INSTALLATION AND MAINTENANCE INSTRUCTIONS
NC-100 Control Module
SPECIFICATIONS
Normal Operating Voltage:
External Supply Voltage (between Terminals T10 and T11)
Maximum:
Temperature Range:
Humidity:
Dimensions:
Accessories:
RELAY CONTACT RATINGS:
CURRENT RATING
2 A
3 A
2 A
0.46 A
0.7 A
0.9 A
0.5 A
0.3 A
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
NC-100 Supervised Control Modules are intended for use in addressable, two-
wire systems, where the individual address of each module is selected using
the built-in rotary switches. This module is used to switch an external power
supply, which can be a DC power supply, to notification appliances. It also su-
pervises the wiring to the connected loads and reports their status to the panel
as NORMAL, OPEN, or SHORT CIRCUIT. The NC-100 has two pairs of output
termination points available for fault-tolerant wiring and a panel-controlled
LED indicator. This module can be used to replace a C304 module that has
been configured for supervised wiring operation.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, these modules shall be connected to listed com-
patible system control panels only.
MOUNTING
The NC-100 mounts directly to 4-inch square electrical boxes (see Figure 2A).
The box must have a minimum depth of 2
cal boxes (SMB500) are available. The module can also mount to the DNR(W)
housing.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. When using control modules in nonpower limited applications,
the CB500 Module Barrier must be used to meet UL requirements for the sepa-
ration of power-limited and nonpower-limited terminals and wiring. The bar-
rier must be inserted into a 4˝×4˝×2
must be placed into the barrier and attached to the junction box (Figure 2A).
The power-limited wiring must be placed into the isolated quadrant of the
module barrier (Figure 2B).
NO-460-005
15 to 32VDC
80 Volts (RMS or DC)
32°F to 120°F (0°C to 49°C)
10% to 93% Non-condensing
4.675" H x 4.275" W x 1.4" D (Mounts to a 4˝ square by 2
SMB500 Electrical Box; CB500 Barrier
MAXIMUM VOLTAGE
25 VAC
30 VDC
30 VDC
30 VDC
70.7 VAC
125 VDC
125 VAC
125 VAC
1
/
inches. Surface mounted electri-
8
1
/
˝ junction box, and the control module
8
1
/
˝ deep box.)
8
LOAD DESCRIPTION
PF = 0.35
Resistive
Resistive
(L/R = 20ms)
PF = 0.35
Resistive
PF = 0.75
PF = 0.35
1.
Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2.
Set the address on the module per job drawings.
3.
Secure module to electrical box (supplied by installer), see Figure 2A.
Wire should be stripped to the appropriate length (recommended strip length
is
1
/
" to
3
/
"). Exposed conductor should be secured under the clamping plate
4
8
and should not protrude beyond the terminal block area. Caution: Do not loop
wire under terminals. Break wire run to provide supervision of connections.
IMPORTANT: When using the NC-100 control module for audio applications,
remove Jumper (J1) and discard. The Jumper is located on the back as shown
in Figure 1B. J1 must be removed whenever power supply monitoring feature
is not required.
NOTE: All references to power limited represent "Power Limited (Class 2)".
All references to Class A also include Class X.
FIGURE 1A. CONTROLS
AND INDICATORS:
C0909-01
1
12 Clintonville Road
Northford, CT 06472-1653
Phone: 203.484.7161
APPLICATION
Non-coded
Non-coded
Coded
Non-coded
Non-coded
Non-coded
Non-coded
Non-coded
FIGURE 1B:
J1
C0910-00
I56-3501-005
Need help?
Do you have a question about the Notifier NC-100 and is the answer not in the manual?
Questions and answers