The UD10-DCU is designed for use with most currently available The UD10-DCU Universal Display can be used with various 4-20 Det-Tronics gas detectors . Refer to the "Specifications" section of this mA gas detection devices, with or without HART . The unit provides manual for a list of compatible gas detectors .
NOTE MAGNETIC SWITCHES Det-Tronics offers two magnet options for activating Four internal magnetic switches provide a non-intrusive user interface internal magnetic switches. While the two magnets can that allows navigation through the menu . See Figure 1 for switch usually be used interchangeably, the best results will locations .
Access To Menus CONFIGURATION OVERVIEW To access the menus, use the magnet to activate the ENTER/ The user must select the sensor mode/type manually from the UD10- SELECT button . This will display the Main Menu . DCU display . The selection options are: •...
CALIBRATION GAS CONCENTRATION require a gas concentration of 50% full scale . Calibration gas concentration can be viewed from the UD10-DCU menu under The calibration gas concentration is programmed from S Display Status->LON Config . downloaded to the UD10-DCU . See Table 3 for calibration gas limits . NTMOS, CGS, and PIR9400 Table 2—UD10-DCU Alarm Limits UD10-DCU Limits...
IMPORTANT SAFETY NOTES LOGGING Events that can be logged in the UD10-DCU include: CAUTION • Calibration (Date, time, and success Y/N are logged for detectors The wiring procedures in this manual are intended to that do not provide their own calibration logging capabilities .) ensure proper functioning of the device under normal conditions.
INSTALLATION If the vapor of interest is lighter than air, place the detector above the potential gas leak . Place the detector close to the floor for NOTE gases that are heavier than air . Note that air currents may cause a For complete instructions regarding wiring, installation, gas that is slightly heavier than air to rise under some conditions .
WIRING COM 2 - Communication network connections: Connect to COM 1 terminals of the previous device on POWER SUPPLY REQUIREMENTS the loop, A to A and B to B . Calculate the total gas detection system power consumption rate in watts from cold start-up . Select a power supply with adequate 24 VDC - Connect the “+”...
Page 11
UD10 Sensor Connector DISPLAY UNIT FACTORY USE ONLY LON ADDRESS SELECTION SWITCHES SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 SHIELD J3-4 1 B COM J3-5 1 A COM J3-6 VALUES OF ALL SWITCHES IN THE ON POSITION ARE ADDITIVE. Power Supply Connector A2509 Figure 2—Wiring Terminal Board...
LON ADDRESS SWITCH SETTING DETECTOR TYPE/MODE SELECTION PROCEDURE Each device on the LON/SLC must be assigned a unique address . After power has been applied and the warm-up period is complete, This is accomplished by setting DIP switches on the module’s circuit select the UD10-DCU operating mode .
CONFIGURATION Create a new DCU point with the correct LON address/point number . See Figure 4 below . Figure 4—Point Type Selection Screen 95-8656...
Page 14
The DCU configuration software supports six detector types: • Explosive • Oxygen • Universal (Automatic Calibration) • Universal (Manual Calibration) • PointWatch • DuctWatch Table 5 shows the recommended settings for each detector type . Table 5—Recommended Settings for each Detector Type Detector Type Recommended Configuration Comments...
Page 15
Enter the appropriate data on the DCU Editor Screen . See Figure 5 . The units and range entered at S will be seen in S and the Controller, but are not sent to the UD10-DCU . It is the user’s responsibility to ensure that S matches the actual detector type .
Page 16
UD10-DCU Input Trim Time and date for the UD10-DCU is automatically set by the EQP When the UD10-DCU is used with a detector that supports HART controller via the LON network . Changes to the time on the S communication, an automated process can be used to trim the UD10- computer will be reflected at the UD10-DCU when the controller RTC DCU input .
OPTIONAL SYSTEM TESTS DISPLAY BACKLIGHT OPERATION The following tests are available for verifying proper operation of The UD10-DCU can be programmed to turn on the backlight feature various functions of the gas detection system: of the digital display when an alarm or fault occurs or a magnetic switch is activated .
