Allowed thresholds: 4 to 15 K
Examples of values:
Underfloor heating: 5 K
Radiator heating: 7 to 10 K
Accumulator charge 7 to 10 K
►Minimum speed of the charge pump
Set the condenser's circulator pump a minimum speed be-
low which the speed does not decrease during charging.
Factory setting: 40%
Allowed thresholds: 20–60%
►Maximum speed of the charge pump
Set the condenser's circulator pump a maximum speed
above which the speed does not increase during charging.
Factory setting: 100%
Allowed thresholds: 70–100%
COLLECTOR
►Minimum speed of the source pump
Set the collector's circulator pump a minimum speed be-
low which the speed does not decrease during charging.
Factory setting: 40%
Allowed thresholds: 20–70%
►Maximum speed of the source pump
Set the collector's circulator pump a maximum speed
above which the speed does not increase during charging.
Factory setting: 100%
Allowed thresholds: 70–100%
►Free cooling
Set the collector's circulator pump a speed setting for free
cooling situations. Free cooling is activated using external
contact information.
Factory setting: 100%
Allowed thresholds: 20–100%
ELECTRIC HEATER (internal supply water

electric heater)

Operating mode
indicates the operating mode of the electric heater
►Collector's temperature limit for electric heater op-
eration
Set a threshold for the measurement (B91) coming to the
collector, in which case the electric heater will start heat-
ing alongside the compressor to protect the collector from
freezing.
Factory setting: –4°C
Allowed thresholds: set based on the application
v 2-1 17022021
►On, sequence 1
Setting the release of the first sequence of the electric
heater
►On, sequence 2
Setting the release of the second sequence of the electric
heater
►On, sequence 3
Setting the release of the third sequence of the electric
heater
►Confirmation (P value)
Setting the P value for capacity calculation
►Integral Time (I time)
Setting the I time for capacity calculation
HEATING CIRCUIT 1/2/3
The settings of the heating circuits are set on a circuit-by-
circuit basis for each heating circuit in use.
►Alert limits
The upper and lower limit alerts are set for the supply tem-
perature sensor and the room temperature sensor.
►Summer/winter setting
The settings related to the summer and winter change of
the heating circuit are set. The heating circuit goes to the
STOP mode in the summer mode and to the HEATING
mode in the winter mode. If the heating circuit is intended
to be heating all year round, WINTER is selected as the
mode.
►Summer/winter mode
Auto/lt: automatically switches between the summer and
winter modes according to the outdoor temperature time
constant.
DATE: changes between the summer and winter modes
according to fixed dates.
Summer: fixed in STOP mode
Winter: fixed in HEATING mode
►Summer/winter time constant
A filtered temperature time interval for measuring the
change of the heating circuit is set to the heating circuit.
►Start date
A fixed start date is set for the heating season to specify
the date on which the heating will enter into the WINTER
mode.
►End date
A fixed end date is set for the heating season to specify the
date on which the heating will enter into the SUMMER
mode.
►Reset outdoor temperature
The filtered outdoor temperature is reset.