TRANS-MINIATS
AUTOMATIC TRANSFER SWITCH
User Manual
Þ
Introduction Manual. ENG TRANS-MINIATS 02 V06 09/18

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the TRANS MINI ATS and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for EMKO TRANS MINI ATS

  • Page 1 TRANS-MINIATS AUTOMATIC TRANSFER SWITCH User Manual EMKO ELEKTRON K A. . Ý Þ Demirta Org. San. Bolg. þ Karanfil Sk. No: 6 TR 16369 Bursa / TURKEY Phone : +90 224 261 1900 Faks : +90 224 261 1912 www.emkoelektronik.com.tr E-mail emko@emkoelektronik.com.tr...
  • Page 2: Table Of Contents

    CONTENTS 1.Introduction............................Page 1.1 General Specifications......................Page 1.2 Warranty............................ Page 1.3 Maintenance ..........................Page 1.4 Order Information........................Page 2.Installation............................Page 2.1 Unit Configuration........................Page 2.2 Panel Mounting.......................... Page Figure 2.1 Front View........................ Page Figure 2.2 Panel Cut-Out......................Page 2.3 Electrical Connection......................... Page 3.Definition Of Front Panel And Accessing To The Parameters............
  • Page 3 EU DECLARATION OF CONFORMITY Manufacturer’s Name : EMKO ELEKTRONIK A.S. Manufacturer’s Address : DOSAB, Karanfil Sk., No:6, 16369 Bursa, TURKEY The manufacturer hereby declares that the product: Product Name : Automatic Transfer Switch Type Number : TRANS-MINIATS Product Category : Electrical equipment for measurement, control and...
  • Page 4: Introduction

    1.2 Warranty EMKO Elektronik warrants that the equipment delivered is free from defects in material and workmanship. This warranty is provided for a period of two years. The warranty period starts from the delivery date. This warranty is in force if duty and responsibilities which are determined in warranty document and instruction manual performs by the customer completely.
  • Page 5: Unit Configuration

    2.Installation Ýçindekiler Before beginning installation of this product, please read the instruction manual and warnings below carefully. A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
  • Page 6: Electrical Connection

    2.3 Electrical Connection TRANS-MINIATS three phase connections schematic BATTERY - FUSE-5 BATTERY + FUSE-4 Emergency Stop or Configurable Input-1 Mains Break. Feedback or Configurable Input-2 Gen. Break. Feedback or FUSE-7 Configurable Input-3 Configurable Input-4 Generator Generator Ready or Contactor Configurable Input-5 Relay Mains Contactor...
  • Page 7: Front Panel Description

    3. Front Panel Description And Accessing To The Parameters 3.1 Front Panel Description ü RESET AUTO Number Comment This LED indicates that any alarm was detected. This LED shows that the unit is in the AUTO mode. In the Manual and Auto modes, this LED indicates that the engine is starting up or is running. This button is used for showing next page in normal operation.In Programming mode it is used for entering parameter edit section, saving parameter value and showing next parameters on the currently selected page.This button will also silence the alarm horn after a...
  • Page 8 LCD display Description Mains Page1 Current page name MAINS Measurement values V12: 380V V1 : 220 ü V23: 380V V2: 220V V31: 380V V3: 220V Mains okay Engine Status RESET or Error Messages AUTO 128x64 Dot-matrix LCD display. Use the Next button to select which Data display page (screen) is to be displayed.
  • Page 9 Data display pages on the LCD display; Mains Page1: V12: Mains voltage L1-L2 MAINS V23: Mains voltage L2-L3 V31: Mains voltage L3-L1 V12: 380V V1 : 220 Mains voltage L1-N V23: 380V V2: 220V Mains voltage L2-N V31: 380V V3: 220V Mains voltage L3-N Mains okay Mains Page2:...
  • Page 10 Input & Output Status Page: Inputs: Input status information. If an input is active, related digit INPUT & OUTPUT is displayed as "1" else it is displayed as "0". Conf. in-1, Conf. in-2, Conf. in-3, Conf. in-4, 1 4 5 8 Conf.
  • Page 11 Event Log display pages on the LCD display; Event Log Page1: 1.1: The first page of related event log EVENT LOG 1.1 Emergency stop: This message indicates that an emergency stop alarm has occurred. (Event history: 04/06/2013 date, 17:28:09 04/06/2013 17:28:09 time).
  • Page 12 Example-1: Displaying all Data display pages. MAINS MAINS GENERATOR V12: 380V V1 : 220 Fq:50.0Hz V12: 380V Fq:50.0Hz V23: 380V V2: 220V kWh : 30600 ü ü ü V31: 380V V3: 220V kVArh: 7200 Mains okay Mains okay On load LOAD LOAD POWER SUPPLY...
  • Page 13 Example-2: Displaying all Event Log display pages MAINS V12: 380V V1 : 220 Program Program ü V23: 380V V2: 220V Language ü Language ü V31: 380V V3: 220V Event log Event log Mains okay RESET RESET RESET Press Enter button AUTO AUTO AUTO...
  • Page 14: Accessing To The Operator Parameters

