The purpose of this device description is to ensure optimum installation, commissioning, operation and maintenance of the PIREG-C2 and must be read prior to carrying out any of the actions described. Keep the device description handy and accessible to all users for possible referencing. Pass this manual on to future users of the PIREG-C2.
PIREG-C2. The appropriate temperature coefficient of the heat- ing conductor must be set at the PIREG-C2 by means of the DIP switches or via the interfaces. The tem- perature coefficient of the heating conductor must be positive over the entire temperature range. The...
La résistance ohmique apparente est intégrée dans le PIREG-C2. Le transformateur de courant doit être monté de telle sorte que les champs mag- nétiques de dispersion du transformateur de soudage ou d'autres champs de dispersion n'influ- encent pas la mesure.
The PIREG-C2 can conduct the calibration at room temperature (always taken to be 20°C) as well as at any other ambient temperature between 0 - 50 °C. The controlled is informed of the actual reference tem- perature from outside.
OK signal. The sealing controls are then released. During calibration steps 1 to 7, no "Start" signal may be given as otherwise the PIREG-C2 will interrupt the calibration with error 2.
PIREG-C2. At the beginning of the 8-point Tc correction, the "Calibration" LED flashes while the communication setup time at a cycle rate of 1 Hz, while the PIREG-C2 tries to establish the connection to the external ther- mometer.
OFF state. Single-point Tc correction has an OFF and an ON state. After the single-point Tc correction was started, the PIREG-C2 is in the OFF state. When the PIREG-D is in the ON state, the heating conductor is heated to the tempera- ture which was set as target value in the OFF state.
Start" signal is still applied (evaluation of the rising edge). If the DIP switch 10 is switched in the ON position for less than one second, the PIREG-C2 is set to the single-point Tc correction. If the pulse control was configured by command (KONF) for the calibration start input (5), the PIREG-C2 switches in the single-point Tc correction when a high-signal is applied for less than one second (...
The PIREG-C2 performs its own calibration for each heat conduc- tor, which is also stored separately. 3.2.3. Time log functions: The PIREG-C2 offers the possibility to record the time behaviour of a sealing process, e.g. to detect long-term changes (from V1.01/1.09/1.06). The time log functions are used to rec- ord the time behaviour of the sealing system, which essentially consists of the sealing transformer and heating conductor, during a sealing process.
OK range during the sealing process after the stabilisation time has ended the PIREG-C2 will go to error state with error 8. The stabilisation time begins as soon as the actual value has reached the temperature OK range. In the event of a change of the target value by more than 2 °C, the stabilisation period is restarted.
- Variant 1: Under variant 1, the PIREG-C2 monitors the heating time to a maximum value. If the actual value of the temperature does not reach the temperature OK range within the set heating time, the PIREG-C2 switches to the error state with error 8.
R20 value monitoring and sets the OK range around the stored reference R20 value. If the currently calibrated R20 value of the controller is outside the OK range, the PIREG-C2 will go to the error state with error 10.
- Temperature coefficient correction range ex- 3.1.8 and 3.1.9. ceeded or - Parameter error: continuity and dynamics of the 3.1.1. selected temperature coefficients in relation to the temperature range. 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 15 of 66...
PIREG-C Figure 7: Error areas 3.4.9. Error memory: The PIREG-C2 has an error memory in which the last 100 error events are stored. The error memory can be read out by command (FESP) and cleared by command (FESL). The respec- tive error event is stored together with the value of the operating hours counter at the time of the error, so it can be linked to a time.
DIP switches (factory setting). The other is extended operation via the RS232 (1), RS485 (2) and USB interfaces (3), with which the PIREG-C2 is equipped. Combinations of both types of operation are possi- ble. When operating via an RS232, RS485 or USB interface, extended adjustments are possible, for in- stance freely selectable temperature coefficients and temperature ranges.
