Page 1
Manual ML 533 Important Note: It is essential for safety that the installer and user of the Expo system follow these instructions. Please refer to the standard for principles and definition. These instructions apply only to the pressurizing system. it is the responsibility of the manufacturer of the pressurized enclosure to provide instructions for the enclosure.
Section 1:System Specification ......................1 ® MiniPurge Control Unit Data .............................2 Relief Valve Unit and Purge Outlet Valve with integral spark arrestor ............3 Section 2:Quick User Guide ........................4 Installation ....................................4 Operation of the System ..............................4 Section 3:Application Suitability ......................5 Section 4:Description and Principle of Operation ................6 Section 5:Main Components ........................8 Air Supply Filter / Regulator ...............................8 Logic Air Supply Regulator ..............................8...
Class I Div 1 Groups B C & D Type X Pressurization -20ºC to +55ºC ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011 T: +1 (440) 247 5314 T: +86 532 8906 9858 E: sales@expoworldwide.com...
Yellow On completion of an uninterrupted purge cycle of the required length, the system will indicate purge complete. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011 T: +1 (440) 247 5314 T: +86 532 8906 9858 E: sales@expoworldwide.com...
® The following materials are used in the construction of MiniPurge systems. If substances that will adversely affect any of these materials are present in the surrounding environment, please consult Expo Technologies for further guidance. Materials of Construction Stainless Steel...
Secondary Pressure Sensor to allow the Control Unit to sense a low pressure fault in the Motor Terminal Box. See Section 6, Multiple Enclosure. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011...
Page 10
Normal Operation Fault Condition - loss of pressure outside of CLAPS regulation ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011 T: +1 (440) 247 5314 T: +86 532 8906 9858 E: sales@expoworldwide.com...
“Purge Complete” signal; it remains in the closed position until the next purge cycle is initiated. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011...
Cable entry methods (for example conduit or cable glands) must be certified to Class I Div 1 standards. The main requirement is that NEMA 4X or better ingress protection must be provided by use of seals or washers. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011...
® The MiniPurge is designed for use under normal industrial conditions of ambient temperature, humidity and vibration. Please consult Expo before installing this equipment in conditions that may cause stresses beyond ® normal industrial conditions.The MiniPurge system must be installed by a competent person in accordance with relevant standards, such as IEC / EN 60079-14, and any local codes of practice.
(dry) contacts within the pressurized enclosure. This is commonly achieved using the Power Interlock Switch. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011...
To adjust the lift off pressure of the Relief Valve: • Attach test equipment as described in the Commissioning Section. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011 T: +1 (440) 247 5314 T: +86 532 8906 9858 E: sales@expoworldwide.com...
General Information If you are having problems that cannot be corrected using one of the methods described, please call Expo or your supplier for further assistance. If the system is less than 12 months old, parts under warranty should be returned to Expo for investigation.
D826 Hook Up, P and I Diagram) CONNECTION DIAGRAM FOR AMU-ABS4-001 SD8355 ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011 T: +1 (440) 247 5314 T: +86 532 8906 9858 E: sales@expoworldwide.com...
Page 23
SA body) Compensation Valve” (LCV) which is adjusted so that the flow is enough to compensate for any leakage from the PE. ¤ ¤ Expo Technologies Limited Page 1 of 7 ML384 Issue 03 – 09.01.13...
No valve may be fitting shall be fitted externally. In addition, for "Y" and fitted in any tube connecting the Expo system to the PE. "Z" Pressurization systems, a suitable indicator shall be provided.
Page 25
Pressure Sensor settings, are used (please ask Expo if in doubt). flow rates and purge time. Note: No valves may be fitted between the Expo system 1.5.2 Other marking, for the PE, required by the and the alarm switch.
Page 26
LCV slowly observing the manometer or gauge (see as follows: item 2.1.3 above). The PE pressure will start to fall as the 2.3.1 Open the supply shutoff valve. ¤ ¤ Expo Technologies Limited Page 4 of 7 ML384 Issue 03 – 09.01.13...
Page 27
PE as 2.3.10 “Y” and “Z” purge systems do not control the shown on the PE or Expo system nameplate. enclosure power. It is the responsibility of the user to Never turn on the power without purging first unless...
Page 28
Is there debris stuck on the face of the Relief Valve dealt with below. If a cure cannot be effected by following disk, perhaps held there because of the magnetic the procedure shown below please call Expo (24 hour material? answering) or your supplier for further assistance.
Page 29
Purge Flow Sensor needs re-calibrating it can either be point to the Purge Flow Sensor is not air-tight e.g. fitting returned to Expo for this service or it can be done by nuts not tightened or tube damaged. Check and repair as the user as follows: necessary.
Breather Drain UL Listing EBNV.E10444* *Certificates are attached to the manual. ML533 | v5 Page Expo Technologies UK Expo Technologies US Expo Technologies China T: +44 (0) 20 8398 8011 T: +1 (440) 247 5314 T: +86 532 8906 9858 E: sales@expoworldwide.com...