    3.2 Accessing To The Operator Parameters PROGRAM OPERATOR SETTING OPERATOR SETTING MAINS MAINS VOLT LEVEL MAINS VOLT LEVEL MAINS VOLT LEVEL Operator setting Password Mains Volt level Under volt trip Under volt trip Under volt trip ü ü ü ü ü...
  • Page 15: Accessing To The Technician Parameters

    3.3 Accessing To The Technician Parameters PROGRAM TECHNICIAN SETTING TECHNICIAN SETTING SYSTEM SYSTEM NETWORK SYSTEM NETWORK SYSTEM NETWORK Operator setting Password System Network CT ratio CT ratio CT ratio ü ü ü ü ü ü Technician setting Mains Breakers PT ratio 500 A PT ratio Factory adjustment...
  • Page 16 GENERATOR GENERATOR FREQ LEVEL GENERATOR FREQ LEVEL GENERATOR FREQ LEVEL Volt level Under freq shutdown Nominal frequency Under freq shutdown ü ü ü Frequency level Under freq prealarm 43.0 Hz Under freq prealarm Current level & act. Under freq reset Under freq reset Power level Over freq shutdown...
  • Page 17 INPUTS CONF. INPUT-1 CONF. INPUT-1 CONF. INPUT-1 TECHNICIAN SETTING Conf. input-1 Dis,user conf.or list Dis,user conf.or list Dis,user conf.or list Engine ü ü ü ü Inputs Conf. input-2 Polarity Polarity Outputs Conf. Input-3 Indication Indication Timers Conf. Input-4 Activation Activation AUTO AUTO AUTO...
  • Page 18 CURRENT OFFSET USER ADJUSTMENT CURRENT OFFSET CURRENT OFFSET Current I1 offset Mains voltage offset Current I1 offset Current I1 offset ü ü ü Gen. voltage offset Current offset Battery offset AUTO USER ADJUSTMENT BATTERY OFFSET BATTERY OFFSET BATTERY OFFSET Mains voltage offset Batt.volt offset Batt.volt offset Batt.volt offset...
  • Page 19: Changing And Saving Parameter Values

    3.4 Changing And Saving Parameters Values Operation Screen MAINS PROGRAM V12: 380V V1 : 220 Program Operator setting ü ü V23: 380V V2: 220V Language ü Technician setting V31: 380V V3: 220V Event log Factory adjustment Mains okay RESET RESET RESET AUTO AUTO...
  • Page 20: Parameters

    4. Parameters 4.1 Operator Parameters 4.1.1 Mains MAINS VOLT LEVEL ( Default Unit Mains->Volt level Under volt trip Mains Under Voltage Under volt reset Mains Under Voltage Reset Over volt trip Mains Over Voltage Over volt reset Mains Over Voltage Reset MAINS FREQ.
  • Page 21 POWER LEVEL ( Generator->Power level Default Unit Under power shutdown Generator Under Power Shutdown 0(dis) 9999 Under power prealarm Generator Under Power Pre-Alarm 0(dis) 9999 Under power reset Generator Under Power Pre-Alarm Reset 9999 Over power shutdown Generator Over Power Shutdown 0(dis) 9999...
  • Page 22: Technician Parameters

    4.2 Technician Parameters 4.2.1 System SYSTEM NETWORK ( System->Network Default Unit CT ratio Current Transformer Ratio 9999 PT ratio Voltage Transformer Ratio Type of AC system Select AC system; 0- 1 Phase 2 Wire 1- 3 Phase 4 Wire 2- 2 Phase 3 Wire L1-L2 3- 2 Phase 3 Wire L1-L3 Generator kVA rating Generator kVA rating set...
  • Page 23 Example: If Hardware Breaker Selection parameter is selected as 0; For closing For opening Gen. Shalter Gen. Shalter Gen. Closed Out. (NO) t[s] Gen. Closed Out. (NC) t[s] Gen. Shalter Opened Closed User Configured: Mains and Gen breaker s have only close drives, when want to breaker close, close breaker output on and after 1 sec.
  • Page 24 rtNB brCP brCP brCP brCP brCP brCP brCP brCP brCP brCP GCB close sPLD sPLD sPLD command t[s] brOP brOP brOP GbCt GbCt GbCt GbCt GbCt GbCt GbCt GCB open command t[s] Feedback input t[s] GCB fail to close alarm t[s] Example-2: GCB Open Diagram If Hardware Breaker Selection parameter is selected as 2 (user configured), Gen.
  • Page 25 Mains Open Timer This is used to monitor the opening of the mains contactor or breaker. It will only operate if an auxiliary input is configured as ‘Mains Closed Auxiliary’ and connected to the auxiliary on the mains contactor or breaker.
  • Page 26 COMMUNICATION ( Default Unit System->Communication Slave address Slave Address Baud Rate 0 - 1200 baud 1 - 2400 baud Baud rate 2 - 4800 baud 3 - 9600 baud 4 - 19200 baud 5 - 38400 baud Parity Parity NONE EVEN Stop bit Stop Bit (0->...
  • Page 27: Mains

