Warranty / Guarantee (general information) For HERZ - heat pumps, we offer a 5 year or 10.000 compressor hours warranty on the closed refrigeration circuit. As an option, the warranty can be extended (material warranty on the heat pump compressor) to 10 years.
Adequate lighting must be provided in the technical room. The technical room may only be entered by authorized persons. ◼ Should you have any queries, please call us. ◼ Initial commissioning must be carried out by the HERZ Customer Service department or an authorised specialist (otherwise any warranty claim will not be applicable).
Notes on documentation 1.2 Symbols The symbols used on the device and/or used in this documentation have the following meaning: Pictogram Signal word Meaning Documentation Reference to other documentation! Note Important Note! Warning note Notice of a dangerous situation! Electric Danger of electrical voltage! voltage Caution –...
HERZ. People (including children) who, because of their physical, sensory or mental capabilities or because of their lack of experience or knowledge, are unable to use the equipment safely must not use this equipment unless they are supervised or instructed by a responsible person.
In order to prevent any maintenance errors, if maintenance is not carried out properly, it is recommended to be carried out regularly by authorised personnel or by the HERZ Customer Service department. Spare parts must be obtained directly from the manufacturer or a distribution partner. The customer will not...
Information of the device 3 INFORMATION OF THE DEVICE 3.1 Intended use The commotherm heat pumps may only be used for ◼ Heating ◼ Cooling and for ◼ Hot water preparation. Any other use is not considered as intended. In addition, the device may only be used within its technical range of application! The technical area of application is shown in the assembly instructions! To the intended use of the device the following also applies: ◼...
◼ Check the pressure on the heating side ◼ Check the electrical connections and the cabling HERZ Energietechnik GmbH offers also maintenance contracts. For further information please contact our service hotline.
System overview 4 SYSTEM OVERVIEW commotherm AWi-Mono (outdoor unit) Figure 4.1: System overview - Outdoor Unit Evaporator + Ventilators Condenser Process reversing valve Refrigerant pipe connections Inverter compressor BLCD controller for compressor Flow heat pump (Hydro-Unit) Return heat pump Electrical control cabinet...
Page 12
System overview commotherm AWi-Mono - indoor unit (hydro module) Figure 4.2: System overview - indoor unit (hydro unit) Operating display T-Control E-heating rod in the flow Flow sensor Condenser pump Switching valve Flow heat pump Flow heating Flow of hot water boiler...
Mode of operation 5 MODE OF OPERATION The figure shows the cooling circuit of the commotherm AWi heat pump with its most important components. A refrigerant circulates and run through various changes of state. In the evaporator the refrigerant absorbs energy resp.
Mode of operation The HERZ heat pump is an “electrically-driven compression heat pump with the refrigerant, R32”. An electrically driven compressor, compresses and feeds the refrigerant through a pipe circuit consisting of copper pipes, whereby pressure up to 49 bar may arise.
In the event of fire, any type of fire extinguisher may be used! There is no risk of the R32 refrigerant escaping if the HERZ heat pump is used correctly. If there is an escape of refrigerant due to improper use, there is a risk of suffocation (air displacement) and frostbite (exit points may become extremely cold).
Mode of operation 5.2 Safety devices The pressures in the commotherm heat pump should remain within a define range. To ensure this, so-called pressure switches are built in. These serve on the one hand as a safety device, and on the other hand to ensure that the heat pump works in the defined range.
Description of heat pump control 6 DESCRIPTION OF HEAT PUMP CONTROL 6.1 Operating conditions Status 0 Ready If the heat pump is in “heating operation” or “cooling operation” mode but there is no request from the consumer, the operating condition "ready" also appears Status: 1 Pump flow In this condition, the source and condenser pump start up and run for a pre-set time.
Page 18
Description of heat pump control Status: 9 Min. temp. The heat pump changes to this state as soon as the back flow temperature of the heat pump drops below the value of the set Min. Temp. Cooling / Defrost WT. In this operating state, the heat pump switches off and the condenser pump runs.
Temperature manager 7 TEMPERATURE MANAGER The heat demand of the individual modules (hot water tank, buffer tank, heating circuit, solar, etc.) is controlled by the temperature manager. The below-mentioned scheme explains the functionality of the temperature manager. A module contains of an in- and output. Every module sends a required demand temperature to the temperature manager.
T-CONTROL 8 T-CONTROL The handling and menu navigation are described in this chapter. The individual terms listed in the menus of the individual modules are explained in the following chapters. 8.1 Starting the system To switch on the display, the following condition must be fulfilled: ◼...
T-CONTROL 8.3 Main menu After start up following figure will appear. In the centre of the screen important values according the heat pump, buffer, hot water tank, heating circuit and so on are shown. The shown values can be adapted individually.
