Halton disclaims any and all liability related to this document. Halton gives no explicit or implied warranties in terms of this document. Any permitted use of the information included herein is at your own risk. Halton may amend or replace the information included in this document at its sole discretion without further notice and liability.
Page 5
Halton Max MUC - Installation, commissioning and maintenance guide 1.4 Saf Safet ety no y not t es es All information in this section is important and relevant for your safety. Please pay special attention to these icons and the accompanying messages when used later in context in this manual.
Page 6
Halton Max MUC - Installation, commissioning and maintenance guide Do not lift objects over 20kg (44lbs) alone. Use a lift or seek assistance. C C A A UTION! UTION! Risk of personal injury or material damage. Not t es es Not t e: e: Notes are statements to which you should pay special attention.
Page 7
Halton Max MUC - Installation, commissioning and maintenance guide 2 2 P P r r oduct descrip oduct description tion 2.1 Ov Over ervie view w Fig. 1. Fig. 1. Halton Max Ultra Circular (MUC) Circular airflow management damper using the ultrasound technique for airflow measurement.
Fig. 2. Fig. 2. Halton Max Ultra Circular (MUC) has two ultrasound sensors for airflow measurement. The damper can function either as a supply or exhaust unit. It maintains the required airflow through ultrasound measurement, regardless of airflow and pressure variations in the ductwork.
Page 9
Halton Max MUC - Installation, commissioning and maintenance guide 2.3 S S tructur tructure and mat e and materials erials Fig. 3. Fig. 3. Halton Max Ultra Circular (MUC) structure No. . P P ar art t Material erial Casing Galvanised steel or stainless steel (EN 1.4404, AISI...
▪ Determining the installation place. ▪ Checking the safety distances. ▪ Connecting the damper to the ductwork. ▪ Connecting the wiring. Fig. 7. Fig. 7. Halton Max Ultra Circular (MUC) installation process 3.1.2 3.1.2 Ins Installation inf tallation information ormation...
Page 13
Halton Max MUC - Installation, commissioning and maintenance guide Wiring Wiring The wiring must only be carried out by qualified personnel following the local regulations. For the power supply, a safety isolating transformer must be used. The bus must be implemented according to standard EIA/TIA-485.
Page 14
Halton Max MUC - Installation, commissioning and maintenance guide ▪ Dim. 100 = ±5% or ±1.00 l/s ▪ Dim. 125 = ±5% or ±1.25 l/s ▪ Dim. 160 = ±5% or ±2.5 l/s ▪ Dim. 200 = ±5% or ±4.0 l/s ▪...
Page 15
Halton Max MUC - Installation, commissioning and maintenance guide S S t t eps 1. Before you start, do the following: a. Check the inside of the damper for damage and loose parts. b. Remove any contamination from the ductwork.
Page 16
Halton Max MUC - Installation, commissioning and maintenance guide 5. Fix the duct to the damper with pop rivets such that it cannot be moved. R R esults esults The damper is installed. Use tape to ensure tightness, if necessary.
Page 17
Halton Max MUC - Installation, commissioning and maintenance guide 2. Connect the input, output, and communication wires. Not t e: e: See Installation inf tallation information ormation Wiring diagr Wiring diagrams 3. Replace the controller cover and fasten the screws.
The airflow range for Halton Max Ultra Circular (MUC) is preset at the factory. The factory settings for the control signal and feedback signal are the same, but they can be configured individually. If the airflow range is not specified by the customer, the default factory settings are the following: ▪...
Page 19
Halton Max Ultra Circular (MUC) airflow controller has a control panel with a display and four pushbuttons. Fig. 14. Fig. 14. Control panel The LCD display can show 16 characters in 2 lines.
Page 20
Butto Fig. 15. Fig. 15. Halton Max Ultra Circular (MUC) start-up views ▪ Press the OK button to move to the next view. Press the ESC button to move to the previous view. ▪ Press the left or right arrow buttons to move between different parameter settings.
Page 21
Modbus RTU parameter list, see The default communication settings are Slave-ID 1, 115200bsp, O (Odd), 8 (bit), 1 (stop bit). You can change the communication settings on the correct parameter pages of the Halton Max Ultra Circular (MUC) controller: ▪ Controller support slave ID: 1..247 ▪...
