Safety Instructions Congratulations for choosing a product from CG Drives & Precautions to be taken with a Automation! connected motor Before you begin with installation, commissioning or If work must be carried out on a connected motor or on the...
IT Mains supply The AC drives can be modified for an IT mains supply, (non-earthed neutral), please contact your supplier for details. Alarms Never disregard an alarm. Always check and remedy the cause of an alarm. CG Drives & Automation 01-7492-01r0...
EMC and standards........71 Control board............47 EMC standards............71 Terminal connections ..........48 Stop categories and emergency stop ....71 4.2.1 Stand by supply interface (SBS)......49 Configuration with jumpers and switches ..... 49 CG Drives & Automation 01-7492-01r0...
Page 8
Top cover for IP20/21 version ......204 11.5 I/Os and Virtual Connections [500]..... 150 13.18 Other options............204 11.5.1 Analogue Inputs [510] .......... 150 13.19 AFE - Active Front End........... 204 11.5.2 Digital Inputs [520] ..........155 CG Drives & Automation 01-7492-01r0...
Page 9
Dimensions and Weights........215 14.5 Environmental conditions........218 14.6 Fuses and glands ..........219 14.6.1 According to IEC ratings........219 14.6.2 Fuses according to NEMA ratings ......223 14.7 Control signals............224 Menu List............ 225 Index ............249 CG Drives & Automation 01-7492-01r0...
AFE- Active Front End AFE- Active front end option, Instruction manual The Quick Setup Card can be put in a cabinet door, so that / 01-5386-01 it is always easy to access in case of an emergency. CG Drives & Automation 01-7492-01r0 Introduction...
The warranty applies when the equipment is installed, operated and maintained according to instructions in this instruction manual. Duration of warranty as per contract. Faults that arise due to faulty installation or operation are not covered by the warranty. Introduction CG Drives & Automation 01-7492-01r0...
EN(IEC) 61800-3:2004 (Any kind of metal screened cable may be used). The standard AC drive is designed to meet the requirements according to category C3, for a motor cable length of maximum 80 m. Introduction CG Drives & Automation 01-7492-01r0...
The recycling of materials will help to conserve natural resources. For more detailed information about recycling this product, please contact the local distributor of the product. CG Drives & Automation 01-7492-01r0 Introduction...
Nominal torque of motor Motor torque Output frequency of AC drive Nominal frequency of motor Nominal speed of motor Maximum output current Speed Actual motor speed Torque Actual motor torque Sync Synchronous speed of the motor speed Introduction CG Drives & Automation 01-7492-01r0...
50 (1.97) mm (in) 50 (1.97) NOTE: When a 300 to 3K0 model is placed between two walls, a minimum distance at each side of 200 mm (7.9 in) must be maintained. Mounting CG Drives & Automation 01-7492-01r0...
7200 (4238) 8000 (4709) 8800 (5179) 9600 (5650) 10400 (6121) 11200 (6592) 12000 (7063) NOTE: For the models 48-860/69-650 to 69-3K0 the mentioned amount of air flow should be divided equally over the cabinets. Mounting CG Drives & Automation 01-7492-01r0...
• Swing out the lower part of the cover a bit and remove the cover downwards. Be careful, don't swing out the cover too much as this could damage the “lips” at the upper hinges. Now it is easy to access all terminals. CG Drives & Automation 01-7492-01r0 Installation...
Connect the mains cables according to fig. 31 to 39. The AC drive has as standard a built-in RFI mains filter that complies with category C3 which suits the Second Environment standard. Installation CG Drives & Automation 01-7492-01r0...
Page 31
D and model 69-033 to 69-058 frame size D69. L1 L2 L3 DC- DC+ R EMC gland - s creen connection of motor cables Fig. 33 Mains and motor connections, model 002-025, frame size C69. CG Drives & Automation 01-7492-01r0 Installation...
Page 32
Fig. 37 Mains and motor connections model 48-142 to 48- 293 (frame sizes E2 and F2) (principle drawing). Fig. 39 Mains and motor connections model 48-365-20 (frame size FA2) with the optional terminals for DC-, DC+ and Brake (principle drawing). Installation CG Drives & Automation 01-7492-01r0...
Connect the motor cables according to U - U, V - V and W - W, see fig. 31, to fig. 39. NOTE: The terminals DC-, DC+ and R are options. CG Drives & Automation 01-7492-01r0 Installation...
Page 34
Screened cables Fig. 41 Screen connection of cables.. Unpainted mounting plate Metal connector housing Mains Metal EMC Motor (L1,L2,L3,PE) coupling nut Brake resistor (option) Fig. 42 AC drive in a cabinet on a mounting plate. Installation CG Drives & Automation 01-7492-01r0...
Page 35
“circuit” closed, by using metal housing and (330 ft)(for powers below 7.5 kW (10.2 hp)) please contact cable glands. CG Drives & Automation), it is possible that capacitive current peaks will cause tripping at overcurrent. Using output coils can prevent this. Contact the supplier for appropriate coils.
5. Fix the clamps on appropriate place and tighten the cable in the clamp with good electrical contact to the cable screen. 6. Put the cable interface plate in place and secure with the fixing screws. Fig. 46 Removed upper mounting rail. Installation CG Drives & Automation 01-7492-01r0...
Page 37
7. Put the cable interface plate in place and secure with the fixing screws. Fig. 48 All cables and cable clamps connected. CG Drives & Automation 01-7492-01r0 Installation...
Ground via the mounting screws. Make sure that these will have good contact to the grounded mounting plate/ cabinet wall. For detailed information about use of the IP20 modules, please contact CG Drives & Automation. PEBB 1 PEBB 2 (Master)
Page 39
PEBB 3 PEBB 2 (Master) Mains cables Motor cables L1, L2, L3 U, V, W Fig. 52 IP20 module sizes I/I69 with qty 3 x 3 Mains cables and qty 3 x 3 motor cables. CG Drives & Automation 01-7492-01r0 Installation...
16-34 mm 16-34 mm 16- 150 48-090-54 42 (for 16- 150 16 - 120 42 (for 42 (for 35-150 mm 48-109-54 35-120 35-150 mm 16 - 185 ** 48-146-54 ***** ***** 10 ** 48-175-54 CG Drives & Automation 01-7492-01r0 Installation...
Page 44
*** Use 90 °C Mains and motor cables if surrounding temperature is higher than 35 °C otherwise 75 °C cables. **** IP 23 or IP 54 for cabinet drive. ***** Cable lug tightening torque = 20 Nm, when terminal lug removed. Installation CG Drives & Automation 01-7492-01r0...
