Page 3
The instruction and warnings given below concern the standard version; refer to the sale 1.2 DESCRIPTION BOOST is an electronic panel for direct start-up of operating programs for clean water, waste of 2 single-phase or three-phase pumps with water and minimum level management with over current and dry running protection.
• (400V ± 10% 50/60Hz x il BOOST -400/...) protected. The line must be protected with an • (230V ± 10% 50/60Hz x il BOOST -230) Earth leackage and magnetic switch measured in accordance with the regulations locally in force.
Installation BOOST 3.1 ASSEMBLING Fix the control panel for a stable support with If use an electric screwier pay attention not to screws and screw anchor using the holes spoil the thread or the screws. arranged in the box. After the fixing, remove every plastic or metallic To fix the cables in their terminals use a tool surplus (ex.
Installation BOOST 3.2 ELECTRICAL CONNECTIONS BOOST 230 display N L C N L C 1 2 3 C Alarm output selector (J2/J3) 12 Vcc output free contact N.O. 230 V 50÷60 Hz...
Page 8
(P1 and P2). IMPORTANT! The BOOST control panel is not intended as a reading instrument, therefore the value of the current absorption detected and shown on the display may differ from the actual value by ±10%. For an accurate verification of the current absorption, use a suitable reading instrument.
Installation BOOST 3.4 ADJUSTMENTS AND SETTINGS PARAMETERS SETTING AND CONTROL PANEL OPERATIVITY TRIMMER 1 TRIMMER 2 TRIMMER 3 To set the maximum absorbed current parameters At the end of this phase, by pressing the “AUT” (pump 1 and pump 2) and the sensitivity of the...
Installation BOOST 3.5 DIP-SWITCH SETTING SW1 DIP-SWITCH DIP-SWITCH 1 - PROGRAM SELECTION The panel is set as standard with dip-switch 1 in the “OFF” position. To access the menu and select the programs on display, set dip-switch 1 to the “ON” position with the panel on (see “PROGRAMS SETTING”).
Installation BOOST 3.6 PROGRAMS SETTING ACCESS TO PROGRAMS DIP-SWITCH 1 To access the menu and select the programs on display, set dip-switch 1 to the “ON” position with panel on. PROGRAMS SETTING To select the program to be set, scroll through the sequence with the “AUT”...
Page 12
Installation BOOST PROGRAM DESCRIPTION PUMP 1 MAXIMUM CURRENT (default: 10A) Setting of the threshold value of the maximum absorbed current, below which the panel intervenes stopping the pump 1 and activating the alarms. CHANGE PUMP 1 MAXIMUM CURRENT 1 0 0...
Page 13
Installation BOOST PROGRAM DESCRIPTION CLEAN WATER (DEFAULT) Preset program for operation with pressure switches, floats for clean water or CLC level probes (see application example 1). WASTE WATER Preset program for operation with floats for waste water or CLC level probes (see application example 2).
Page 14
Installation BOOST 3.7 TRIMMER SETTINGS If you want to modify the threshold value of PROTECTION DELAY the maximum motors absorbed current or the The pumps protections switching sensitivity of the CLC input level probes, you delay has been set at 5 sec.
General use BOOST 4.1 KEYPAD AND LIGHTS INDICATIONS BOOST CONTROL PANEL blue light indicating power network presence and powered panel. ALARM red light to indicate a general alarm and pump stop (min and max Amp, min or max level and dry running).
Page 16
General use BOOST 4.2 ALARMS LED SIGNALING DEACTIVATION All alarms are displayed on the If the panel is in alarm and you control panel (red led flashing) and want to silence it, press the “0” activate the following outputs: button twice.
Page 17
General use BOOST DISPLAY ALARMS To view the type of alarm, turn off the ignition, The display will show the alarm code present open the door and turn it on again. (see table below). CODE ALARM CODE ALARM AL 1...
General use BOOST 4.3 TYPICAL INSTALLATIONS EXAMPLE 1 p 3 o n p 4 o f f p 5 o f f start/stop start/stop G1 optional, if not used it must be jumpered. Pr 1 Pr 2 start/stop start/stop start...
Page 19
General use BOOST EXAMPLE 2 p 3 o f f p 4 o n p 5 o f f start start stop EXAMPLE 3 p 3 o f f Pr 1 Pr 2 start/stop start/stop p 4 o f f p 5 o n G1 optional, if not used it must be jumpered.
“0” button. Turning the main switch interlocking door in “OFF” position. 5.2 SERVICE BOOST does not require any routine maintenance DANGER! provided that their working limits are observed. Make sure that BOOST is...