AFRISO ACT 443 ProClick Installation And Operating Manual

Constant temperature controller

Advertisement

Quick Links

INSTALLATION AND OPERATING MANUAL
AFRISO Sp. z o.o.
Customer Service Team
Szałsza, ul. Kościelna 7
tel. 32 330 33 55
42-677 Czekanów
zok@afriso.pl
www.afriso.pl
NOTE
The product may only be used if you have fully read and understood these operating instructions. The manual is also
available on the AFRISO websites in the Internet.
WARNING
The product may only be mounted, commissioned and disposed of by qualified, specially trained staff.
Electrical work should always be entrusted to a qualified electrician.
Alterations performed by unauthorized staff may cause a threat and are forbidden for safety reasons.
The product is powered by 230 V AC. This may cause severe injuries or death.
Do not let the product go into contact with water.
Do not alter the product in any way.
Before mounting the product please read the manual of the mixing valve.
APPLICATION
Used in water based cooling and heating systems. Mounted directly on 3- and 4-way mixing valves. Maintains a constant
temperature of the medium in the range of 10÷90°C. Additionally, the product can also control a circulation pump.
SCOPE OF DELIVERY
1.
ACT 443 ProClick constant temperature controller equipped with two temperature sensors with a pipe mounting
adapter, a knob with a double-sided scale ("from 0 to 10" and "from 10 to 0"), as well as an electric cable with
a plug and a circulation pump control cable.
2.
Installation and operating manual.
3.
Mixing valve mounting manual.
CONSTRUCTION
ProClick system
disconnecting pushbutton
Colour display
HELP button
Fig 1. Construction of the ACT ProClick constant temperature controller
SETTINGS
1. Initiating the controller settings
Take off the knob
(Fig.
8) and then press and hold the
Fig. 8. Controller
description
2. Language selection
Polski
Select the required language using the
the
button.
3. Selection of operating mode
Select the operating mode of the system - heating or cooling.
4. Diagram selection
Select the appropriate diagram in accordance with the mounting position of the mixing valve in the system.
The available diagrams are: mixing valve mounted on the heat source return pipe
(Fig.
10), or on a 4-way valve
(Fig.
11).
5. Opening direction
After selecting the appropriate diagram, the next step is to select the direction of opening the valve. When
the ACT 443 ProClick constant temperature controller is mounted on the supply pipe to maintain a constant
temperature of the heating medium entering the system, the direction of operation of the controller should
be chosen to ensure that rotating the valve sleeve in the chosen direction increases the flow of medium from
the heat source into the system. The
setting indicates controller operation to the right – clockwise. The
setting indicates controller operation to the left – counter clockwise.
6. Temperature setting for heating and cooling mode
The next step is setting the temperature for heating mode. Select the minimum temperature (Tmin), the
maximum temperature (Tmax) and the required medium temperature to be maintained after the mixing
valve in the range from Tmin to Tmax. After setting the temperatures for heating mode, set the temperatures
for cooling mode. The
graphic symbolizes the exit from the settings and return to the initial screen.
7. Selecting the scale
In the last step, you need to select the right scale, either "0 to 10" or "10 to 0", corresponding to the chosen
diagram
(Fig.
9,
Fig.
10,
Fig.
11). To change the scale, you need to lift up the plate, and put it on again facing
the other side.
953.001.0080 5 Version: 09.2024
ACT 443 ProClick constant
temperature controller
Control buttons
Knob
Double-sided scale
Manual mode pushbutton
and
buttons for 5 seconds.
Colour display
USB maintenance connector
Exiting the settings/menu
Confirming selection
Navigating the menu, decreasing setting
values
Navigating the menu, increasing
setting values
Help button
Manual mode pushbutton
Knob with a scale
and
buttons, confirm your choice with
(Fig.
9), on the supply pipe
MOUNTING AND USAGE
The controller can be mounted on the valve in four different positions
orient itself horizontally. The blue ring with indicator must point upwards. If it does not, pull off the knob and blue
ring, then mount it back with the indicator pointing upwards.
Fig. 2. Possible mounting positions
Mounting/dismounting the controller on the ARV
Vario ProClick mixing valve
To mount or dismount the controller, press and hold
the ProClick system pushbutton (1), and then slide the
actuator on or off the valve spindle.
1
2
Rys. 4. Fig. 4. Mounting/dismounting of the ACT ProClick
controller on the ARV Vario ProClick valve
ELECTRICAL CONNECTIONS
Fig. 6. T1 and T2 sensor connection block
1. The T1 and T2 temperature sensors should be mounted in accordance with the chosen diagram
Fig.
11) by using the adapters included, or specially prepared sleeves.
2. Then, connect the sensors to the included connection block in accordance with
3. Connect the circulation pump to the proper controller connection block
1
2
4. Connect power to the device using the power cable with a plug.
page
3
4
T2
T1
Fig. 9. Diagram with the ARV Vario ProClick mixing valve mounted on the return to the heat source, in order to
protect the heat source against low-temperature corrosion
The circulation pump will be switched on after the set heat source temperature (T2) is exceeded. The default
value is set at 50°C. This setting can be altered through the S3.2 parameter.
T2
Fig. 10. Diagram with the ARV Vario ProClick mixing valve mounted on the supply pipe to maintain a constant
temperature of the medium flowing to the system
The required mixed temperature setting can be changed through pressing and holding both the
buttons for 1 second, without having to go through the whole menu.
T2
Fig. 11. Diagram with a 4-way mixing valve mounted in order to protect the heat source against low-tempe-
rature corrosion
When selecting the diagram with the 4-way valve, the default minimum return temperature (T2) is 50°C.
This setting can be altered through the S3.2 parameter. When this temperature is reached, the controller will
turn on the circulation pump and start controlling the system supply temperature.
(Fig.
2), the display will always automatically
Fig. 3. Improper mounting position
Mode of operation of the ACT constant temperature
controller
Switching between automatic and manual mode can be done
using the manual mode pushbutton. When the pushbutton
is in the upper position, the controller works automatically.
When the pushbutton is pressed down, manual operation,
meaning freely turning the knob of the controller, is enabled.
Fig. 5. Operation mode pushbutton
Fig. 7. Circulation pump connection block
Fig.
(Fig.
7).
ARV Vario ProClick
L
ARV Vario ProClick
T1
L
T1
(Fig.
9,
Fig.
10,
6.
Heat
source
on the
right
Heat
source
on the
right
and
Heat
source
on the
right

Advertisement

loading
Need help?

Need help?

Do you have a question about the ACT 443 ProClick and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for AFRISO ACT 443 ProClick

  • Page 1 The required mixed temperature setting can be changed through pressing and holding both the the ACT 443 ProClick constant temperature controller is mounted on the supply pipe to maintain a constant buttons for 1 second, without having to go through the whole menu.
  • Page 2 The REACH regulation (1907/2006/UE). and S3.12). The full text of the EU Declaration of Conformity is available at the following web address: www.afriso.pl. - Source protection. When T2 < T2min (S3.11), the controller opens the mixing valve. When the temperature at MAINTENANCE sensor T2 rises above that set in S3.11, the controller returns to normal operation.