Page 48
* With cable lug for M6 screw. ** Valid when brake chopper electronics are built in. °C Mains and motor cables if surrounding temperature is higher than 35 °C otherwise 75 °C cables. *** Use 90 Installation CG Drives & Automation 01-7492-01r0...
Add the current for the motors in parallel. Motor Current: Menu [225] Set the average speed for the motors in Motor Speed: parallel. Menu [227] Set the average Cos PHI value for the Motor Cos PHI: motors in parallel. CG Drives & Automation 01-7492-01r0 Installation...
AnIn 3 connecting all 230VAC signals to the control board relay terminals 31 - 52. AnIn 4 Analogue outputs AnOut 1 Min speed to max speed AnOut 2 0 to max torque Control Connections CG Drives & Automation 01-7492-01r0...
See menus [512], [515], [518] and [51B] in section 11.5, page 150. NOTE: the 2 analogue outputs AnOut 1 and AnOut 2 can be configured using the software. See menu [530] section 11.5.3, page 157 CG Drives & Automation 01-7492-01r0 Control Connections...
It is important not to enable any additional termination apart from the two in each cable end as it will impose as an additional load for a transmitting transceiver and may cause malfunctioning. Control Connections CG Drives & Automation 01-7492-01r0...
1 kΩ / ¼ W type potentiometer for best control linearity. *** Optional terminals X1: 78 - 79 for connection of Motor-PTC on frame sizes B, C and D. Fig. 57 Connection example. CG Drives & Automation 01-7492-01r0 Control Connections...
Fig. 58 Connecting the control signals, VFX model 003 to 018, frame size B. Fig. 60 Connecting the control signals, VFX model 48-025 to 48-058 frame size C2 and model 69-002 to 69-025 frame size C2(69). Control Connections CG Drives & Automation 01-7492-01r0...
Page 57
Fig. 62 Connecting the control signals, VFX model 48-060 to 48-105 frame size D2 and model 69-033 to 69-058 frame size D2(69). Fig. 64 Connecting the control signals, VFX model 48-142 to 48-365 frame size E2, F2 and FA2 (principle drawing). CG Drives & Automation 01-7492-01r0 Control Connections...
For a PLC it is therefore important that the return wire remains in proximity to the signal wire. It is important that the pair of wires is fully twisted over 360°. CG Drives & Automation 01-7492-01r0 Control Connections...
Page 60
Control Connections CG Drives & Automation 01-7492-01r0...
Mains supply, 3 -phase Safety earth Motor earth Motor output, 3-phase U, V, W WARNING! In order to work safely the mains earth must be connected to PE and the motor earth to CG Drives & Automation 01-7492-01r0 Getting Started...
Fig. 68 Wiring. 5.3.2 Switch on the mains Once the mains is switched on, the internal fan in the AC drive will run for 5 seconds (In frame size A3 the fan runs continuously). Getting Started CG Drives & Automation 01-7492-01r0...
We select a low value to check the rotation direction without damaging the application. 5.4.5 Run the AC drive Press the key on the control panel to run the motor forward. If the motor is running the main connections are OK. CG Drives & Automation 01-7492-01r0 Getting Started...
Page 64
Getting Started CG Drives & Automation 01-7492-01r0...
Applications This chapter contains tables giving an overview of many different applications/duties in which it is suitable to use AC drives from CG Drives & Automation. Further on you will find application examples of the most common applications and solutions.
Process inefficiency due to e.g. a damaged or Load Curve Protection quickly detects deviation. broken blade. Energy wasted and risk of process 411–41B, 41C1 –41C9 Warning is sent or safety stop activated. failure. Applications CG Drives & Automation 01-7492-01r0...
Set Ctrl 1 or Set Ctrl 2. NOTE: The selection via the digital inputs is immediately activated. The new parameter settings will be activated on-line, also during Run. NOTE: The default parameter set is parameter set A. CG Drives & Automation 01-7492-01r0 Main Features...
• Set relay 1, menu [550] to “AutoRst Trip”; a signal will be available when the maximum number of restarts is reached and the AC drive stays in fault condition. • The reset input must be constantly activated. Main Features CG Drives & Automation 01-7492-01r0...
• 300 rpm, when DigIn 5 is low and DigIn 6 is high. commands are only able to start the AC drive. • 800 rpm, when both DigIn 5 and DigIn 6 are high. CG Drives & Automation 01-7492-01r0 Main Features...
Page 70
If both RunR and RunL inputs are active, then the AC drive stops according to the selected Stop Mode. Fig. 73 gives an example of a possible sequence. Main Features CG Drives & Automation 01-7492-01r0...
Page 71
See fig. 72. The Enable and Stop input must be active continuously in order to accept any run-right or run-left command. The last edge (RunR or RunL) is valid. fig. 74 gives an example of a possible sequence. CG Drives & Automation 01-7492-01r0 Main Features...
NOTE: Load from and copy to the AC drive is only possible when the AC drive is in stop mode. AC drive Fig. 75 Copy and load parameters between AC drive and control panel. Main Features CG Drives & Automation 01-7492-01r0...
The autoset function automatically sets the 4 alarm levels whilst running: maximum alarm, maximum pre-alarm, minimum alarm and minimum pre-alarm. Fig. 76 gives an example of the monitor functions for constant torque applications. CG Drives & Automation 01-7492-01r0 Main Features...
Page 74
Fig. 76 Main Features CG Drives & Automation 01-7492-01r0...
NOTE: With option Safe Stop, a “Safe Torque Off (STO)” stop according EN-IEC 62061:2005 SIL 3 & EN-ISO 13849-1:2006, can be achieved. See section 13.13 page 204 CG Drives & Automation 01-7492-01r0 EMC and standards...
Page 76
EMC and standards CG Drives & Automation 01-7492-01r0...
For example parameter 43123 in parameter set communication option boards. A contain the same type of information as 44123 in parameter set B. NOTE: This RS 232 port is not isolated. CG Drives & Automation 01-7492-01r0 Communication...
3” to 42906. NOTE! It is possible to view the transmitted process value in control panel menu Operation [710]. The presented value is depending on settings in menus “Process Min [324]” and “Process Max [325]”. Communication CG Drives & Automation 01-7492-01r0...
4-bit signed exponent. Gives a value range: format (F=0). -8..+7 (binary 1000 .. 0111) m10-m0 11-bit signed mantissa.Gives a value range: -1024..+1023 (binary 10000000000..01111111111) A signed number should be represented as a two complement binary number, like below: CG Drives & Automation 01-7492-01r0 Communication...