T-CONTROL 8.4 Symbols explanation In this section important symbols are explained, which are displayed on the following menu pictures. This symbol shows that remote access is currently taking place. This symbol shows that an e-mail is currently being sent. This symbol shows that a USB stick is currently connected. With the aggregate-test connected components can be tested individually.
T-CONTROL 8.5 Code – entry If entering the code, the following operations can be performed: ◼ Setting up values ◼ Activation of the aggregate-test (Description see chapter 8.4) ◼ Setting up or changing of date & time (see chapter 8.6) Navigation in the menu settings.
T-CONTROL 8.6 Date and time selection Navigation 1: Navigation 2: Screen: Screen: By pressing the button: By pressing the button: the language can be set up. the language can be set up. the server name can be set up. (The server receives the time can be set up.
T-CONTROL Main menu values 8.7.1 Adding / defining display values Code – entry Navigation 1: Navigation 2: Show value Screen: Screen: By pressing the button: By pressing the button: an overview of available values the selected value can be add favorite Act.clear will be displayed deleted...
T-CONTROL Navigation 3: Load scheme Navigation 4: Show value HEAT PUMP 004 Screen: Screen: By pressing the button: Note: The values of the default scheme can also be Compressor, adapted individually. Thereby press 3-5 seconds on charge pump, the value will be confirmed and the value and follow the procedure described in actual return displayed at the main menu.
T-CONTROL Fault messages and warnings Navigation: → Screen: By pressing the button: the current fault messages will be displayed.(By default, current errors are always Actual displayed first) Archive all fault messages will be displayed. Note: ◼ A red highlighted field represents an active fault (appears in the lower left box). ◼...
T-CONTROL Modules Navigation: → Screen: By pressing the button: the „heat pump“ menu will be displayed HEAT PUMP the „buffer values“ menu will be displayed Buffer the „hot water tank values“ menu will be displayed HOT WATER TANK the „heating circuit values“ menu will be displayed HEATING CIRCUIT If several modules have been created, you can navigate through the menu of the modules (up or down).
T-CONTROL 8.10 Module configuration Heat pump Buffer Hot water tank Overview Overview Overview Status Status Status Settings Settings Settings Inputs/Outputs Barrier times Agg-Test Operating hours Circulation pump Time program/Barrier times Heating circuit Time mode Solar Overview Overview Overview Status Time program Status Settings Settings...
T-CONTROL 8.11.1 Heat pump Navigation: → → BOILER Screen: By pressing the button: The corresponding mode for the heat pump can be set here (OFF, heating mode, Mode cooling mode, emergency mode, via Hardware). the „Heatpump status“ menu will be displayed (Schematic representation of the heat pump and overview of various values) the menu for the "settings"...
Page 31
T-CONTROL Term Description Unit Menu „Heatpump status“ Status 1 Flow temperature Display of the heat pump flow temperature °C Back flow Display of the heat pump back flow temperature °C temperature Pump speed Display of the speed of the pump inlet temperature Menu „Settings“...
Page 32
T-CONTROL Term Description Unit Flow OK Indicates the state: ▪ If the control lamp lights up, the flow monitor reports sufficient flow. In-/Outputs Indicates the state of the condenser pump: ▪ when switch is green ➔ output active Condenser pump When active, the condenser pump is switched on and supplies heat to the connected modules (Buffer, hot water tank, heating circuit).
Page 33
T-CONTROL Term Description Unit Display of the heat Display the number of the heat pump starts pump starts Total generated Display of the energy, which is obtained from the heat pump out of the heat energy since: source since reset date. The value can be reset to 0 with the Rest button.
T-CONTROL 8.11.2 Buffer Navigation: → → BUFFER Screen: By pressing the button: the „buffer status“ menu will be displayed the menu for the "settings" will be displayed the menu for the "Aggregate-Test“ will be displayed the „barrier times“ menu will be displayed Term Description Unit...
Page 35
T-CONTROL Term Description Unit Setting up the summer must temperature (15-95). That´s the Buffer Summer must temperature (Buffer bottom temperature- respectively if installed Buffer °C temperature centre temperature), which will be provided during summer operation. Setting up the temperature difference (-5 -25) between heat supplier (= Difference boiler) and buffer temperature bottom for excitation of the buffer loading °C...
T-CONTROL 8.11.3 Hot water tank Navigation: → → Hot water tank Screen: By pressing the button: The release for charging the boiler is set. If fast start up is activated, the hot water tank is heated independently (maximum loading time) to the requested set temperature the „hot water tank status“...
Page 37
T-CONTROL Term Description Unit Menu "Settings" Settings Must temperature Setting the must temperature (47-85) of the boiler °C Activate/setting the min. temperature (20-58) (ON/OFF) ▪ With activated min. Outside of the hot water tank loading time, the hot Min. Temperature °C water tank temperature is set to the set min.