    4.2.2 Mains MAINS VOLT LEVEL ( Default Unit Mains->Volt level Under volt trip Mains Under Voltage Under volt reset Mains Under Voltage Reset Over volt trip Mains Over Voltage Over volt reset Mains Over Voltage Reset MAINS FREQ. LEVEL ( Default Unit Frequency...
  • Page 28 CUR LEVEL & ACT Generator->Current level & act. Default Unit Under cur. set 9999 Generator Under Current Set Under cur. prealarm Generator Under Current Pre-Alarm 0(dis) 9999 Under cur. reset Generator Under Current Pre-Alarm Reset 9999 Under cur. act. Generator Under Current Actions 0(dis) Disable Warning (Alarm Only, No Shutdown)
  • Page 29: Generator

    WORKING CALENDAR Generator->Working calendar Default Unit Disable/enable select DISBL ENABL DISBL Working Calendar Disable or Enable Start time on monday 0.00 23.59 0.00 H.Min Working Calendar Work Start Time on Monday Stop time on monday 0.00 23.59 23.59 H.Min Working Calendar Work Stop Time on Monday Start time on tues.
  • Page 30: Engine

    4.2.5 Engine LOAD TEST ( Default Unit Engine->Load test Disable/enable select 0-DISABLE Disable, No Load or On Load Selection 1-NO LOAD 1-NO LOAD 2-ON LOAD Disable, No Load or On Load Selection DISABLE T est mode disable NO LOAD The generator will be running without taking the load in test mode. ON LOAD T he generator will be running with load in test mode.
  • Page 31: Inputs

    4.2.6 Inputs CONF. INPUT-1 ( Inputs->Conf. input-1 Default Unit Dis,user conf.or list 0- Disable 0(dis) 1- User Configured 2- Select From List Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Indication If User Configured 0- Status 1- Warning Non-Latching 2- Warning Latching 3- Electrical Trip...
  • Page 32 CONF. INPUT-2 ( Inputs->Conf. input-2 Default Unit Dis,user conf.or list 0- Disable 0(dis) 1- User Configured 2- Select From List Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Indication If User Configured 0- Status 1- Warning Non-Latching 2- Warning Latching 3- Electrical Trip 4- Shutdown...
  • Page 33 CONF. INPUT-3 ( Inputs->Conf. input-3 Default Unit Dis,user conf.or list 0- Disable 0(dis) 1- User Configured 2- Select From List Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Indication If User Configured 0- Status 1- Warning Non-Latching 2- Warning Latching 3- Electrical Trip 4- Shutdown...
  • Page 34 CONF. INPUT-4 ( Inputs->Conf. Input-4 Default Unit Dis,user conf.or list 0- Disable 0(dis) 1- User Configured 2- Select From List Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Indication If User Configured 0- Status 1- Warning Non-Latching 2- Warning Latching 3- Electrical Trip 4- Shutdown...
  • Page 35 CONF. INPUT-5 ( Inputs->Conf. Input-5 Default Unit Dis,user conf.or list 0- Disable 0(dis) 1- User Configured 2- Select From List Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Indication If User Configured 0- Status 1- Warning Non-Latching 2- Warning Latching 3- Electrical Trip 4- Shutdown...
  • Page 36 CONFIGURABLE INPUTS SELECTIONS 0 REMOTE START ON LOAD In AUTO mode, if one of the configurable inputs are selected as 0 (Remote Start On Load), the unit doesn't perform the mains failure control in order to start the generator. In AUTO mode, if one of the configurable inputs are selected as 0 (Remote Start On Load ) and this input is active, then the unit will perform the start sequence...
  • Page 37 15 AUTO RESTORE INHIBIT When module in the AUTO mode. In the event of a remote start or mains failure, the generator will be instructed to start and take load. On removal of the remote start signal or mains return, the module will continue to run the generator on load until this AUTO RESTORE INHIBIT input is removed.
  • Page 38: Outputs

