EMKO TRANS-ATS.D Manual
EMKO TRANS-ATS.D Manual

EMKO TRANS-ATS.D Manual

Automatic transfer switch
Hide thumbs Also See for TRANS-ATS.D:

Advertisement

Quick Links

1. Introduction
1.1 General Specifications
The unit provides the voltage monitoring for both sources and automatic transfer switching. In
the event of any Source voltage failure, the remote start relay output is energized(
application selected
Both automatic and manual control is possible. A test mode is also available which allows the
generator with the higher priority to be run.
The unit is extensively programmable through the front panel, with password protection on
two levels. Operational parameters can also be monitored and controlled from a PC via a
built-in USB port.
The unit monitors both sources and gives warning of any faults that are detected.
If a fault is detected, the unit shuts down the engine(if generator application selected), transfers
load to the other source and shows the failure message on the LCD display.
1.2 Warranty
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from
the delivery date. This warranty is in force if duty and responsibilities which are determined in
warranty document and instruction manual performs by the customer completely.
1.3 Maintenance
Repairs should only be performed by trained and specialized personnel. Cut power to the device
before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
TRANS-ATS.D
AUTOMATIC TRANSFER SWITCH
) and the unit automatically transfers the load from one source to other .
Introduction Brochure. ENG TRANS-ATS_D 01 V05 04/21
if generator

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TRANS-ATS.D and is the answer not in the manual?

Questions and answers

Jimmy
June 6, 2025

To get another password when the latest password forgotten

Subscribe to Our Youtube Channel

Summary of Contents for EMKO TRANS-ATS.D

  • Page 1 LCD display. 1.2 Warranty EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date.
  • Page 2 2. Installation Ýçindekiler Before beginning installation of this product, please read the instruction manual and warnings below carefully. A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
  • Page 3: Electrical Connection

    2.3 Electrical Connection TRANS-ATS.D three phase connections schematic BATTERY - FUSE-7 BATTERY + FUSE-6 Emergency Stop or Configurable Input-1 FUSE-5 Configurable Input-2 FUSE-4 Configurable Input-3 Configurable Input-4 Configurable Input-5 Source 2 Configurable Input-6 Contactor Relay Configurable Input-7 Source 2 Ready or...
  • Page 4 3. Changing And Saving Parameters Values Operation Screen S1: MAINS PROGRAM V12: 380V V1 : 220 Operator setting Press the Up or V23: 380V V2: 220V ü Technician setting ü Down buttons to V31: 380V V3: 220V Factory adjustment select the section Source 1 okay you wish to view/change.
  • Page 5 4. Parameters 4.1 Operator Parameters 4.1.1 Source 1 (Mains) SOURCE 1 VOLT LEVEL (Source 1 Default Unit ->Volt level Under volt trip Source 1 Under Voltage Under volt reset Source 1 Under Voltage Reset Over volt trip Source 1 Over Voltage Over volt reset Source 1 Over Voltage...
  • Page 6: System Network

    4.2 Technician Parameters 4.2.1 System SYSTEM NETWORK ( System->Network Default Unit CT ratio Current Transformer Ratio 9999 PT ratio Voltage Transformer Ratio Type of AC system Select AC system; 0- 1 Phase 2 Wire 1- 3 Phase 4 Wire 2- 2 Phase 3 Wire L1-L2 3- 2 Phase 3 Wire L1-L3 Phase sequence Phase Sequence (dis, L123 or L321)
  • Page 7: Lcd Display

    BREAKERS ( Default Unit System->Breakers Type of Breaker Hardware Breaker Selection S2 brk.cls.contact NO / NC Source 2 Close Breaker Contact Type S2 brk.cls.relay NOR / PULS Source 2 Close Breaker Relay Type S2 brk.cls.time Source 2 Close Timer S2 brk.open relay NOR / PULS Source 2 Open Breaker Relay Type S2 brk.open time...
  • Page 8: System General

    DEFAULT SETTINGS ( Default Unit System->Default settings Save setting to def. YES / NO Save setting to default Reset default sets YES / NO Reset default sets Reset factory sets YES / NO Reset factory sets PASSWORD SETTINGS ( Default Unit System->Password settings Operator password...
  • Page 9 SOURCE 2 ACTIONS (Source 2 Actions -> Default Unit S2 fail.stop mode ENABL/DISBL ENABL Look Source 2 Failure at Stop Mode En/Dis S2 always return delay ENABL/DISBL DISBL Always Look Source 2 Return Delay S2 return delay Source 2 return delay S2 fail delay Source 2 fail dlelay 4.2.4 Load...
  • Page 10: Engine General

