Up to 16 points can be registered for one unit. ◇Command (Register) Data specification ① Data specification Word No. Word No. Destination % # 5 characters 5 characters ×10 ×10...
KW1M Eco-POWER METER 7.4 MODBUS (RTU) Communication 7.4.1 Overview of MODBUS (RTU) ◆8-bit binary data in command is transmitted as it is. Data format Start bit : 1 bit Data bit : 8 bits *7bits is not available. Parity : No parity, Even parity, Odd parity Selectable Stop bit : 1 bit (Fixed) Error detection...
Page 50
KW1M Eco-POWER METER ◇Data: Data depends on the function code. A request message from the master side is composed of data item, number of data and setting data. A response message from the slave side is composed of number of bytes, data and exception code in negative acknowledgement.
Page 51
KW1M Eco-POWER METER <3> Reset integral electric power (0064H, 0065H: 2-word) of address 1 (When setting to 0 [0000, 0000H]) ・Command Number of Slave Function Data item Number of 3.5 idle data item to ⇒ address code data characters write (01H) (10H) (0064H)
KW1M Eco-POWER METER 7.4.2 Data Register List <AKW1111/AKW1111B (400VAC applicable type)> Data item Range: Hexadecimal MODBUS Name Unit Kind of date (Range: Decimal) Function code (MEWTOCOL) 0036H Rate (CHG) 0H to 270FH (0 to 9999) 0.01 Unsigned 16bit 03H/06H/10H (DT00054) Conversion factor 0037H 0.001...
Page 53
KW1M Eco-POWER METER Data item Range: Hexadecimal MODBUS Name Unit Kind of date (Range: Decimal) Function code (MEWTOCOL) 0096H 0H to F423FH (DT00150) Load ON-time 0.1h Unsigned 16bit 03H/06H/10H 0097H (0 to 999999) (DT00151) 0098H 0H to F423FH (DT00152) Load OFF-time 0.1h Unsigned 16bit 03H/06H/10H...
KW1M Eco-POWER METER 7.4.3 Data Register List <AKW1110/AKW1110B> Data item Range: Hexadecimal MODBUS Name Unit Kind of date (Range: Decimal) Function code (MEWTOCOL) 0036H Rate (CHG) 0H to 270FH (0 to 9999) 0.01 Unsigned 16bit 03H/06H/10H (DT00054) 0037H Conversion factor 0.001 0H to 270FH (0 to 9999) Unsigned 16bit...
KW1M Eco-POWER METER Chapter 8 Specifications 8.1 Main unit Item AKW1111/AKW1111B AKW1110/AKW1110B Rated operating voltage 100-240V AC Rated frequency 50/60Hz common Rated power consumption 8VA (240VAC at 25℃) 6VA (240VAC at 25℃) Inrush current Max. 30A (240VAC at 25℃) Allowable operating 85-264V AC (85% to 110% of rated operating voltage) voltage range Allowable momentary...
KW1M Eco-POWER METER <Using the dedicated CT> ・5A/50A/100A/250A/400A/600A (Select with setting mode) Input Primary side <Using a commercial CT with the secondary side current 5A> current rating ・1 to 4000A (Set with setting mode) *Use a CT with secondary side current of 5A when measure 600A or more. Cut-off 1.0 to 50.0%F.S (Set with setting mode) current...
KW1M Eco-POWER METER 8.3 Output Specifications 8.3.1 Pulse output (Transistor output) AKW1111/AKW1111B AKW1110/AKW1110B Number of output point 1 point Insulation method Optical coupler Output type Open collector Output capacity 100mA 30V DC Pulse width approx. 100ms ON state voltage drop 1.5V or less OFF state leakage current 100μA or less...
KW1M Eco-POWER METER 8.5 Self-diagnostic function If an error occurs, the following indication will be given. Indicator Meaning Output status To recover Err0 CPU error Turn the power off and then on again. Err1 Memory error* EEP-ROM life ended. Replace the unit. *Includes the possibility that the EEP-ROM’s life has expired.
KW1M Eco-POWER METER 8.8 Dedicated Current Transformer Specifications ●Clamp-on type AKW4801B AKW4802B AKW4803B AKW4804B AKW4808B Model No AKW4801C AKW4802C AKW4803C AKW4804C AKW4808C Primary side rated current 5A / 50A 100A 250A 400A 600A Secondary side rated 1.67mA / 33.3mA 125mA 200mA Current 16.7mA...
Page 60
KW1M Eco-POWER METER ●Through type AKW4506B AKW4507B AKW4508B Model No AKW4506C AKW4507C AKW4508C Primary side rated current 50A / 100A 250A / 400A 600A Secondary side rated 16.7mA / 33.3mA 125mA / 200mA 200mA Current Transform ratio 3000:1 2000:1 3000:1 Ratio error ±1.0%F.S.
KW1M Eco-POWER METER Panel cutout 9.2 How to mount to DIN rail (1) Hook “A” of main unit on the upper side of DIN rail. (2) Making “A” part as a support fit the bottom side of main unit to DIN rail. (3) It will be completely fixed to DIN rail with a “click”...
KW1M Eco-POWER METER Chapter 10 Q&A I’d like to measure by Eco-POWER METER. Measured load is 50 to 60A in normal operation. But the inrush current is 130 to 140 A. Which CT is selected? (100A or 250A) Select 100ACT. Stable current more than 1 second is necessary to measure.
KW1M Eco-POWER METER Revision History Issue Date Manual no. Content of revision January, 2010 ARCT1F473E First edition January, 2012 ARCT1F473E-1 edition [Add function] 600ACT input Add through type CT [Improve spec.] Improve the accuracy [Correct error] VT wiring July, 2013 ARCT1F473E-2 edition Company name change...