    4.2.7 Outputs CONF. OUTPUT-1 ( Outputs->Conf. output-1 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function 0-NOT USED 1-AIR FLAP CONTROL 2-ALARM RESET 3-AUDIBLE ALARM 4-AUTO START INHIBIT 5-AUXILIARY MAINS FAILURE 6-BATTERY HIGH VOLTAGE 7-BATTERY LOW VOLTAGE 8-CALLING FOR SCHEDULED RUN(EXERCISE) 9-RESERVED...
  • Page 39 CONF. OUTPUT-2 ( Outputs->Conf. output-2 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options CONF. OUTPUT-3 ( Outputs->Conf. output-3 Default Unit Polarity 0- Normally Open (Close To Activate) 1- Normally Close (Open To Activate) Function The same as Configurable Output-1 options...
  • Page 40 CONFIGURABLE OUTPUTS SELECTIONS 0 NOT USED Output is not used 1 AIR FLAP CONTROL Normally used to control an air flap, this output becomes active upon an Engine shutdown failure situation. Inactive when the set has come to rest. 2 ALARM RESET The output indicates that an alarm reset being performed.
  • Page 41 22 DELAYED ALARMS ACTIVE The output indicates that the delayed alarms now enabled. Can be used to control external logic circuitry. 23 DIGITAL INPUT1 ALARM This output indicates that digital input 1 alarm has occurred. 24 DIGITAL INPUT2 ALARM This output indicates that digital input 2 alarm has occurred.
  • Page 42 48 GENERATOR FAILED TO CLOSE This output source has intended to be used to indicate a failure of the generator contactor or breaker. It can only be used if the unit is configured to use 'generator closed auxiliary' feedback. 49 GENERATOR FAILED TO OPEN This output source has intended to be used to indicate a failure of the generator contactor or breaker.
  • Page 43 70 MAINS FAILED TO OPEN This output source has intended to be used to indicate a failure of the mains contactor or breaker. It can only be used if the unit is configured to use 'mains closed auxiliary' feedback. 71 MAINS FAILURE This output indicates that the unit has sensed that a failure of the incoming AC mains supply.
  • Page 44 92 RESERVED 93 RESERVED 94 REMOTE START PRESENT This output indicates that a digital input that has been configured as 'remote start' is active. This output could be used to pass the remote start signal on to else where in the control system. 95 RESERVED 96 SHORT CIRCUIT This output indicates that the module has detected a short circuit on the generator output.
  • Page 45 RESERVED RESERVED RESERVED RESERVED RESERVED RESERVED 122 REMOTE CONTROL ACTIVE This output indicates that the engine is being controled remotely.
  • Page 46: Timers

    4.2.8 Timers START TIMERS ( Unit Default Timers->Start timers Mains transient delay 20.0 Mains Transient Delay Mains fail start dely 9999 Mains Fail Start Delay Remote start delay 3600 Remote Start Delay Generator fail delay Generator fail delay Safety on delay Safety On Delay Warming up time Warmup Time...
  • Page 47 STOPPING TIMERS ( Unit Default Timers->Stopping timers Mains return delay 0 3600 Mains Return Delay Remote stop delay Remote Stop Delay Cooling time 0 (dis) 3600 Cooling Time Fail to stop delay Fail To Stop Time Mains Return Delay This timer dictates how long the unit will wait before it will un-load the generator (back to the mains supply if AMF) and initialise it's run-on and shutdown cycle.
  • Page 48: User Adjustment

    4.2.9 User Adjustment MAINS VOLTAGE OFFSET ( Default Unit User adjustment->Mains voltage offset Mains V1 offset Mains V1 Offset Mains V offset Mains V Offset Mains V offset Mains V Offset GEN. VOLTAGE OFFSET ( Default Unit User adjustment->Gen. voltage offset Gen.
  • Page 49 Error Messages And Explanations: Battery high warning! : Battery high error Battery low warning! : Battery low error Emergency stop! : Emergency stop error Fail to start alarm! : Fail to start alarm Gen break.close fail! : Generator breaker not closed alarm Gen break.open fail! : Generator breaker not opened alarm Gen over frq.prealr! :...
  • Page 50 Event Messages And Explanations: Battery high warning : Battery high error Battery low warning : Battery low error Changed mode to auto : Changed mode to auto Changed mode to man : Changed mode to manual Changed mode to stop : Changed mode to stop Changed mode to test : Changed mode to test...
  • Page 51: Specifications

    5. Specifications Equipment use : Electrical control equipment for generating sets. Housing & Mounting :111 mm x 81 mm x 61 mm. (including connectors) . Plastic housing for panel mounting Panel Cut-Out : 81mm x 70mm. Protection IP65 at front panel. Weight : Approximately 0,3 Kg.
  • Page 52: Other Informations