1.Introduction
1.1 General Specifications
The unit provides the mains voltage monitoring and automatic transfer switching. In the event of a
mains voltage failure, the remote start relay output is energized and the unit automatically
transfers the load from the mains to the generator. Both automatic and manual control is possible.
A test mode is also available which allows the generator to be run without taking the load.
The unit is extensively programmable through the front panel, with password protection on
two levels. Operational parameters can also be monitored and controlled from a PC via a
built-in RS-232 communication port.
The unit monitors generator operation and gives warning of any faults that are detected.
If a fault is detected, the unit shuts down the engine and shows the failure message on the LCD
display.
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
TRANS-MINIATS
AUTOMATIC TRANSFER SWITCH
Introduction Brochure. ENG TRANS-MINIATS 01 V10 06/22

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TRANS-MINIATS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EMKO TRANS-MINIATS

  • Page 1 1.2 Warranty EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.
  • Page 2 2. Installation Ýçindekiler Before beginning installation of this product, please read the instruction manual and warnings below carefully. A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
  • Page 3: Electrical Connection

    2.3 Electrical Connection TRANS-MINIATS three phase connections schematic BATTERY - FUSE-5 BATTERY + FUSE-4 Emergency Stop or Configurable Input-1 Mains Break. Feedback or Configurable Input-2 Gen. Break. Feedback or FUSE-7 Configurable Input-3 Configurable Input-4 Generator Generator Ready or Contactor Configurable Input-5...
  • Page 4 3. Changing And Saving Parameters Values Operation Screen MAINS PROGRAM V12: 380V V1 : 220 Program Operator setting ü ü ü V23: 380V V2: 220V Language Technician setting V31: 380V V3: 220V Event log Factory adjustment Mains okay RESET RESET RESET AUTO AUTO...
  • Page 5 4. Parameters 4.1 Operator Parameters 4.1.1 Mains MAINS VOLT LEVEL ( Default Unit Mains->Volt level Under volt trip Mains Under Voltage Under volt reset Mains Under Voltage Return Over volt trip Mains Over Voltage Over volt reset Mains Over Voltage Return MAINS FREQ.
  • Page 6: System Network

    POWER LEVEL ( Generator->Power level Default Unit Under power shutdown Generator Under Power Shutdown 0(dis) 9999 Under power prealarm Generator Under Power Pre-Alarm 0(dis) 9999 Under power reset Generator Under Power Pre-Alarm Return 9999 Over power shutdown Generator Over Power Shutdown 0(dis) 9999...
  • Page 7: Lcd Display

    Stop Bit (0-> 1 stop bit,1-> 2 stop bit) Stop bit Note: = Selectable value of this parameter is “ENGLISH/TURKISH” at Trans-MiniATS (TR) devices. NO / NC : Normally Open / Normally Close NOR / PULS : Normal / Pulse...
  • Page 8 DATE & TIME SET ( Default Unit System->Date & time set Year Year Month Month Date Week Day of week Hour Hour Minute Minute Second Second DEFAULT SETTINGS ( Default Unit System->Default settings YES / NO Save setting to def. Save setting to default YES / NO Reset default sets...
  • Page 9 GENERATOR FREQ LEVEL ( Default Unit Generator-> Frequency level Under freq shutdown Generator Under Frequency Shutdown 30.0(dis) 75.0 43.0 Under freq prealarm Generator Under Frequency Pre-Alarm 30.0(dis) 75.0 45.0 Under freq reset Generator Under Frequency Pre-Alarm Return 30.0 75.0 46.0 Over freq shutdown Generator Over Frequency Shutdown 30.0(dis)
  • Page 10: Power Supply Battery

    WORKING CALENDAR Generator->Working calendar Default Unit Disable/enable select Working Calendar Disable or Enable DISBL ENABL DISBL Start time on monday Working Calendar Work Start Time on Monday 0.00 23.59 0.00 H.Min Stop time on monday Working Calendar Work Stop Time on Monday 0.00 23.59 23.59...
  • Page 11 4.2.6 Inputs CONF. INPUT-X ( Inputs->Conf. input-x Default Unit Dis,user conf.or list in1=2 0- Disable 0(dis) in2, 3=0 1- User Configured in4=0 2- Select From List in5=2 Polarity in1=1 0- Normally Open (Close To Activate) in2, 3=0 1- Normally Close (Open To Activate) in4, 5=0 Indication If User Configured...
  • Page 12 4.2.7 Outputs CONF. OUTPUT-1 ( Outputs->Conf. output-1 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function 0-NOT USED 1-AIR FLAP CONTROL 2-ALARM RESET 3-AUDIBLE ALARM 4-AUTO START INHIBIT 5-AUXILIARY MAINS FAILURE 6-BATTERY HIGH VOLTAGE 7-BATTERY LOW VOLTAGE 8-CALLING FOR SCHEDULED RUN(EXERCISE) 9-RESERVED...
  • Page 13 CONF. OUTPUT-2 ( Outputs->Conf. output-2 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options CONF. OUTPUT-3 ( Outputs->Conf. output-3 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options...
  • Page 14 4.2.9 User Adjustment MAINS VOLTAGE OFFSET ( Default Unit User adjustment->Mains voltage offset Mains V1 offset Mains V1 Offset Mains V offset Mains V Offset Mains V offset Mains V Offset GEN. VOLTAGE OFFSET ( Default Unit User adjustment->Gen. voltage offset Gen.
  • Page 15: Specifications

    5. Specifications Equipment use : Electrical control equipment for generating sets. Housing & Mounting :111 mm x 81 mm x 61 mm. (including connectors) . Plastic housing for panel mounting Panel Cut-Out : 81mm x 70mm. Protection Against Mech. Impacts : 1Joule (IK06) Protection Class...
  • Page 16: Other Informations

    Note: Devices have time clock. If real time clock is needed, “RTC” expression must be added to end of order code. Example: Trans-MiniATS.RTC Thank you very much for your preference to use Emko Elektronik products, please visit our web page to download detailed user Your Technology Partner manual.