Page 80
// round etmp.m=etmp.m*value; // make signed Rreturn (*(unsigned short int *)&etmp); //--------------------------------------------------------------------------- float eint16_to_float(unsigned short int value) float f; eint16 evalue; evalue=*(eint16 *)&value; if (evalue.f) if (evalue.e>=0) f=(int)evalue.m*pow10(evalue.e); else f=(int)evalue.m/pow10(abs(evalue.e)); else f=value; return f; //--------------------------------------------------------------------------- Communication CG Drives & Automation 01-7492-01r0...
Area C: Edit Cursor if editing or heading in menu [100], 8 characters field. Area D *: Shows the status of the AC drive (3 digits). The following status indications are possible: CG Drives & Automation 01-7492-01r0 Operation via the Control Panel...
Page 82
Area K: First row character 7 show an inverted B in case a Bluetooth connection is active. Area L: First row character 8 show a WiFi symbol in case a WiFi connection is active. Operation via the Control Panel CG Drives & Automation 01-7492-01r0...
During editing, preferred view will not be displayed and the cursor will appear blinking to the left. See also below. Preferred view is not shown during editing. Language = blinking during editing English Loc/Loc CG Drives & Automation 01-7492-01r0 Operation via the Control Panel...
(terminals 1-22). Exception is the JOG-function which can give start Weekday [933] command, see Jog Speed [348] on page 127. Display of actual weekday, read only. 1240rpm Weekday Monday Key/Key Operation via the Control Panel CG Drives & Automation 01-7492-01r0...
AC drive will not change, e.g. Run/Stop conditions and the actual speed will remain exactly the same. When the AC drive is set to Local operation, the display will show in area B in the display. CG Drives & Automation 01-7492-01r0 Operation via the Control Panel...
Fig. 82 Menu structure. Toggle between menus in the toggle loop TOGGLE and Switching between LOC/REM local and remote key: control Change the sign of a value Operation via the Control Panel CG Drives & Automation 01-7492-01r0...
Example: When you press Next the 4 will flash. 0rpm Acc Time 10.0s Flashing Key/Key Press Enter to save the setting and Esc to leave the edit mode. CG Drives & Automation 01-7492-01r0 Operation via the Control Panel...
Press “Next” key for menu [300]. Fig. 83 Programming example 0rpm Process Key/Key Press “Enter” key for menu [310]. 0rpm Set/View ref 0rpm Key/Key Press “Next” key twice for menu [330]. Operation via the Control Panel CG Drives & Automation 01-7492-01r0...
5. Available settings for the menu, listed selections. 6. Communication integer value for the selection. For use with communication bus interface (only if selection type parameters). 7. Description of selection alternative, setting or range (min - max value). CG Drives & Automation 01-7492-01r0 Functional description...
Extended signal monitoring as set in Always 100+ menus 110 - 160 ** Can only be selected if Encoder option board is installed. As Normal 100 without text at second Normal 100wo and third lines. Functional description CG Drives & Automation 01-7492-01r0...
• V/Hz Mode (output speed [712] in rpm) is used when several motors in parallel of different type or size are con- nected or if parallel motors are not mechanically con- nected to the load CG Drives & Automation 01-7492-01r0 Functional description...
"V/Hz (VFX)" mode. monitor the communication between the AC drive and the controlling equipment. See the following menus for more information: Keyboard [2645] and [2646] Communication: RS-485 [262], Fieldbus [263], Wireless [270] Functional description CG Drives & Automation 01-7492-01r0...
Page 93
(terminals 1-22), the Default: +Com keyboard or the wireless communication (RS485, Fieldbus). Range: 0–9999 The command comes from an option. Option Only available if the option can control the reset command. CG Drives & Automation 01-7492-01r0 Functional description...
Load Default command [243]. Brake chopper activation level is adjusted using the setting of [21B]. NOTE: The setting is affected by the “Load from CP” command [245] and if loading parameter file via EmoSoftCom. Functional description CG Drives & Automation 01-7492-01r0...
Default: 500 V for VFX52 690 V forVFX 69 Range: 100-700 V Resolution NOTE: The Motor Volts value will always be stored as a 3 digit value with a resolution of 1 V. CG Drives & Automation 01-7492-01r0 Functional description...
Page 96
) A (see Note 2 page 91) Set the nominal Motor cosphi (power factor). Range: 25 - 150% x I Motor Cos ϕ ϕ Default: (see Note 2 page 91) Range: 0.45 - 1.00 Functional description CG Drives & Automation 01-7492-01r0...
Page 97
NOTE: If the ID Run is aborted or not completed the message “Interrupted!” will be displayed. The previous data do not need to be changed in this case. Check that the motor data are correct. CG Drives & Automation 01-7492-01r0 Functional description...
Page 98
(2 kHz for models 48-293/295 and 48-365) Range 1.50 - 6.00kHz * Resolution 0.01kHz * Maximum is 8 kHz if [222] Motor freq > 400 Hz and if < 400 Hz max remains at 6 kHz. Functional description CG Drives & Automation 01-7492-01r0...
Page 99
“Deviation 2” trip message with ID = 2. Encoder fault delay time [22G1] Define the encoder fault and speed deviation delay time. 22G1 Enc F Delay Default: Range Off, 0.01 - 10.00 s where Off = 0 CG Drives & Automation 01-7492-01r0 Functional description...
Page 100
Synchronous Motor and Synchronous Reluctance Motors.If 22J1 BEMF Motor Type Default: Motor dependent (V) Default: Async Range: 100-700 V Async Asynchronous motor Resolution PMSM Permanent magnet synchronous motor Sync Rel Synchronous Reluctance motor Functional description CG Drives & Automation 01-7492-01r0...
A minimum allowed speed can be set in menu [238] NOTE: When Mot I2t Type=Limit, the AC drive can control the speed < MinSpeed to reduce the motor current. CG Drives & Automation 01-7492-01r0 Functional description...
Page 102
1.2 times of 100% nominal motor current. NOTE: If it is not possible to reduce the current, the AC drive will trip after exceeding 110% of the limit. Functional description CG Drives & Automation 01-7492-01r0...
Page 103
Channel 1 - 5 used for PT100 PT100 1-5 protection Channel 1 - 6 used for PT100 PT100 1-6 protection NOTE: This menu is only active if PT100 is enabled in menu [234]. CG Drives & Automation 01-7492-01r0 Functional description...
[721] VSD status. NOTE: Parameter set cannot be changed during run if the parameter set includes change of the motor set (M2-M4). In this case always stop the motor before changing parameter set. Functional description CG Drives & Automation 01-7492-01r0...