    4.2.5 Power Supply ENGINE PLANT BATTERY ( Unit Default Engine->Plant battery Under volt 6.0(dis) 30.0 10.0 Battery Undervolts Warning Under volt reset 30.0 10.5 Battery Undervolts Warning Reset Under volt delay Battery Undervolts Volts Delay Over volt 6.0(dis) 30.0 30.0 Battery Overvolts Warning Over volt reset 6.0 30.0...
  • Page 11 4.2.7 Inputs CONF. INPUT-X ( Inputs->Conf. input-x Unit Default Dis,user conf.or list in1=2 0- Disable 0(dis) in2,3=0 1- User Configured in4, 5=0 2- Select From List in6,7=0 in8=0 Polarity in1, 3=1 0- Normally Open (Close To Activate) in2, 4=0 1- Normally Close (Open To Activate) in5, 6=0 in7, 8=0 Indication...
  • Page 12 CONF. EXP. INPUT-X ( Inputs->Conf. exp. input-x Default Unit Dis,user conf.or list 0- Disable 0(dis) 1- User Configured 2- Select From List Hardware type > -Ve Switched Battery - > +Ve Switched Battery + Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Indication If User Configured...
  • Page 13 4.2.8 Outputs CONF. OUTPUT-1 ( Outputs->Conf. output-1 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function 0-NOT USED 1-AIR FLAP CONTROL 2-ALARM RESET 3-AUDIBLE ALARM 4-AUTO START INHIBIT 5-AUXILIARY SOURCE 1 FAILURE 6-BATTERY HIGH VOLTAGE 7-BATTERY LOW VOLTAGE 8-CALLING FOR SCHEDULED RUN(EXERCISE) 9-AUXILIARY SOURCE 2 FAILURE...
  • Page 14 CONF. OUTPUT-2 ( Outputs->Conf. output-2 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options CONF. OUTPUT-3 ( Outputs->Conf. output-3 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options...
  • Page 15 CONF. EXP. OUTPUT-7 ( Outputs->Conf. exp. output-7 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options CONF. EXP. OUTPUT-8 ( Outputs->Conf. exp. output-8 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options...
  • Page 16 Default Unit GPRS MODULE ( Expansion modules->GPRS Disable/enable select 0-DISABLE GPRS SERVER Expansion GPRS Module Selection GPRS SERVER GPRS CLIENT 3-SMS Call back selection ENABL/DISBL DISBL Call Back Selection Cell inf refresh rate 0(dis) Cell info refresh rate Location data ENABL/DISBL DISBL Location data...
  • Page 17 Error Messages And Explanations: Battery high warning! : Battery high error Battery low warning! : Battery low error Can bus warning! : Can bus error Emergency stop! : Emergency stop error Exp.spare-1 alarm! : Expansion module spare 1 error Exp.spare-2 alarm! : Expansion module spare 2 error Exp.spare-3 alarm! : Expansion module spare 3 error Exp.spare-4 alarm! : Expansion module spare 4 error Exp.spare-5 alarm! : Expansion module spare 5 error...
  • Page 18 Event Messages And Explanations: Battery high warning : Battery high error Battery low warning : Battery low error Can bus warning : Can bus error Changed mode to auto : Changed mode to auto Changed mode to man : Changed mode to manual Changed mode to stop : Changed mode to off Changed mode to test : Changed mode to test Emergency stop : Emergency stop error...
  • Page 19: Specifications

    5. Specifications Equipment use : Electrical control equipment for generating sets. Housing & Mounting : 229 mm x 152 mm x 41 mm. (including connectors) . Plastic housing for panel mounting Panel Cut-Out : 182mm x 135mm. Protection IP65 at front panel. Weight : Approximately 0,53 Kg.
  • Page 20 Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY Phone : +90 224 261 1900 Fax : +90 224 261 1912 Thank you very much for your preference to use Emko Elektronik products, please visit our web page to download detailed user Your Technology Partner manual.

Table of Contents