Page 31
[ ] DENOTES IMPERIAL IF IN DOUBT ASK to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. FLATNESS TO BE LESS THAN X.XX ±0.1...
Page 32
IF IN DOUBT ASK [ ] DENOTES IMPERIAL to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. FLATNESS TO BE LESS THAN X.XX ±0.1...
Page 33
[ ] DENOTES IMPERIAL IF IN DOUBT ASK to be copied or communicated in part or in whole without written consent from Expo Technologies Limited, neither are they to be used in any way against our interests. FLATNESS TO BE LESS THAN X.XX ±0.1...
Page 39
This Certificate does not replace the original EAC Document In accordance with SERCONS INTERNATIONAL Russian Certification Authority in Europe the company: Expo Technologies Limited, United Kingdom, Unit 2, The Summit Hanworth Road, Sunbury on Thames Sur-rey , TW16 5DB fulfills the necessary requirements to be certified according to EAC regulations.
FM Approvals a = Model size 1, 2, 3, 4, 5 or 6. 1151 Boston Providence Turnpike b = Enclosure type cs, ss, bp, pm or nm. P.O. Box 9102 Norwood, MA 02062 USA c = Option code AA, AC, AO, AS, CT, DS, DT, ET, IS, FM, MO, MT, NO, OA, OB, OC, OS, OV, T: 781 762 4300 F: 781-762-9375 www.fmapprovals.com PC, PN, PO, SS, TW, and/or **.
Page 43
Outlet Orifice. hazardous (classified) locations to be used to reduce the internal area of a connected enclosure to a Class II, Division 2, Group F and G hazardous (classified) location in accordance with Expo 11. aZDPbc. Mini-Z-Purge Type DP Control System.
Page 44
This certifies that the equipment described has been found to comply with the following Approval Standards and other documents: FM Class 3600 2011 FM Class 3610 2010 FM Class 3615 2006 FM Class 3620 2014 ANSI/NFPA 496 2013 Original Project ID: Approval Granted: 1X8A4.AE Subsequent Revision Reports / Date Approval Amended...
Page 45
FM Approvals b = Enclosure type cs, ss, bp, pm or nm. 1151 Boston Providence Turnpike c = Option code AA, AC, AO, AS, CT, DS, DT, ET, IS, FM, MO, MT, NO, OA, OB, OC, OS, OV, P.O. Box 9102 Norwood, MA 02062 USA PC, PN, PO, SS, TW, and/or **.
Page 46
(classified) locations to be used to reduce the internal area of a connected enclosure to arrangements. a Class II, Division 2, Group F and G hazardous (classified) location in accordance with Expo Note: All CFHP Systems must include an RLV Series Relief Valve matched to the specific Technologies Installation, Operation and Maintenance Manual ML386 DP.
Page 47
This certifies that the equipment described has been found to comply with the following Approval Standards and other documents: ANSI/NFPA 496 2013 CSA C22.2 No 25 1966 CSA C22.2 No 30 1986 CSA C22.2 No. 157 1992 Original Project ID: 1X8A4.AE Canadian Project ID: 3052954 Approval Granted:...
Page 48
= sub module conditions of use specified in the schedule to this certificate. 1 = Timer Module powered by Expo Battery Pack 2 = IS Power Supply This certificate relates to the design, examination and testing of the products specified herein. The FM...
Page 49
SCHEDULE Canadian Certificate Of Conformity No: FM16CA0176X 2. The Electronic Timer shall be installed within an enclosure which provides protection against impact. 3. The Enclosure shall be metallic providing a minimum IP20. 4. For light alloy enclosures, materials shall not contain, by mass, more than 7.5% in total of magnesium, titanium and zirconium.
Page 50
= sub module Approvals surveillance audit program has further determined that the manufacturing processes and quality 1 = Timer Module powered by Expo Battery Pack control procedures in place are satisfactory to manufacture the product as examined, tested and Approved.
Page 51
SCHEDULE US Certificate Of Conformity No: FM16US0373X 2. The Electronic Timer shall be installed within an enclosure which provides protection against impact. 3. The Enclosure shall be metallic providing a minimum IP20. 4. For light alloy enclosures, materials shall not contain, by mass, more than 7.5% in total of magnesium, titanium and zirconium.
Page 52
FTQH7.E302348 - Enclosures for Use in Zone Classified FTRV.E302348 - Enclosures for Use in Hazardous Locations Hazardous Locations Certified for Canada Enclosures for Use in Hazardous Locations Enclosures for Use in Zone Classified Hazardous Locations Certified for See General Information for Enclosures for Use in Hazardous Locations Canada FEAM SRL E302348...
MiniPurge Systems are manufactured under Production Quality Assurance Notification 99ATEXM043, issued by CSA Group (Netherlands) B.V. (EU Notified Body No. 2813). Technical documentation and assessments are in the Expo Technologies confidential technical file SC004. For and on behalf of Expo Technologies Ltd...