Page 105
A>B means that the content of parameter set A is copied into parameter set B. NOTE: The parameters in menu “[220] Motor data”, are not affected by loading defaults when restoring parameter sets A–D. CG Drives & Automation 01-7492-01r0 Functional description...
Page 106
M1M2M3 Data from motor 1, 2, 3 and 4 are loaded. All data is loaded from the control panel. NOTE: Loading from the control panel will not affect the value in menu [310]. Functional description CG Drives & Automation 01-7492-01r0...
5 attempts to autoreset a trip. 1–3600 1–3600 1–3600 s • To reset the autoreset counter, de-activate the always high remote-reset input and then activate it again. • The autoreset counter is now zeroed. CG Drives & Automation 01-7492-01r0 Functional description...
Page 108
Delay time starts counting when the fault is gone. When the time delay has elapsed, the alarm will be reset if the function 1–3600 1–3600 1–3600 s is active. PT100 TT Default: Trip Selection: Same as menu [25B] Functional description CG Drives & Automation 01-7492-01r0...
Page 109
Select the preferred way to react to a max alarm trip. is active. Max Alarm TT Com Error Default: Trip Default: Selection: Same as menu [25B] 1–3600 1–3600 1–3600 s CG Drives & Automation 01-7492-01r0 Functional description...
Page 110
1- 3600 1- 3600 s 1–3600 1–3600 1–3600 s External Motor Trip Type [25S] Select the preferred way to react to an alarm trip. Ext Mot TT Default: Trip Selection: Same as menu [25B] Functional description CG Drives & Automation 01-7492-01r0...
Fieldbus EtherCAT or EtherNet/IP). Integrated RS485 interface enabled (can be used in parallel to fieldbus option). NOTE: Toggling the setting in this menu will perform a soft reset (re-boot) of the Fieldbus module. CG Drives & Automation 01-7492-01r0 Functional description...
Page 112
CANopen, Profibus, DeviceNet. Read - only for EtherCAT. 2631 Address Default: CANopen 1-127, Profibus 0–126, Range: DeviceNet 0–63 Node address valid for CANopen (RW), Profibus(RW), DeviceNet (RW) and EtherCAT (RO). Functional description CG Drives & Automation 01-7492-01r0...
The AC drive will give a warning if there is Warning no communication for time set in parameter [2644]. NOTE: Menu [214] and/or [215] must be set to COM to activate the communication fault function. CG Drives & Automation 01-7492-01r0 Functional description...
Page 114
An unique number for the Ethernet Default: the communication command registers: module. - Run (2 or 42902) Subnet Mask [2653] - RunR (3 or 42903) - RunL (4 or 42904) 2653 Subnet Mask - Reference (42905) Default: 0.0.0.0 Functional description CG Drives & Automation 01-7492-01r0...
Configure WiFi interface to connect to an existing WiFi network provided by an external Router/AP. Remaining WiFi Station parameters [272X] will be used to select the network to connect to and to provide the required credentials. CG Drives & Automation 01-7492-01r0 Functional description...
Page 116
SSID [2725] First 16 chars of network name to connect to if "[2721]WiFi Mode" = Station or SSID network name to broadcast if "[2721] WiFi Mode = AccessPoint. 2725 SSID Default Emotron_<5 random digits> Functional description CG Drives & Automation 01-7492-01r0...
Page 117
NOTE: Default is 0 or if a BLE control panel is used an eight digit unique ID used in the broadcast name. Paring key [2732] Six digit numeric for the control panel BLE pairing with mobile or other BLE device. 2732 Paring Key Default 123456 CG Drives & Automation 01-7492-01r0 Functional description...
“Dec Time [332]”. NOTE: Write access to this parameter is only allowed when menu “Ref Control [214]” is set to Keyboard. When Reference control is used, see chapter 9. Communication on page 73. Functional description CG Drives & Automation 01-7492-01r0...
. Only when Drive mode [213] is set to Speed or V/Hz. . Only when Drive mode [213] is set to Torque. NOTE: When PT100 is selected, use PT100 channel 1 on the PTC/PT100 option board. CG Drives & Automation 01-7492-01r0 Functional description...
¨ Process Min [324] Ü This function sets the minimum process value allowed. Process Min & Default: · 0.000-10000 (Speed, Torque, F(Speed), Range: F(Torque)) -10000– +10000 (F(AnIn, PT100, F(Bus)) Å Ä Ö á Functional description CG Drives & Automation 01-7492-01r0...
Page 121
NOTE: If Speed, Torque or Frequency is chosen in menu “[321] Proc Source”, menus [322]- [328] are hidden. Ratio=Linear F(Val) PrMax Default: Ratio=Quadratic Process Speed [324] Speed Speed 0.000- 0-10000 0.000-10000 [341] [343] 10000 Fig. 88 Ratio. CG Drives & Automation 01-7492-01r0 Functional description...
Fig. 91 shows the settings of the acceleration and deceleration times with respect to the nominal motor speed. Nom. Speed Acc Time [331] Dec Time [332] (NG_06-F11) Fig. 91 Acceleration and deceleration times. Functional description CG Drives & Automation 01-7492-01r0...
Page 123
Minimum speed [341] = 600 rpm in 8 seconds according to ramp time parameter Acc>Min speed [335]. Calculated as following: 600 rpm is 20% of 3000 rpm => 20% of 40 s = 8 s. CG Drives & Automation 01-7492-01r0 Functional description...
Page 124
0 –sync speed take 2 x Time while a step from 0–2 x sync speed will take 3 x Time (middle part 0.5sync speed – 1.5sync speed linear). Also valid for menu [338], Deceleration ramp type. Functional description CG Drives & Automation 01-7492-01r0...
Page 125
Only encoder speed used for detecting rotating machine, i.e. no rotating machine detection via initial motor current. Encoder 2 Note: Only active if encoder is present. If no Encoder, functionality is equal to selection Off. CG Drives & Automation 01-7492-01r0 Functional description...
Engage time [33E] then a Brake warning is generated and the torque is kept, i.e. prolonging normal brake engage mode, until brake closes or an emergency action is needed by the operator, such as setting down the load. Functional description CG Drives & Automation 01-7492-01r0...
Page 127
NOTE: Although this function is designed to operate a mechanical brake via the digital outputs or relays (set to brake function) controlling a mechanical brake, it can also be used without a mechanical brake and hold the load in a fixed position. CG Drives & Automation 01-7492-01r0 Functional description...