T-CONTROL 8.11.4 Heating circuit Navigation: → → HEATING CIRCUIT Screen: By pressing the button: Selection of the operating mode (for a description, see "Overview of operating modes") the „hot water tank status“ menu will be displayed the menu for the "settings" will be displayed the menu for the "Aggregate-Test“...
Page 39
T-CONTROL Term Description Unit Overview Operation modes Selection operation modes: ▪ Heating OFF The heating system is switched off ▪ Heating time mode: Heating corresponds to the set heating time ▪ Durable heat: Constant heat up to required set room temperature or to the calculated feed flow target temperature ▪...
Page 40
T-CONTROL Term Description Unit Active Heating time Indicates the actual operating mode mode Remote control Display of the selected remote controller number Balancing room Setting the value (-5 to +5) for calibrating the room sensor °C sensor Kneeling barrier over Activates the kneeling barrier over the room temperature room temperature Barrier over room...
Page 41
T-CONTROL Term Description Unit Indicates the state of the heating circuit: Lock heating circuit If the control lamp lights up, the heating circuit is blocked Menu "Time program / Barrier times" Time program 1 2 3 1 - 3 times can be set. The second and third time can be added by the +.Example: ▪...
T-CONTROL Term Description Unit Current outdoor Display of the current outside temperature °C temperature Setting the outside temperature (10-30) above which the selected cooling Switch-off temperature °C circuit is deactivated. Humidity Activation of the humidity measurement status (ON/OFF). measurement active Maximum difference Setting the maximum difference (2-15) to the room temperature °C...
Page 43
T-CONTROL Table 8. 1: Operation mode "Screed drying" Flow set If screed drying gets interrupted, resume Bake out day temperature in drying as follows: °C Day of interruption resume from day 0 – 15 17 – 23 5 – 12 24 –...
T-CONTROL 8.11.6 Time mode Navigation: → → Time mode Screen: By pressing the button: the menu for the "settings" will be displayed the menu for the "time program“ will be displayed Indicates the state of the active requirement of the time mode Demand active If the indicator lamp lights up, the requirement is activated Required temperature...
T-CONTROL Term Description Unit By pressing the symbol Monday preset gets assigned to remaining weekdays 8.11.7 Solar NOTE: At the solar module 5 resp. 6 (only at external solar module) program numbers are available, which are set up by the service technician. The only differences of the programs are the integration and the number of tanks (e.g.
Page 46
T-CONTROL Term Description Unit Menu "Settings" Settings Setting up the minimum collector temperature (15-70) to startup the solar Pump trigger °C pump Tank 1 must Setting up the set temperature (25-90) of tank 1 °C temperature Difference 1 Setting up the collector difference (5-30) of tank 1 °C Tank 1 max.
T-CONTROL 8.11.8 Hydraulic compensator Navigation: → → Hydraulic compensator Screen: By pressing the button: the „Hydraulic compensator status“ menu will be displayed the menu for the "Aggregate-Test“ will be displayed the „barrier times“ menu will be displayed Indicates the required temperature of the downstream module (e.g. heating Required temperature circuit) in °C Existing temperature...
T-CONTROL Term Description Unit Display of the state of the switching valve. Switching valve If the indicator lamp lights up, the switching valve is activated. Indicates the state of pump 2: Pump 2 Pump 2 is the pump in the flow on the secondary side.If the indicator lamp lights up, pump 2 is switched on Menu "Barrier times"...
T-CONTROL Term Description Unit Indicates the required temperature of the downstream module (e.g.: buffer) Required temperature °C The required temperature is the temperature, which the upstream module disposal to the downstream module Pump Indicates the state of the net pump Menu "Aggregate-Test"...
Page 50
T-CONTROL Status Indicates the temperature of the upstream module Existing temperature °C (e.g.: buffer top temperature) Indicates the required temperature of the downstream module (e.g.: buffer) Required temperature °C The required temperature is the temperature, which the upstream module disposal to the downstream module Zone valve Indicates the state of the zone valve Status 2...
T-CONTROL 8.11.11 External requirement The external requirement module provides an interface to an external foreign control loop (e.g. central building control system). The requirement, which can be digital or analogue, is registered as a required temperature (e.g. boiler must temperature by the boiler or buffer top temperature by the buffer) in the heat supplier (e.g.
T-CONTROL Term Description Unit Display of the requirement curve Menu "Barrier times" Barrier times 1 - 2 times can be set.The second time can be added by the +.Example: ▪ 08:00 – 10:00 Time 1 time 1: ▪ 15:00 – 21:00 time 2: Setting up individual buffer tank loading times of every weekday, when it 08:00 –...
Page 53
T-CONTROL current signal [mA] figure 8. 3: Analogue set temperature as a function of the applied current signal of the external requirement At the input of the external requirement module a current signal between 4 and 20 mA should be given, because a current signal is compared to a voltage signal insensitive to electromagnetic disturbances and voltage losses at the cables.
