Copeland E3-FSD Quick Start Manual

Copeland E3-FSD Quick Start Manual

Facility status display

Advertisement

Quick Links

E3-Facility Status Display (FSD)
The E3-FSD reports alarm information and more, (such as temperatures, occupancy, case
status, and setpoints) and provides a centralized device for store personnel to review
information by communicating with the E3 via Ethernet connectivity (minimum E3
firmware revision 2.26).
The E3-FSD has a touch screen color display for quick navigation, which enables alarms
and other relevant store information to be viewed from where it is most convenient for the
user.
The E3-FSD can be configured to filter out notices and/or return-to-normal alarms, and
provides a quick review of all advisories and detailed advisory information. The E3-FSD
also receives alerts and provides annunciated alarms and alarm information directly to
store and department managers. This compact unit can be installed virtually anywhere
with a standard Ethernet connection and 24VAC power sources.
Specifications
Operating Temperature
Operating Humidity
Storage Humidity
Voltage
Dimensions
2 Ethernet Ports
Lithium Battery Marking
STEP 1: Mounting
Use the 603-0110 mounting plate kit to mount the E3-FSD flush onto the wall.
The E3-FSD box body style is designed to be mounted against or inside a wall or panel. If mounted against a surface, the controller will be
3.75" off the mounting surface. If mounted inside a surface, the door and front section of the back panel will rest 1.55" (plus the depth of the
plate) off the mounting surface.
Standard Mount
The standard mount is meant for the controller to be mounted against a wall using the four mounting holes at the rear of the enclosure shown
in Figure 1 - Four Mounting Holes Location . These holes are accessible without any removal of any components inside the enclosure.
026-4277 R2
©2024 Copeland LP.
-40°F to 140°F (-40°C to 45°C)
*Tested to UL60730-1 standard
5% to 95% RH non-condensing at 90°F
5% to 100% RH
24VAC ±20%, 50/60 Hz, Class 2 transformer
12 x12 x 3.75 in.
ETH 0, ETH 1
Caution: The cell used in this device may present a fire or chemical burn hazard if mistreated.
Do not disassemble, heat above 212°F or incinerate.
QUICK START GUIDE
Facility Status Display (P/N 860-5000)

Advertisement

loading
Need help?

Need help?

Do you have a question about the E3-FSD and is the answer not in the manual?

Questions and answers

Summary of Contents for Copeland E3-FSD

  • Page 1 Use the 603-0110 mounting plate kit to mount the E3-FSD flush onto the wall. The E3-FSD box body style is designed to be mounted against or inside a wall or panel. If mounted against a surface, the controller will be 3.75”...
  • Page 2 Scale. Once this hole is cut, mount the plate to the back of the E3-FSD housing and attached using the four screws and hardware included in the kit (Figure 3 - Mounting Plate Attached to the E3-FSD - front open and Figure 5 - Mounting Plate Attached to Rear Housing - back view).
  • Page 3 E3-FSD Inside Back Enclosure with Plate Attached - 4 mounting holes indicated Figure 3 - Mounting Plate Attached to the E3-FSD - front open E3-FSD with Mounting Plate - Front View Figure 4 - Mounting Plate Attached to Rear Housing - front closed 026-4277 R2 ©2024 Copeland LP.
  • Page 4 Connect the Ethernet cable to the ETH port labeled ETH0 NETWORK. NOTE: Do not exceed the maximum Ethernet cable length of 328 feet (100 meters). Figure 6 - Ethernet Connection NOTE: The E3-FSD comes pre-wired from the factory. No alarm or horn wiring is required. 026-4277 R2 ©2024 Copeland LP.
  • Page 5 Figure 8 - Connect 24VAC Power STEP 4: Software Setup and Parameter Settings Once mounted and powered on, log in and follow the steps below. Your E3-FSD comes with Feature setup and Setpoint files pre-loaded at the factory. Login with your default user/password: user/fsdadmin (it is recommended to change your password after initial login).
  • Page 6 Figure 9 - E3-FSD System Values Page Set Alarm Annunc to ENABLED (default). Set UnitNumber to the number of your E3-FSD on the network. Enter a Group Name for the correct peer network name. Site Name and Unit Name fields are both optional settings.
  • Page 7 This is the default configuration. Note that if the audible alarm should be silent, select None in the Audible Alarm field of the Options tab. By default it is set to External. Typically, these will be left as they are in the default setup. Figure 12 - Point List Advance mode: Figure 13 - Advance Mode 026-4277 R2 ©2024 Copeland LP.
  • Page 8 The contents of this publication are presented for informational purposes only and they are not to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. Copeland reserves the right to modify the designs or specifications of such products at any time without notice.