Page 128
Release Speed [33D]. Vector Brake Default: Vector brake switched off. AC drive brakes normal with voltage limit on the DC link. Maximum AC drive current (I ) is available for braking. Functional description CG Drives & Automation 01-7492-01r0...
Page 129
Start Vector 33J2 DC Hold Spd Default: Default: 10rpm Normal (U) 0 U-phase Range: 0 - 250 rpm Sequence Sequentially select different vectors Encoder Based on encoder position CG Drives & Automation 01-7492-01r0 Functional description...
“Min Speed [341]” to make it possible that the analogue input reference can go below the "Min Speed" level to activate the “Sleep mode”. This applies when PID Process controller is not used Functional description CG Drives & Automation 01-7492-01r0...
Page 131
Skip Speed 1 High [345] Skipspd1 HI sets the higher value for the 1st skip range. SkipSpd 1 Hi Default: 0 rpm Freq Range: 0 – 4 x Sync Speed com- mand (NG_06-F18) Fig. 99 Jog command. CG Drives & Automation 01-7492-01r0 Functional description...
IxR Compensation value can be set in the menu [353]. NOTE: This menu is visible only in V/Hz mode. IxR Comp Default: Function disabled Automatic Automatic compensation User Defined 2 User defined value in percent. Functional description CG Drives & Automation 01-7492-01r0...
Page 133
Therefore it is important that the Motor I t Current [232] is set correctly. Flux optimizing area Fig. 101 Flux Optimizing NOTE: Flux optimization works best at stable situations in slow changing processes. CG Drives & Automation 01-7492-01r0 Functional description...
[355] is limited by I x 120%, but not higher Non volatile 1 memorized. After a new start command than 400%. the output speed will resume to this saved value. Motpot Motpot DOWN Fig. 102 MotPot function. Functional description CG Drives & Automation 01-7492-01r0...
Page 135
NOTE: If only Preset Ctrl3 is active, then the Preset Ref 4 can be selected. If Presets Ctrl2 and 3 are active, then the Preset Ref 2, 4 and 6 can be selected. CG Drives & Automation 01-7492-01r0 Functional description...
NOTE: RUN command must be activated manually via Keyboard button. NOTE: The setting will automatically return to Off when the autotuning is finished. NOTE: This menu is only visible if AC drive Mode = Speed or V/Hz. Functional description CG Drives & Automation 01-7492-01r0...
NOTE: Menu [386] has higher priority than menu Process [342]. feedback Process 06-F95 Fig. 103 Closed loop PID control. PID I Time [384] Setting the integration time for the PID controller. PID I Time Default: 1.00 s Range: 0.01–300 s CG Drives & Automation 01-7492-01r0 Functional description...
Page 138
Min Speed for 30 seconds. The AC drive will activate/wake up when the “Process value” goes above the PID Activation Margin which is related to the process reference, i.e. goes above (7+1) m. See fig. 105. Functional description CG Drives & Automation 01-7492-01r0...
Page 139
[389] time [388] [387] Stop steady Start steady state test state test [712] Speed Normal PID Normal PID Steady state test Stop/Sleep [341] Min Speed [386] PID<Min Spd Fig. 106 Steady state test. CG Drives & Automation 01-7492-01r0 Functional description...
Number of drives if 'Fixed MASTER' is used, see Select Drive [393]. (I/O Board is used.) NOTE: Used relays must be defined as Slave Pump or Master Pump. Used digital inputs must be defined as Pump Feedback. Functional description CG Drives & Automation 01-7492-01r0...
Page 141
- Stop - Standby condition. - Trip condition. NOTE: If the Status feedback inputs (DigIn 9 to Digin 14) are used, the master drive will be changed immediately if the feedback generates an 'Error'. CG Drives & Automation 01-7492-01r0 Functional description...
Page 142
“Stop Delay [39A]”. stopped. A delay time prevents the nervous switching of pumps. Lower Band Stop Delay Default: Range: 0-100% of total min speed to max speed Default: Range: 0-999 s Functional description CG Drives & Automation 01-7492-01r0...
Page 143
During the Settle start: • PID controller is off. • The speed is kept at a fixed level after adding a pump. Settle Start Default: Range: 0-999 s CG Drives & Automation 01-7492-01r0 Functional description...
Page 144
Switch on Speed procedure starts Actual Additional pump Trans Master pump Flow/Pressure Actual start command of next pump (RELAY) (NG_50-PC-16_1) Fig. 111 Transition speed start Functional description CG Drives & Automation 01-7492-01r0...
Page 145
Actual shut down of pump pumps indicate fault or are shut off for maintenance. Master pump No of Backup Default: Trans Range: Actual Additional pump Flow/Pressure Switch off procedure starts Fig. 113 Transition speed stop CG Drives & Automation 01-7492-01r0 Functional description...
Crane Relay CR1 on the Crane option board is fixed to the NOTE: Speed signal is limited to < 32767. No Trip function. Crane Relay1 Default: No Trip Selections Fixed to No Trip Functional description CG Drives & Automation 01-7492-01r0...
Page 147
Crane option board is active. Dev Time Speed 3 Default: 0.10 s Default: Range: 0.05 – 1 s Range: 0 – 4 x Motor Sync speed NOTE: Speed signal is limited to < 32767. CG Drives & Automation 01-7492-01r0 Functional description...
Page 148
N input used for Brake Brk Ackn Acknowledge. See page 122. Note: Brake Acknowledge via Crane I/O has priority (and overrules) Brake acknowledge via control board I/O ([521 DigIn1] - [528 Dig In8]). Functional description CG Drives & Automation 01-7492-01r0...
Max Alarm Basic Ramp Alarm Min Alarm Default: (Pre) alarms are inhibited during Load curve acceleration/deceleration. (Pre) alarms active during acceleration/ Speed deceleration. Fig. 114 Basic load type and Load curve. CG Drives & Automation 01-7492-01r0...
Page 150
Load Curve [41C], that does not generate an alarm. The Max Alarm Margin is a percentage of nominal motor torque. In case of Load Curve R, the margin is percentage of Load curve torque at the actual speed. 4161 MaxAlarmMar Default: Range: 0–400% CG Drives & Automation 01-7492-01r0...
Page 151
[41B] - [4191] Range: 0-400% These default set levels can be manually changed in menus [416] to [419]. After execution the message “Autoset OK!” is displayed for 1s and the selection reverts to “No”. CG Drives & Automation 01-7492-01r0...