TROUBLESHOOTING Example: If a Fault condition is indicated on the UD10-DCU faceplate, the For a Display (UD10-DCU) related fault: nature of the fault can be determined by using the magnetic tool to Main Menu > Display Status > Fault/Status > Fault navigate to the appropriate Fault screen .
Page 19
Table 7—Troubleshooting Guide - Device Faults Device Faults Description Recommended Action Loop Fault Current loop below fault threshold Check 4-20 mA loop wiring for shorts or opens. Supply Voltage Verify proper wiring to the device and correct voltage 24 volt power supply voltage too low Fault output from the power supply.
Table 7—Troubleshooting Guide - Device Faults, Continued Device Faults Description Recommended Action Power may have been interrupted while the de- EE Fault Fault in non-volatile memory vice was updating its internal data logs. Recycle power. Sensor signal level is outside the range of the Ref ADC Sat Return to factory.
* Carbon dioxide only. 5.86 ** Hydrogen sulfide only. (14.9) (13.2) (6.9) DETECTOR COMPATIBILITY— The UD10-DCU can be used with the Det-Tronics gas detectors listed in Table 8 . UNIT OF MEASUREMENT— (11.9) PPM, % LFL, % V/V, LFLM, or Mg/M 3.46 (8.8) OPERATING TEMPERATURE—...
Page 22
WIRING TERMINALS— CERTIFICATION— 14 to 18 AWG, 2 .5-0 .75 mm wire can be used . For complete approval details, refer to the appropriate Appendix: CONDUIT ENTRIES— 3/4” NPT or M25 . ® ENCLOSURE MATERIAL— APPROVED Epoxy coated aluminum or 316 stainless steel . Appendix A –...
DEVICE REPAIR AND RETURN ORDERING INFORMATION Prior to returning devices, contact the nearest local Detector Sensor module, transmitter module and termination boxes (if used) Electronics office so that a Return Material Authorization (RMA) must be ordered separately . number can be assigned . A written statement describing the malfunction must accompany the returned device or component Refer to the UD10-DCU Model Matrix for ordering details .
UD10-DCU MODEL MATRIX MODEL DESCRIPTION UD10-DCU Universal Display Unit TYPE MATERIAL Aluminum Stainless Steel (316) TYPE THREAD TYPE 5 Port, Metric M25 5 Port, 3/4" NPT TYPE OUTPUTS Relay, 4-20 mA, RS485, HART EQP / DCU Emulator TYPE APPROVAL INMETRO (Brazil) Russia FM/CSA/ATEX/CE/IECEx TYPE...
APPENDIX A FM APPROVAL DESCRIPTION Class I, Div . 1, Groups B, C & D T5; Class I, Div . 2, Groups B, C & D T4; Class I, Zone 1/2 AEx d IIC T5; Class II/III, Div . 1/2, Groups E, F & G . T amb –40°C to +75°C NEMA/Type 4X, IP66 Conduit seal not required .
APPENDIX B CSA CERTIFICATION DESCRIPTION CSA 2029512 . Class I, Div . 1, Groups B, C & D T5; Class I, Div . 2, Groups B, C & D T4; Class II/III, Div . 1/2, Groups E, F & G T5 . (Tamb = –40°C to +75°C) Type 4X Conduit seal not required .
• The UD10 and AV10 control unit complies with EN 60079-29-4 when connected to a Detector Head that also has been evaluated to EN 60079-29-4 . • Flameproof joints are not user serviceable; contact Det-Tronics . • The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to EN 60079-1:2014, §16 •...
Page 28
EN 60079-29-1 standard . • The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to EN 60079-1:2014, §15 . • Flameproof joints are not user serviceable; contact Det-Tronics Service . 95-8656...
Page 29
• The UD10 and AV10 control unit complies with IEC 60079-29-4 when connected to a Detector Head that also has been evaluated to IEC 60079-29-4 . • Flameproof joints are not user serviceable; contact Det-Tronics . • The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to IEC 60079-1:2014, §16 •...
Page 30
IEC 60079-29-1 standard . • The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to IEC 60079-1:2014, §15 . • Flameproof joints are not user serviceable; contact Det-Tronics Service . 95-8656...