Page 22
Halton Max MUC - Installation, commissioning and maintenance guide 4.2 S S t t ep b ep by s y st t ep ins ep instructions tructions 4.2.1 4.2.1 C C onfiguring basic c onfiguring basic contr ontroller set oller settings in analog mode...
Page 24
Halton Max MUC - Installation, commissioning and maintenance guide 4.2.5 4.2.5 R R eboo ebooting the c ting the contr ontroller oller C C ont onte e xt xt S S t t eps 1. Go to the controller parameter menu.
Halton Max MUC - Installation, commissioning and maintenance guide 5 5 Maint Maintenanc enance e ELEC C TRIC TRICAL HA AL HAZ Z ARD! ARD! Before carrying out any work, turn off the power supply to avoid injury from electrical current.
Page 26
Circular (MUC) actuat cular (MUC) actuator or Descrip Description tion The Halton Max Ultra Circular (MUC) airflow controller LAC-1.UO1 controls the airflow using ultrasound technology. It provides accurate airflow measurements with two ultrasound sensors. T T echnic echnical data al data...
Page 27
Halton Max MUC - Installation, commissioning and maintenance guide 7.2 C C ontr ontroller c oller connections onnections C C onnection diagr onnection diagram Fig. 16. Fig. 16. Halton Max Ultra Circular (MUC) connection diagram T T erminals erminals T T erminal erminal Name Name C C omment...
Halton Max MUC - Installation, commissioning and maintenance guide T T erminal erminal Name Name C C omment omment Analog actuator reference signal Ground 24 V DC/AC Power supply output for the analog actuator * Connected to Siemens GDB 161.1E actuator or Belimo LM24A-SR actuator...
Page 29
Halton Max MUC - Installation, commissioning and maintenance guide Wiring diagr Wiring diagram: Modbus c am: Modbus communic ommunication ation Fig. 18. Fig. 18. Wiring diagram: Modbus communication 7.4 P P ar aramet ameter ers s 7.4.1 7.4.1 Halt Halton Max Ultr...
Page 30
Halton Max MUC - Installation, commissioning and maintenance guide Default ault P P ar aramet ameter er Descrip Description tion V V alues alues v v alue alue AI1min Vmin=0 Minimum flow setting Vmin [m AI1max Vmax=Vnom Maximum flow setting Vmax [m...
Page 31
Halton Max MUC - Installation, commissioning and maintenance guide 7.4.2 7.4.2 Halt Halton Max Ultr on Max Ultra Cir a Circular (MUC) ins cular (MUC) installation c tallation cases ases V V alue o alue of f Safet ety dis...
Page 32
Halton Max MUC - Installation, commissioning and maintenance guide V V alue o alue of f Safet ety dis y distanc tance e Installation c tallation case Sensor position Sensor position paramet ameter er SelectDuctT SelectDuctType Side 5D..7D Outwards 5D..7D Inwards 5D..7D...
Page 33
Halton Max MUC - Installation, commissioning and maintenance guide V V alue o alue of f Safet ety dis y distanc tance e Installation c tallation case Sensor position Sensor position paramet ameter er SelectDuctT SelectDuctType Outwards 5D..7D Inwards 5D..7D Side 5D..7D...
Page 34
Halton Max MUC - Installation, commissioning and maintenance guide 7.4.3 7.4.3 Halt Halton Max Ultr on Max Ultra Cir a Circular (MUC) Modbus R cular (MUC) Modbus RTU par TU paramet ameter ers s 3xxxx 3xxxx, Input r , Input regis...
Page 35
Halton Max MUC - Installation, commissioning and maintenance guide Default ault R R egis egist t er er P P ar aramet ameter er Descrip Description tion V V alues alues v v alue alue 0 → Stop DamperStatus 30015 Status of damper 1 →...
Page 36
Halton Max MUC - Installation, commissioning and maintenance guide R R egis egist t er er Parameter Descrip Description tion V V alues alues Default v ault value alue 0 .. 1000 40030 K factor of PI regulator → 0.0 .. 100.0 0 ..