Page 152
0 - 31 % Range: 0–400% of max torque NOTE: Speed signals are limited to < 32767. NOTE: The speed values depend on the Min- and Max Speed values. they are read only and cannot be changed. CG Drives & Automation 01-7492-01r0...
NOTE: LVO and OVC are not active in torque mode. OverVolt Ctl Default: Overvoltage control activated Overvoltage control off NOTE: LVO and OVC are not active in torque mode. CG Drives & Automation 01-7492-01r0...
[5168] AnIn2 Operation = Sub- [515] AnIn2 Setup = 4-20 mA [5164] AnIn2 Function Min = Min (0 rpm) [5166] AnIn2 Function Max = User defined [5167] AnIn2 Value Max = 300 rpm [5168] AnIn2 Operation = Add+ CG Drives & Automation 01-7492-01r0...
Page 155
AnIn Min and AnIn Max menus. Sets the input for a bipolar voltage input, User where the scale controls the range for the Bipol V input signal. Scale can be defined in advanced menu AnIn Bipol. CG Drives & Automation 01-7492-01r0...
Page 156
(NG_06-F25) With AnIn1 Function ValMin you define a user-defined Fig. 121 Inverted reference value for the signal. Only visible when user-defined is selected in menu [5134]. 5135 AnIn1 VaMin Default: 0.000 Range: -10000.000 – 10000.000 CG Drives & Automation 01-7492-01r0...
Page 157
AnIn1 is only active if the digital input is DigIn high. AnIn1 Operation [5138] 5138 AnIn1 Oper Default: Add+ Analogue signal is added to selected Add+ function in menu Analogue signal is subtracted from Sub- selected function in menu CG Drives & Automation 01-7492-01r0...
Page 158
AnIn4 Advan AnIn3 Fc Default: Selection: Same as in menu AnIn3 Setup [518] Same functions as “AnIn1 Setup [512]”. AnIn3 Setup Default: 4–20 mA Dependent on Setting of switch S3 Selection: Same as in menu CG Drives & Automation 01-7492-01r0...
Liquid cooling low level signal. clockwise rotary field. LC Level NOTE: The Liquid Cooling Level is active Run Left command (negative speed). The low. RunL output of the AC drive will be a counter-clockwise rotary field. CG Drives & Automation 01-7492-01r0...
Page 160
Same function as “DigIn 1[521]”. Default function for DigIn 8 is Reset. For DigIn 3 to 7 the default function is Off. DigIn 2 Default: RunR Selection: Same as in menu DigIn 1 Additional digital inputs [529] to CG Drives & Automation 01-7492-01r0...
NOTE: When selections AnIn1, AnIn2 …. AnIn4 is selected, the setup of the AnOut (menu [532] or [535]) has to be set to 0-10V or 0-20mA. When the AnOut Setup is set to e.g. 4-20mA, the mirroring is not working correct. CG Drives & Automation 01-7492-01r0...
Page 162
AnOut functionMin [5334] to “User-defined” and AnOut1 VaMin[5335] = 0.0. This results in an anlogue output signal from 0/4 mA to 20mA: 0Hz to Fmot. This principle is valid for all Min to Max settings. CG Drives & Automation 01-7492-01r0...
Page 163
Only visible when user-defined is selected in menu [5334]. 5337 AnOut1VaMax Default: 0.000 Range: -10000.000–10000.000 AnOut2 Function [534] Sets the function for the Analogue Output 2. AnOut2 Fc Default: Torque Selection: Same as in menu CG Drives & Automation 01-7492-01r0...
All Pumps All pumps are running The max or min pre alarm level has Pre Alarm Only Master Only the master is running been reached. Local/Rem mode indication Loc/Rem Local = 1, Remote = 0 CG Drives & Automation 01-7492-01r0...
Page 165
Failure occurred in built-in option Option board. NOT1 NOT gate 1 output NOT2 NOT gate 2 output NOT3 NOT gate 3 output NOT4 NOT gate 4 output NOT5 NOT gate 5 output CG Drives & Automation 01-7492-01r0...
1–3 is the number of the board which is related to the position of the I/O option board on the option mounting plate. See menu DigOut 1 [ NOTE: Visible only if optional board is detected or if any input/output is activated. CG Drives & Automation 01-7492-01r0...
See DigOut 1 for description of the different selections. VIO 1 Source Default: Selection: Same as for menu [541]. Virtual Connections 2-8 [563] to [56G] Same function as virtual connection 1 [561] and [562]. CG Drives & Automation 01-7492-01r0...
Page 168
[322] Process Err Fig. 125 Analogue comparator type “Window” PT100_4 °C The output signal can be programmed as a virtual PT100_5 °C connection source and to the digital or relay outputs. PT100_6 °C AnMux1 AnMux2 CG Drives & Automation 01-7492-01r0...
Page 169
The reference signal passes the Level HI value from above (negative edge), the comparator CA1 output stays high, mode =RUN. The reference signal passes the Level LO value from above (negative edge), the comparator CA1 output=STOP. CG Drives & Automation 01-7492-01r0...
Page 170
Set by Process settings High Process Ref [321] and [322] Set by Process settings Process Err [321] and [322] NOTE: If Bipolar selected [6115] then Min value is Fig. 127 equal to -Max in the table. CG Drives & Automation 01-7492-01r0...
Page 171
(negative edge), the comparator CA1 is reset, output is set low. The reference signal passes the Level LO value from above (signal outside Window band), the comparator CA1 is reset, output is set low. CG Drives & Automation 01-7492-01r0...
Page 172
Reset delay [6115] Bipolar An.Value Fig. 130 Set/reset delay for output signal. [6112] HI < 0 [6111] [6113] LO < 0 Fig. 128 Principle functionality of comparator features for “Type [6114] = Hysteresis ”and “Polar [6115]”. CG Drives & Automation 01-7492-01r0...
Second input to AnMux1. Select one of AnIn1 - 4. Input numbered as [6111], i.e. AnIn1 = 16 and default is AnIn2. 6212 AnMux InB Default: Process Val Selections: Same as in menu CA1 Value 6112 CG Drives & Automation 01-7492-01r0...
6222 AnMux InB Default: Process value Selections: Same as in menu CA1 Value 6112 Operator [6223] The function is the same as in Operator [6213]. 6223 Operator Default: Selections: Same as in menu Operator 6113 CG Drives & Automation 01-7492-01r0...
Operator 2 = + (OR), menu [6415] Operator 3 = & (AND), menu [6417] The following expression is created, using the menus above: CA1&F1+T1Q&NOT1 With the default setting for L1 Expression this is representing: ((CA1&F1)+T1Q)&NOT1 CG Drives & Automation 01-7492-01r0...