• The UD10 and AV10 control unit complies with IEC 60079-29-4 when connected to a Detector Head that also has been evaluated to IEC 60079-29-4 . • Flameproof joints are not user serviceable; contact Det-Tronics . • The actual enclosure must provide a maximum measured reference pressure of 15 bar measured according to IEC 60079-1:2014, §16 •...
APPENDIX F UD10-DCU with GT3000 TOXIC GAS DETECTOR NOTE For complete information regarding the GT3000 Gas Detector, refer to instruction manual 95-8616. WIRING UD10-DCU with GT3000/C706X 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet. Maximum recommended cable length from UD10 to sensor/STB termination box is 2000 feet.
SEE NOTE 1 BLACK UD10 DISPLAY UNIT Sensor Connector SENSOR TERMINATION BOX GREEN SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 SHIELD J3-4 1 B COM J3-5 1 A COM J3-6 GT3000 GAS DETECTOR Power Supply Connector NOTE 1 GROUND THE SHIELD AT THE DISPLAY UNIT END ONLY.
CALIBRATION From UD10-DCU Using the magnet to activate the switches on the UD10-DCU GT3000 WITH TOXIC GAS SENSOR display, navigate to the "Calibration" menu . Main Menu From GT3000: Process Vars Using the magnet, activate the magnetic calibration switch on Display Status Device Cal Calibration...
GT3000 WITH OXYGEN SENSOR From UD10-DCU Using the magnet to activate the switches on the UD10-DCU From GT3000: display, navigate to the Calibration menu . Using the magnet, activate the magnetic calibration switch on Main Menu the GT3000 . The green LED turns to yellow . Process Vars Display Status Device Cal...
APPENDIX G UD10-DCU with PIR9400 POINTWATCH IR GAS DETECTOR NOTE For complete information regarding the PIR9400 Gas Detector, refer to instruction manual 95-8440. WIRING UD10-DCU with PIR9400 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
PIRTB JUNCTION BOX PIR9400 DETECTOR UD10 DISPLAY UNIT SEE NOTE 1 GREEN Sensor Connector SPARE CHASSIS YELLOW 4 – 20 4 – 20 WHITE BLACK SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 SHIELD J3-4 1 B COM J3-5 1 A COM J3-6...
CHANGING OPERATING MODES CALIBRATE SWITCH HOLD CALIBRATION MAGNET When used with a PIR9400, the operating mode of the UD10-DCU AT OUTSIDE BASE OF JUNCTION REMOTE LED BOX AT THIS LOCATION must be changed from “HART Device” to “PIR9400” mode . Refer to TO ACTIVATE CALIBRATION SWITCH the “Startup”...
APPENDIX H UD10-DCU with MODEL PIRECL NOTE For complete information regarding the PIRECL Gas Detector, refer to instruction manual 95-8526. WIRING UD10-DCU with PIRECL/OPECL/NTMOS/CGS 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet. Maximum recommended cable length from UD10 to sensor/STB termination box is 2000 feet.
MODEL PIRECL BLACK 24 VDC – 24 VDC + CALIBRATE 24 VDC – 24 VDC + 4-20 MA + WHITE 4-20 MA – RS-485 B RS-485 A RELAY POWER (RED) UD10 WIRING TO OPTIONAL FAULT (ORANGE) DISPLAY UNIT RELAY BOARD Sensor Connector LOW ALARM (WHITE) NO USER CONNECTION...
CALIBRATION To initiate calibration from the PIRECL while monitoring calibration using the UD10-DCU display: To initiate calibration of the PIRECL from the UD10-DCU Display: Using the magnet, activate the magnetic calibration switch on Using the magnet to activate the switches on the UD10-DCU the PIRECL detector .
MENU STRUCTURE UD10-DCU with Model PIRECL Refer to the following menu when using the UD10-DCU’s LCD display and internal magnetic switches . MENU HELP Status menus only allow the user to view the data. The Setup menus allow the user to both view and edit the data. 95-8656...