- For the 500°C temperature range the points are: 50, 100, 150, 200, 250, 300, 350 and 400 °C. At each step the actual temperature of the heating conductor is reported back to the PIREG-C2 as a tar- get value or directly as a measured value of the external thermometer from outside. Each individual set- ting point is checked immediately when a maximum deviation of ±20 % is recorded (error 13).
Tc correction is carried out outside the standard calibration and is started from the OFF state. Single-point Tc correction has an OFF and an ON state. After start-up the PIREG-C2 is in the OFF state. When the PIREG-D is in the ON state, the heating conductor is heated to the temperature which was set as target value in the OFF state.
PIREG-C2 switches in the calibration state. 4.3.3. Reset input: When a high signal is applied to the reset input (7), the PIREG-C2 is reset to the state after power-on. This allows you to leave the error state without Reset switching off the mains voltage.
4.5.3. Switch 3 Heating time of the automatic temperature coefficient correction: When the DIP switch 3 is switched in the ON position in the Reset state the PIREG-C2 will adopt the value set at the DIP switches 6 to 10 (0…310 s in 10 second steps) as the heating time for the automatic temperature coefficient correction.
5.1.2. Addressed RS232 communication: Communication via the RS232 interface can also be ad- dressed. This allows the RS232 interfaces of up to three PIREG-C2 to be connected in parallel. In this way, a communication partner can communicate with up to three PIREG-C2 via an RS232 interface. The addressing of the RS232 communication is switched on and off by command (KOKO).
Page 23
Start character for short set: Start character for control set and long set: Device ad- 0- 250 range for the individual device addresses of the PIREG-C2. The address 0 is dress GA: the factory setting. 255, at this address, all the PIREG-C2s connected to a bus can be addressed at the same time.
Tc correction is started. While the communication is being triggered, the PIREG-C2 sends the request telegram up to four times to the thermometer if it doesn’t receive a valid reply before. The maximum communication setup time results from the transmission interval time.
Syntax: Acknowledgement: Short set, function field FF, bit 4 = 1 Description: The PIREG-C2 transmits this acknowledgement if the code of the function field FF or the command index BI is unknown to the controller. Example Message: 10 21 10 31 16...
UIMW Querying the samples of Ur and Uir and calculated of the effective values 71h 5.4.38. of Ur and Uir VERS Querying the device and both program version of the PIREG-C2 controller 69h 5.4.39. X WESE Setting the factory settings 0Ch 5.4.40.
OK range around the nominal value is set with lower limit "uuu" (5…99K) and upper limit "ooo" (5…99 K) in K. In variant 1, the actual value of the PIREG-C2 must have reached the temperature OK range before the heating time "ttt" has expired in 0.1 s (0 ... 99.9s). In variant 2, the actual value must have reached the temperature OK range within the time window "sss"...
Description: Querying the setting of the DIP switches of the PIREG-C2. The DIP switches have the same function as the setting switches. The KONF command is used to select whether the DIP switches or the setting switches are to be used.
Setting and querying the setting switches of the PIREG-C2. The setting switches have the same function as the ten DIP switches on the PIREG-C2 without bus system. The KONF command is used to select whether the DIP switches or the setting switches are to be used.
Page 31
- Tc3= „±cccc“ in 0.01x10 (-9999…+9999) At the same time, the PIREG-C2 also checks the progress of the resistance, given by the stored temperature coefficients, for continuity and dynamics in the -20 …+600 °C tem- perature range. As a response, the PIREG-C2 provides the temperature range "sss" for continuity and "ddd"...
OK or error acknowledgement; response time max. 6 ms Release: not in the On or calibration state Setting and querying of the settings of the error configuration of the PIREG-C2 controller. Description: With the error configuration the following error messages can be activated and deactivat- ed at the PIREG-C2.
OK or error acknowledgement; response time max. 225 ms Release: not in the On or calibration state Clear the contents of the error memory with the status z=1. The PIREG-C2 stores the last Description: 100 error events. After deletion, all values of the memory locations are zero.
