Carrier HN72ZA001 Installation Instructions
Carrier HN72ZA001 Installation Instructions

Carrier HN72ZA001 Installation Instructions

Quick connect kit and current sensing relay for rgapa ceiling-mounted return air purifier

Advertisement

HN72ZA001
Quick Connect Kit and Current Sensing Relay
for RGAPA Ceiling-Mounted Return Air Purifier

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance, or
use can cause explosion, fire, electrical shock, or other conditions which
may cause death, personal injury or property damage. Consult a
qualified installer, service agency, or your distributor or branch for
information or assistance. The qualified installer or agency must use
factory-authorized kits or accessories when modifying this product.
Refer to individual instructions packaged with kits or accessories when
installing.
Follow all safety codes. Wear safety glasses, protective clothing, and
work gloves. Use quenching cloth for brazing operations. Have a fire
extinguisher available. Read these instructions thoroughly and follow all
warning or cautions included in literature and attached to the unit.
Consult local building codes and the current editions of the National
Electrical Code (NEC) NFPA 70.
In Canada, refer to the current editions of Canadian Electrical Code CSA
C22.1.
Recognize safety information. This is the safety alert symbol
you see this symbol on the unit and in instructions or manuals, be alert to
the potential for personal injury. Understand the signal words
DANGER, WARNING, and CAUTION. These words are used with the
safety alert symbol. DANGER identifies the most serious hazards which
will result in severe personal injury or death. WARNING signifies
hazards which could result in personal injury or death. CAUTION is
used to identify unsafe practices, which may result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability, or
operation.
WARNING
!
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury or death.
Before installing or servicing the unit, always turn off all power to unit.
There may be more than one disconnect switch. Lock out and tag
switch with a suitable warning label.
CAUTION
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear
appropriate protective clothing, safety glasses and gloves when
handling parts.

HN72ZA001 Kit Contents

• Current Sensing Relay
• Conduit Fitting
• Wire Nuts
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Installation Instructions
NOTE: Read this entire instruction manual before starting the installation.
. When

Tools Required

• Small cross-head screwdriver

INSTALLATION

IMPORTANT: This kit is intended for ceiling-mounted air purifier
units (RGAPA) only. If your unit is mounted next to the furnace or fan
coil (DGAPA or PGAPA), discard this kit.

Mounting to Fan Coil Air Handlers

!
UNIT COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
For Furnace Purifiers:
-
Black Lead connect to Hot (L1) or EAC-1 when provided.
-
White Lead connect to Neutral (L2) or EAC-2 when provided.
-
Green/Ground Lead connect to appliance ground (chassis).
For Fan Coil Purifiers:
-
Black Lead connect to L1.
-
White Lead connect to L2.
-
Green Lead connect to appliance ground (chassis).
IMPORTANT: Power connections are to be made inside the fan coil
wiring compartment per local electrical codes, and the two in-line fuses
that are provided with the air purifier must be installed in the fan coil
wiring compartment.
1. Disconnect main power to the unit and lock out / tag.
2. Open the ceiling grille cover, lower the inner unit, and remove the
filter cartridge and FEM. If necessary, refer to the Installation and
User Instructions.
3. From the top of the air purifier, accessible in the space above the
ceiling, remove the access cover from the RGAPA electrical box.
4. Route the power wiring from the purifier disconnect to a knockout
on the fan coil air handler that provides access to the incoming
power wiring compartment. Affix the end of the conduit to the fan
coil air handler using the included conduit fitting.
5. Remove the yellow and black primary wires from the fan coil air
handler transformer terminals and connect the quick-connect
"piggyback" terminals of the quick-connect kit leads exiting the air
purifier power conduit assembly to the transformer terminals.
6. Reconnect the yellow and black primary wires to their respective
transformer terminals on the "piggyback" terminals.
7. Attach the ground ring terminal on the third wire to the fan coil air
handler chassis ground
1
CAUTION
(Fig.
1).

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HN72ZA001 and is the answer not in the manual?

Questions and answers

Summary of Contents for Carrier HN72ZA001

  • Page 1 6. Reconnect the yellow and black primary wires to their respective handling parts. transformer terminals on the "piggyback" terminals. 7. Attach the ground ring terminal on the third wire to the fan coil air HN72ZA001 Kit Contents handler chassis ground (Fig. • Current Sensing Relay •...
  • Page 2 Fig. 1 – Quick-Connect Kit A210033 Fig. 3 – Wrap Common through Relay A210032 Fig. 2 – Connection Wiring Diagram © 2021 Carrier. All rights reserved. Edition Date: 2/21 Catalog No: IIK-HN72ZA-01 A Carrier Company Replaces: New Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Table of Contents