APPENDIX I UD10-DCU with OPEN PATH ECLIPSE MODEL OPECL NOTE For complete information regarding the OPECL Gas Detector, refer to instruction manual 95-8556. WIRING UD10-DCU with PIRECL/OPECL/NTMOS/CGS 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Page 44
MODEL OPECL BLACK 24 VDC – 24 VDC + CALIBRATE 24 VDC – 24 VDC + 4-20 MA + WHITE 4-20 MA – RS-485 B RS-485 A Sensor Connector UD10 DISPLAY UNIT NO USER CONNECTION SHIELD J3-1 2 B COM J3-2 2 A COM J3-3...
ORIENTATION CALIBRATION OPECL modules must be affixed to a solid, non-vibrating structure To initiate zero calibration of the OPECL from the UD10-DCU capable of supporting a minimum of 100 lbs (46 kg), located within Display: the system’s rated separation distance . See examples below . 1 .
OPECL TRANSMITTER LAMP To initiate zero calibration from the OPECL: FAULT CONDITION 1 . Using the magnet, activate the magnetic calibration switch on the If the OPECL system experiences a Transmitter (Tx) Lamp Fault OPECL receiver . See the figure below . The green LED will turn condition, the UD10-DCU display will not indicate a fault condition red .
APPENDIX J UD10-DCU with NTMOS H S SENSOR NOTE For complete information regarding the NTMOS Gas Detector, refer to instruction manual 95-8604. WIRING UD10-DCU with PIRECL/OPECL/NTMOS/CGS 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet. Maximum recommended cable length from UD10 to sensor/STB termination box is 2000 feet.
Page 48
ORANGE SEE NOTE 1 GREY YELLOW BLACK WHITE UD10 DISPLAY UNIT Sensor Connector SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 NTMOS SHIELD J3-4 SENSOR 1 B COM J3-5 1 A COM J3-6 NOTE 1 GREY AND ORANGE WIRES FOR FACTORY USE ONLY. Power Supply Connector NOTE 2 UD10 HOUSING MUST BE ELECTRICALLY...
The NTMOS sensor must be calibrated using 50 ppm H S in air (never use H S in nitrogen) . Det-Tronics provides two acceptable sources of 50 ppm H calibration gas for use with NTMOS sensors . WARNING FLEXVU UD10...
2 . Activate “Execute” (Enter/Select) to begin the zero calibration . 3 . The UD10-DCU will display “Waiting for Zero” on the main display screen . 4 . When zero calibration is complete (approximately one minute), the UD10-DCU will display “Waiting for Span” on the main display screen .
APPENDIX K UD10-DCU with C706X TOXIC GAS SENSOR NOTE For complete information regarding the C7064E H2S Gas Sensor, refer to instruction manual 95-8396. For the C7067E Chlorine Gas Sensor, refer to instruction manual 95-8439. WIRING UD10-DCU with GT3000/C706X 4000 3500 3000 Wire Size 2500...
Page 52
BLACK UD10 DISPLAY UNIT GREEN Sensor Connector SEE NOTE 1 SHIELD J3-1 2 B COM C706X SENSOR J3-2 2 A COM J3-3 SHIELD J3-4 1 B COM J3-5 1 A COM J3-6 NOTE 1 CONNECT THE GREEN SENSOR LEAD TO THE CHASSIS GROUND LUG ON THE INSIDE BOTTOM OF THE DISPLAY ENCLOSURE.
INSTALLATION INSTALLATION AND WIRING PROCEDURE 1 . Determine the best mounting locations for the detectors . WIRING REQUIREMENTS 2 . Install the C706X sensor within the proper opening in the UD10- The simplest installation involves installing the sensor into one of the DCU or STB junction box .
CALIBRATION MENU STRUCTURE To initiate calibration of the C706X sensor from the UD10-DCU UD10-DCU with C706X Series Sensor Display: Refer to the following menu when using the UD10-DCU’s LCD 1 . Using the magnet to activate the switches on the UD10-DCU display and internal magnetic switches .
APPENDIX L UD10-DCU with MODEL CGS COMBUSTIBLE GAS SENSOR WIRING UD10-DCU with PIRECL/OPECL/NTMOS/CGS 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet. Maximum recommended cable length from UD10 to CGS sensor is 500 feet (using 16 AWG, 1.5 mm2 cable minimum).
