Installation Manual TCS-NET Relay Interface • Thank you very much for purchasing this TOSHIBA / Carrier TCS-NET Relay Interface. • Please read this manual carefully beforehand for proper installation of the relay interface. Contents 1 Precautions for safety ..........2 2 Introduction .
Installation Manual TCS-NET Relay Interface Precautions for safety • Read these “Precautions for Safety” carefully before installation. • The precautions described below include important items regarding safety. Observe them without fail. Understand the following details (indications and symbols) before reading the body text, and follow the instructions.
Installation Manual TCS-NET Relay Interface Introduction Applications / functions / specifications Applications • The TCS-NET Relay Interface is used to connect air conditioners (with TCC-LINK installed) to the air conditioning control system or BACnet system. Functions • The TCS-NET Relay Interface converts signals between TCC-LINK and RS-485. Specifications Power supply 120 VAC, 60 Hz...
Installation Manual TCS-NET Relay Interface Before installation Check the following package contents. Item Quantity Remarks TCS-NET Relay Interface Installation Manual Screw 5/32” x 0.47” (M4 x 12 mm) tapping screws Cable clamp Use the following wiring materials to connect the communication cables and power cables. (locally procured) Line Description Type...
Installation Manual TCS-NET Relay Interface Connection of power cables / earth wires / communication cables CAUTION • The RS-485 communication cables have polarity. Connect A to A, and B to B. If connected with incorrect polarity, the unit will not work. •...
Page 7
Installation Manual TCS-NET Relay Interface The TCC-LINK The RS-485 communication cable must be To connect 2 cables, communication cable must earthed on address 1 (Relay Interface change the preset cable be earthed on the air address SW=1) TCS-NET Relay Interface. clamp to the provided one conditioner.
Installation Manual TCS-NET Relay Interface Wiring connection The following describes a connection example when two or more TCS-NET Relay Interface units are used. Terminator resistor setting (See “6 Setting” for the setting method.) • Set the RS-485 terminator resistor to “120 ohm” for address1 (Relay Interface address SW1=1) TCS-NET Relay Interface unit, and set to “open”...
Installation Manual TCS-NET Relay Interface Setting The following settings are necessary to use TCS-NET Relay Interface. • SW1 TCS-NET Relay Interface address set switch When two or more TCS-NET Relay Interface are used, set a different address for SW1 to avoid address duplication.
Installation Manual TCS-NET Relay Interface Test run Before starting test run Complete the air conditioner test run. Turn on the power of the TCS-NET Relay Interface after all cable connections and settings are completed. Then turn on power of the BACnet Server. Test run Check the TCC-LINK and RS-485 communication status of the TCS-NET Relay Interface by checking the blinking of the LEDs.
Page 13
Free Manuals Download Website h p://myh66.com h p://usermanuals.us h p://www.somanuals.com h p://www.4manuals.cc h p://www.manual-lib.com h p://www.404manual.com h p://www.luxmanual.com h p://aubethermostatmanual.com Golf course search by state h p://golfingnear.com Email search by domain h p://emailbydomain.com Auto manuals search h p://auto.somanuals.com TV manuals search h p://tv.somanuals.com...