T-CONTROL 8.11.12 Additional boiler The recommended hydraulic schemes are shown in appendix. Navigation: → → Additional boiler Screen: By pressing the button: the „additional boiler status“ menu will be displayed (Schematic representation of the boiler and overview of various values) the menu for the "settings"...
Page 55
T-CONTROL Term Description Unit Agg-Test Indicates the state of the back flow pump of the additional boiler ▪ Pump If the indicator lamp lights up, the pump of the additional boiler is operating. Release Indicates the state of the release of the additional boiler. (only automatic boiler) If the indicator lamp lights up, the additional boiler is operating.
T-CONTROL 8.12 System settings Navigation: → → → → Screen: If touching symbol: the network configuration will be displayed. the Remote – settings will be displayed. information such as software version operating system number, … will be displayed. the screensaver settings will be displayed. messages by E-mail can be send Display if a USB stick is plugged in (USB-symbol).Backup of USB stick create or play (backup, software, ...) by pressing the field.
T-CONTROL 8.12.1 Network configuration Navigation 1: Navigation 2: Screen: Screen: By pressing the button: By pressing the button: the IP address of the DNS server NetBIOS Name the NetBIOS name can be set up DNS 1 / DNS 2 can be set up The boiler IP address can be set the network configuration page IP-Address...
Modbus is an application protocol to exchange messages between intelligent Modbus controllers in the building management system. The Modbus protocol “TCP” is used in the HERZ control. This protocol transmits the encoded data via LAN cable. Modbus ensures that connected controllers in the building...
T-CONTROL 8.12.3 Screensaver Navigation: Screen: By pressing the button: Waiting screen the standby mode waiting time can be set up. active Set the display brightness to return to the settings overview. 8.12.4 Remote Navigation: Screen: Note: There is a separate manual "MyHerz" ("MyHerz"), in which the settings are described. The "Remote function" is used for setting the remote maintenance of the system.
T-CONTROL 8.12.5 Information overview Navigation: Screen: Note: The information shows an overview of the current software versions, operating system, firmware and also the hydraulic scheme. If a USB-Stick is plugged in, the hydraulic scheme can be saved. No values can be changed.
Page 61
T-CONTROL the mail settings will be displayed again. Note: Selection: The box must be activated. If the status is inactive, no E-mail will be sent to the recipient. If the box is checked, errors will be transmitted If the box is checked, warnings will be transmitted If the box is checked, information will be transmitted ENTER MAIL SUBJECT...
T-CONTROL 8.12.7 Mail Server settings Navigation: Screen: By pressing the button: Mail Server the mail server address can be entered (=outgoing mail server) the boiler’s E-mail address can be entered Mail address Password the password can be entered SSL,TLS,… the encoding can be chosen (no, SSL, TLS) Port Setting up the TCP port number.
T-CONTROL 8.12.9 Service special Navigation: Screen: By pressing the button: Status module the status of the external modules is displayed Format USB- the USB stick can be formatted. Stick a backup can be created.The backup can be stored directly in the control and/or on an Backup USB-stick.
Fault reports and their corrections 9 FAULT REPORTS AND THEIR CORRECTIONS If a fault arises, the fault must always be rectified first and afterwards cleared by switching the system on again. If several faults arise at the same time, they will be displayed in order of their occurrence. Info / indication Warning Fault;...
Page 65
Fault reports and their corrections No. Fault report Cause of fault Fault correction Check sensor, replace as renew Check plug, replace as renew Sensor break; Value outside the measuring range Check wiring incl. connections, replace BUFFER SENSOR TOP as renew (-10 - 120°C) ✆...
Page 66
Fault reports and their corrections No. Fault report Cause of fault Fault correction Check sensor, replace as renew Check plug, replace as renew Sensor break; Value outside Check wiring incl. connections, replace SENSOR COLLECTOR measuring range (-50 - 200°C) as renew ✆...
Page 67
Fault reports and their corrections No. Fault report Cause of fault Fault correction when exceeding the set maintenance Carry out boiler system maintenance by SERVICE interval authorised personnel Check add. boiler pump add. boiler temperature over 92 °C OVERHEAT ADD.BOILER increase Check settings Boiler operation mode “HEATING OFF”...
Page 68
Fault reports and their corrections No. Fault report Cause of fault Fault correction *Check sensor, replace as renew Check plug, replace as renew Sensor break; Value outside the HP - back flow sensor Check wiring incl. connections, replace measuring range (-50 - 1200°C) as renew ✆...
In accordance with regulations the installation and commissioning of the heat pump must be carried out by specialist personnel authorised by HERZ. If the installation or commissioning, a connection to other machines or changes of the technical specification were not carried out in accordance with regulations, this declaration loses its validity.