Page 56
SET ALL SWITCHES TO THE “ON” POSITION (FACTORY DEFAULT SETTING) CGS INTERFACE BOARD TERMINAL J11 FOR FACTORY USE ONLY LOCATED INSIDE UD10 HOUSING CONNECT TO UD10 MODULE VIA CABLE (FACTORY INSTALLED) CONNECT CGS SENSOR TO TERMINAL J10 CGS INTERFACE BOARD NOTE 1 REMOVE UD10 ELECTRONICS MODULE FOR ACCESS TO CGS INTERFACE BOARD (NO TOOLS REQUIRED).
INSTALLATION CALIBRATION NOTE WIRING REQUIREMENTS For maximum calibration accuracy, allow a new sensor to The simplest installation involves installing the sensor into one of the operate under power for several hours (minimum one hour) to UD10-DCU openings and connecting the wiring directly to the CGS ensure a stable output before performing calibration.
K FACTOR Determining Sensor Life Remaining At the time of calibration, the UD10-DCU logs the sensor mV signal . If the system will be detecting a gas/vapor other than the gas used in This value can be used for determining the approximate sensor life the actual calibration process, a conversion K-Factor must be used .
APPENDIX M UD10-DCU with MODEL 505 TRANSMITTER / CGS SENSOR NOTE For complete information regarding the Model 505 Transmitter, refer to instruction manual 95-8472. WIRING UD10-DCU with PIRECL/OPECL/NTMOS/CGS 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10 is 2000 feet.
Sensor Connector UD10 DISPLAY UNIT MODEL 505 TRANSMITTER SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 SHIELD J3-4 1 B COM J3-5 1 A COM J3-6 Power Supply Connector CONNECT KEYED SENSOR PLUG TO PIN CONNECTOR NOTES 1. SHIELDED SENSOR WIRING CABLE REQUIRED. 2.
CALIBRATION NOTE ZERO/SPAN SWITCH For maximum calibration accuracy, allow a new sensor ZERO ADJUST SENSOR VOLTAGE ADJUST to operate under power for several hours (minimum SPAN ADJUST one hour) to ensure a stable output before performing CAL/NORM SWITCH CALIBRATE LED calibration.
MENU STRUCTURE UD10-DCU with Model 505 / CGS Sensor Refer to the following menu when using the UD10-DCU’s LCD display and internal magnetic switches . MENU HELP Status menus only allow the user to view the data. The Setup menus allow the user to both view and edit the data. 95-8656...
APPENDIX N UD10-DCU with GENERIC 4-20 mA SENSORS NOTE For complete information regarding installation, wiring, and calibration of the sensor, refer to the instruction manual provided by the sensor manufacturer. OPERATION ALARMS The Low, High and Auxiliary alarm levels are independently field The UD10-DCU can be used with generic sensors that generate adjustable .
APPENDIX O UD10-DCU with FLEXSONIC ACOUSTIC GAS DETECTOR NOTE For complete information regarding the FlexSonic Acoustic Detector, refer to instruction manual 95-8657. WIRING UD10-DCU with FlexSonic Acoustic 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10-DCU is 2000 feet.
Page 65
ATX10 TRANSMITTER INTERFACE BOARD TO SOFTWARE CONFIGURATOR ORANGE GRAY BLACK SENSOR POWER GREEN AND OUTPUT Sensor Connector IS GROUND UD10-DCU DISPLAY UNIT SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 SHIELD AC100 J3-4 ACOUSTIC 1 B COM J3-5 SENSOR 1 A COM J3-6...
ALARM/FAULT STATUS ALARM MODE A L A RM BAS I C 59 DB ALARM LEVEL DATE AND TIME 09 N OV 2 01 5 08 :5 2 A2697 Figure 6-1—UD10-DCU Screen When Used with FlexSonic Acoustic Detector AUDIBLE RANGE 4X 30 BANDS = 120 BANDS ULTRASONIC RANGE 8X 3 BANDS = 24 BANDS MAXIMUM AMPLITUDE = 139 dB...