Page 176
Compare to expression is finished (when two or chapter Fig. 130 page 168. three expressions are tied together). &=AND & 6419 L1 Set Dly +=OR Default: 0.0 s ^=EXOR Range: 0 - 36000.0 s CG Drives & Automation 01-7492-01r0...
So initialization of the timer might differ for a set change compared to normal triggering of a timer. Timer1 Trig Timer1 T2 Timer1 T1 Timer1 T1 Timer1 T2 Fig. 132 Alternative timer mode CG Drives & Automation 01-7492-01r0...
Page 178
Selection of mode of operation for Timer 1. Default: 0.0 s 6512 Timer1 Mode Range: 0 - 36000.0 s Default: Timer 2 - Timer 4 [652] - [654] Timer is disabled Refer to the description for Timer 1 [651]. CG Drives & Automation 01-7492-01r0...
Table 40 Truth table for Edge control without priority. Reset priority RESET - (no change) RESET 1 (set) 0 (reset) No change Set priority RESET Edge controlled without priority RESET Fig. 134 Programmable flip-flop modes. CG Drives & Automation 01-7492-01r0...
Page 180
541 = Digital Out 1 function 6611= Counter 1 trigger 6612= Counter 1 reset 6613= Counter 1 High value 6614= Counter 1 Low value 6615= Counter 1 Decrement timer 6619= Counter 1 value Fig. 135 Counters, operating principle. CG Drives & Automation 01-7492-01r0...
Page 181
NOTE: Counter high value has priority so if high and low values are equal then the counter output is de- activated when the value is smaller than the low value. 6714 C1 Low Val Default: Range: 0 - 10000 CG Drives & Automation 01-7492-01r0...
Date when the clock output signal (CLK1) is deactivated. Note that if “Clk1DateOff” is set to an earlier date than “Clk1DateOn”, the result will be that the clock is not deactivated at the set date. 6814 Clk1DateOff Default: 2000-00-00 Range: yyyy-mm-dd (year-month-day) CG Drives & Automation 01-7492-01r0...
Shaft power [714] Clock 2 [682] Displays the actual shaft power. Negative sign is used when Refer to the description for Clock 1 [681]. the shaft is generating mechanical power to the motor. Shaft Power Unit: Resolution: CG Drives & Automation 01-7492-01r0...
Page 184
Displays the actual DC link voltage. DC Voltage Unit: Resolution: 0.1 V IBGT Temperature [71A] Displays the actual IGBT temperature, measured. The signal is generated by a sensor in the IGBT module. IGBT Temp Unit: °C Resolution: 0.1°C CG Drives & Automation 01-7492-01r0...
7 - 5 0=Rem, 1=Key, 2=Com, 3=Option Active limit functions, where 13 - 8 0=No limit, 1=VL, 2=SL, 3=CL, 4=TL Inverter is in warning (A warning condition is active) Inverter is tripped (A Trip condition is active) CG Drives & Automation 01-7492-01r0...
Digital Out 2 is not active. Relay 1 is active, relay 2 and 3 Under voltage are not active. Power fault Desat 0rpm DigOutStatus DClink error RE 100 DO 10 Int error Rem/Rem Ovolt m cut Over voltage Fig. 138 Digital output status example Crane Comm Encoder CG Drives & Automation 01-7492-01r0...
Page 187
Fig. 141 Analogue output status The first row indicates the Analogue outputs. 1 AnOut 1 2 AnOut 2 Reading downwards from the first row to the second row the status of the belonging output is shown in %: CG Drives & Automation 01-7492-01r0...
00: 00: 00–262143: 59: 59 Energy [733] Displays the total energy consumption since the last energy reset [7331] took place. Energy Unit: Wh (shows Wh, kWh, MWh or GWh) 0.0–1GWh, Range: Counter will restart at 0 after 1GWh CG Drives & Automation 01-7492-01r0...
After resetting an alarm, the menu will change and show menu [100]. Below two examples of trip messages are shown. Here the menu shows the date and the real time when the trip occurred. 0rpm Over temp 2020-01-15 17:15:38 Rem/Rem Fig. 142 CG Drives & Automation 01-7492-01r0...
Analogue input status 3-4 Analogue output status 1-2 I/O status option board 1 I/O status option board 2 I/O status option board 3 Run Time Mains Time Energy Set/View ref VIO Status PT100 4, 5, 6 CG Drives & Automation 01-7492-01r0...
- 03.07 = option version, is only visible and valid for special software, type OEM adapted software. Build ID 03 = (major) special software variant number OE1B7F9E 07= (minor) revision of this special software Example: 0E1B7F9E CG Drives & Automation 01-7492-01r0...
Page 192
Shows the software version number of the control panel. Fig. 145 gives an example of the version number. 9251 CP SW ver V 2.00 Fig. 146 Example of software version V 2.00 = Software version CG Drives & Automation 01-7492-01r0...
• After reset command, the trip message will disappear and menu [100] will be indicated. Apart from the TRIP indicators there are two more indicators to show that the inverter is in an “abnormal” situation. CG Drives & Automation 01-7492-01r0 Troubleshooting, Diagnoses and Maintenance...
Over voltage Warning in the manual. Safe stop Warning Brake Trip/Off/Warn Normal OPTION Normal Internal error Normal *) Refer to table table 44regarding which Desat or Power Fault is triggered. Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-7492-01r0...
Fig. 148 Autoreset trip Fig. 148 shows the 3rd trip memory menu [830]: Overvoltage G trip after the maximum Autoreset attempts took place after 345 hours, 45 minutes and 12 seconds of run time. CG Drives & Automation 01-7492-01r0 Troubleshooting, Diagnoses and Maintenance...
Page 198
-Check the monitor setting in section 11.4.1, reached. page 145. -Check the load condition of the machine Min alarm level (underload) has been Mon MinAlarm -Check the monitor setting in section 11.4.1, reached. page 145. Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-7492-01r0...
Page 199
Mains voltage dip due to starting other Try to use other mains supply lines if dip is caused major power consuming machines on by other machinery the same line. Use the function low voltage override [421] CG Drives & Automation 01-7492-01r0 Troubleshooting, Diagnoses and Maintenance...
Page 200
Check settings [33C], [33D], [33E], [33F]. * = 2...6 Module number if parallel power units (size 300–3000 A) ** = If no size is mentioned in this column, the information is valid for all sizes. Troubleshooting, Diagnoses and Maintenance CG Drives & Automation 01-7492-01r0...