APPENDIX P UD10-DCU with MODEL PIRDUCT NOTE For complete information regarding the PIRDUCT Gas Detector, refer to instruction manual 95-8573. WIRING UD10-DCU with PIRDUCT 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10-DCU is 2000 feet. Maximum recommended cable length from UD10-DCU to PIR9400/PIRTB termination box is 2000 feet.
PIRTB JUNCTION BOX PIRDUCT DETECTOR UD10-DCU SEE NOTE 1 DISPLAY UNIT GREEN Sensor Connector SPARE CHASSIS YELLOW 4 – 20 4 – 20 WHITE BLACK SHIELD J3-1 2 B COM J3-2 2 A COM J3-3 SHIELD J3-4 1 B COM J3-5 1 A COM J3-6...
CHANGING OPERATING MODES UD10-DCU mA Output During Calibration (UD10 with PIR9400) When used with a PIRDUCT, the operating mode of the UD10-DCU must be changed from “HART Device” to “PIRDUCT” mode . Refer to Standard Replicate UD10-DCU Display Reading the “Startup” section of this manual for details . Mode Mode Waiting for Zero...
MENU STRUCTURE UD10-DCU with PIRDUCT Gas Detector Refer to the following menu when using the UD10-DCU’s LCD display and internal magnetic switches . MENU HELP Status menus only allow the user to view the data. The Setup menus allow the user to both view and edit the data. 95-8656...
APPENDIX Q UD10-DCU with MODEL PIRECL CARBON DIOXIDE DETECTOR NOTE For complete information regarding the PIRECL CO Gas Detector, refer to instruction manual 95-8676. WIRING UD10-DCU with PIRECL 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10-DCU is 2000 feet.
MODEL PIRECL BLACK 24 VDC – 24 VDC + CALIBRATE 24 VDC – 24 VDC + 4-20 MA + WHITE 4-20 MA – RS-485 B RS-485 A UD10-DCU RELAY POWER (RED) DISPLAY UNIT WIRING TO OPTIONAL FAULT (ORANGE) RELAY BOARD Sensor Connector NO USER CONNECTION LOW ALARM (WHITE)
CALIBRATION To initiate calibration from the PIRECL CO while monitoring calibration using the UD10-DCU display: To initiate calibration of the PIRECL CO from the UD10-DCU Display: Using the magnet, activate the magnetic calibration switch on the PIRECL CO detector . See Figure below . The LED turns Using the magnet to activate the switches on the UD10-DCU from green to red .
MENU STRUCTURE UD10-DCU with Model PIRECL CO Gas Detector Refer to the following menu when using the UD10-DCU’s LCD display and internal magnetic switches . MENU HELP Status menus only allow the user to view the data. The Setup menus allow the user to both view and edit the data. 95-8656...
APPENDIX R UD10-DCU with LS2000 LINE OF SIGHT GAS DETECTOR NOTE For complete information regarding the LS2000 Gas Detector, refer to instruction manual 95-8714. WIRING UD10-DCU with LS2000 4000 3500 3000 Wire Size 2500 2000 1500 1000 Power Supply Voltage Notes: Maximum recommended cable length from power source to UD10-DCU is 2000 feet.
Page 76
LS2000 RECEIVER WITHOUT RELAYS 0V COM SPARE +24 VDC 0V COM 0V COM +24 VDC SHIELD SHIELD INTR B INTR A INTR GND SHIELD SHIELD RS-485 A RS-485 B –mA HART UD10-DCU DISPLAY UNIT Sensor Connector SHIELD J3-1 2 B COM J3-2 2 A COM J3-3...
INSTALLATION CALIBRATION LS2000 modules must be affixed to a solid, non-vibrating structure To initiate zero calibration of the LS2000 from the UD10-DCU capable of supporting a minimum of 100 lbs (46 kg), located within Display: the system’s rated separation distance . See examples below . 1 .
MENU STRUCTURE To initiate zero calibration from the LS2000: 1 . Using the magnet, activate the magnetic calibration switch on the UD10 with LS2000 Line of Sight Gas Detector LS2000 receiver . See Figure below . The green LED will turn red . Refer to the following menu when using the UD10-DCU’s LCD display and internal magnetic switches .
Need help?
Do you have a question about the UD10 DCU Emulator and is the answer not in the manual?
Questions and answers