Preventive maintenance can optimise the product life time and secure trouble free operation without interruptions. For more information on maintenance, please contact your CG Drives & Automation service partner. Precautions to take with a connected motor NOTE: Refer to motor manufacturers instruction manual for motor maintenance requirements.
There is also an optional Control panel with Bluetooth Control panel with Bluetooth (size D and communication available for connection with cellphone or 01-6880-10 tablet. 01-6880-20 Control panel with WiFi (size D and up) CG Drives & Automation 01-7492-01r0 Options...
AC drive to the PC for backup and printing. Recording can be made in oscilloscope mode. Please contact CG Drives & Automation sales for further information. Fig. 152 Handheld Control Panel 2.0 (4-line Control Panel). The Handheld Control Panel - HCP 2.0 is a complete control panel, easy to connect to the AC drive, for temporary use when e.g.
B-D and F69-T69. Name Function Specification terminal External, AC drive + (left) + 24 V main power independent, 24 V ±10% supply voltage for Double control and isolated - (right) communication circuits CG Drives & Automation 01-7492-01r0 Options...
13.19 AFE - Active Front End is not part of the liquid cooling option. Emotron AC Drives from CG Drives & Automation are also Drive units with parallel power modules (frame size available as Low harmonic drives and Regenerative drives.
14.1 Electrical specifications related to model Note: Use motor rated current for drive sizing. Emotron VFX 2.1 - IP20/21 version Table 49 Typical motor power at mains voltage 230 V. AC drive main voltage range 230 - 480 V. Normal duty Heavy duty Max.
Page 210
69-006-20 69-008-20 12.8 C2(69) 69-010-20 69-013-20 20.8 10.4 69-018-20 14.4 69-021-20 18.5 16.8 69-025-20 18.5 69-033-20 69-042-20 D2(69) 69-050-20 69-058-20 * Available during limited time and as long as allowed by drive temperature. Technical Data CG Drives & Automation 01-7492-01r0...
Page 211
Emotron VFX 2.1 - IP54 version (Model 48-300 and up also available as IP20) Table 52 Typical motor power at mains voltage 230 V. AC drive main voltage range 230 - 480 V. Normal duty Heavy duty Frame Max. (120%, 1 min every 10 min)
Page 212
48-2K5-IP 3000 1400 2500 1120 2000 O(10) Larger sizes available on request * Available during limited time and as long as allowed by drive temperature. ** PEBB= Power Electronic Building Block (power module). Technical Data CG Drives & Automation 01-7492-01r0...
Page 213
3000 2100 2500 1700 2000 O(10) Larger sizes available on request * Available during limited time and as long as allowed by drive temperature. ** PEBB= Power Electronic Building Block ( power module). CG Drives & Automation 01-7492-01r0 Technical Data...
Page 214
Emotron VFX 2.1 - IP54 version (Model 69-250 and up also available as IP20) Table 55 Typical motor power at mains voltage 525 V. AC drive main voltage range, for VFX52: 440 - 525 V and for VFX69: 500 - 690 V.
Page 215
S69 (14) 69-3K0-IP 3600 3200 3000 3000 2500 2400 2400 T69 (15) * Available during limited time and as long as allowed by drive temperature. ** PEBB= Power Electronic Building Block (power module). CG Drives & Automation 01-7492-01r0 Technical Data...
- 10 V @10 mA -10VDC +24 V Short-circuit current +100 mA max (together with Digital +24VDC Outputs) Standby supply Standby supply input voltage for control unit. 24 VDC ±10% (max 1A consumption) Technical Data CG Drives & Automation 01-7492-01r0...
74 A - (5% x 74) = 70.3 A; this is not enough. Calculation for model VFX48-090 90 A - (5% x 90) = 85.5 A In this example we select the VFX48-090. Technical Data CG Drives & Automation 01-7492-01r0...
(88.6 x 106.3 x 23.6) 1036 x 2830 x 450 2250 x 3000 x 600 O (2xH+2xI) 836 (1834) 1772 (3907) (40.8 x 111.4x 17.7) (88.6 x 118.1 x 23.6) * Enclosure height/Total height CG Drives & Automation 01-7492-01r0 Technical Data...
Page 220
(88.6 x 165.4 x 23.6) 1176 x 4330 x 450 2250 x 4500 x 600 T69 (5xI69) 1285 (2833) 2777 (6122) (46.3 x 170.5 x 17.7) (88.6 x 177.2 x 23.6) * Enclosure height/Total height Technical Data CG Drives & Automation 01-7492-01r0...
Page 221
545 / 658 x 220 x 291 033 to 058 D2(69) 30 (66) (21.5 / 25.9 x 8.7 x 11.5) H1 = Enclosure height. H2 = Total height including cable interface. * with optional top cover CG Drives & Automation 01-7492-01r0 Technical Data...
WARNING! If the device is stored for more than two years, the DC link capacitor of the devices must be reformed during commissioning. The reforming procedure is described in manual “Capacitor reforming unit”. Technical Data CG Drives & Automation 01-7492-01r0...
Page 224
Note: For IP54 models 48/52-003 to -074 and 69-002 to -058 cable glands are optional. * IP20/21 models are equipped with cable clamps instead of glands. For data on cable connection ranges, see section 3.4.3, page 39. Technical Data CG Drives & Automation 01-7492-01r0...
Page 225
22 - 28 mm (0.87 - 1.1 in) 69-082-54 69-090-54 69-109-54 (Ø23-55 mm (0.9 - 2.16 in)) Cable flexible leadthrough or M63 opening. (Ø17-42 mm (0.67 - 1.65 in)) Cable flexible leadthrough or M50 opening. 69-146-54 69-175-54 69-200-54 CG Drives & Automation 01-7492-01r0 Technical Data...
Page 226
Note: For IP54 models 48/52-003 to -074 and 69-002 to -058 cable glands are optional. * IP20/21 models are equipped with cable clamps instead of glands. For data on cable connection ranges, see section 3.4.3, page 39 Technical Data CG Drives & Automation 01-7492-01r0...
NOTE: Possible potentiometer value in range of 1 kΩ to 10 kΩ (¼ Watt) linear, where we advice to use a linear 1 kΩ / ¼ W type potentiometer for best control linearity. Technical Data CG Drives & Automation 01-7492-01r0...
I n d e x Safety earth ......29, 57 Maximum Frequency ..... 126 Control Panel memory Minimum Frequency ..... 126 Copy all settings to Control Preset Frequency ....131 Symbols Panel ........102 Skip Frequency ...... 127 +10VDC Supply voltage ....224 Frequency .......150 Frequency priority ......