2= too large with temperature monitoring: 3= too small 4= too large 5= heating time exceeded with heating monitoring: 6= heating time fallen below Temperature jump: 7= downwards 8= upwards 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 34 of 66...
Syntax: Read: Control set, BI = 6Bh RS485: Response: Long set with DB0 and DB1 H byte L byte Description: Querying the device type "ttt" (line voltage,...) of the PIREG-C2 controller Example Read: LGTYP Response: AGTYP 200 RS232/USB: Example Read:...
With the value "000" for the heating time "ttt", the heating time limit is switched off. If the set maximum heating time is exceeded in the ON state, the PIREG-C2 goes to error state with error 2 and stops heating.
Long set with DB0 and DB1 H byte L byte Description: Querying the current actual temperature value "iii" in °C of the PIREG-C2. The actual value "iii" is limited to a maximum of 999 and negative actual values are set to zero. Example Read:...
H byte L byte H byte L byte H byte L byte ±aaaa defg DB15 DB14 DB13 DB12 DB11 DB10 H byte L byte H byte L byte H byte L byte ±cccc ±bbbb g3 g2 g1 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 38 of 66...
Description: Querying the following parameters of the calibrated calibration (1...8) of the PIREG-C2 controller: - Settings "defg" (see below) - Reference temperature "bbb" (0...50, 255 with variable reference temperature) in 1 °C - Temperature range "ttt" (100...500) in 1 °C - Temp.
On or calibration state Description: Setting and querying the communication configuration of the PIREG-C2 controller. The communication configuration is used to make the following additional settings for the RS232, RS485 and USB interfaces and the respective communication:...
Page 41
Setting and querying the configuration of the PIREG-C2. The configuration determines whether the temperature setpoint of the PIREG-C2 is controlled via the target value input or via the serial interfaces, which setting elements are used, how the alarm and OK out-...
“zzz” (0…99.9s) in 0.1s of the communication monitoring of the interface with the number “n” (1=RS232, 2=RS485 and 3=USB) The PIREG-C2 controller switches to an error state (error 9) if the communication moni- toring is activated and there is no communication via the interface for a time longer than the set downtime.
8-point Tc correction during calibration and the single-point Tc correction using the external thermometer. After the heating time has elapsed, the PIREG-C2 moves to the next temperature step in the 8-point Tc correction or ends the single-point Tc correction.
"uuu” (1…100) and the upper limit "ooo" (1…100) are used to define an OK range for the P-factor of the controller determined during the calibration. If the P-factor of the controller is outside the OK range, the PIREG-C2 controller switches to the error state (error 10).
“ooo” in % (5...100), an OK range is defined around the reference R20 value for the R20 value (in 0.01 Ω) of the controller currently determined during calibration. If the current R20 value of the controller is outside the OK range, the PIREG-C2 controller switches to the error state (error 10). (from V1.01/1.09/1.06) The reference R20 value monitoring is only carried out if the reference R20 value is de- fined by command (RHZL) for the respective calibration.
Setting and querying the temperature setpoint "sss" in °C of the PIREG-C2. Depending on the selected configuration of the PIREG-C2, either the voltage at the setpoint input or the setpoint specified with this command is used as setpoint. This command is only effec- tive if the setpoint is controlled via the interfaces with the SKONF command.
Syntax: Write: Long set with DB0, BI = 3Ah RS485: Response: short set, OK or error acknowledgement; response time max. 1 ms Release: in all states (effectiveness depends on state) 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 47 of 66...
In RS485 communication, the nine long sets of the response are sent one after the other with a pause of 3ms each. Example Read: LTKEI RS232/USB: Response: 1;0;0251;0273 1;1;0500;0569 … 1;8;2400;2761 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 48 of 66...
"ooo" in K (5…99 K). If the actual value leaves this range during sealing, once the range has already been reached the PIREG-C2 controller goes into error (error 8). 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 49 of 66...
OK range. If the actual value leaves the temperature OK range during the stabilisation time, the PIREG-C2 controller does not go into error. In the event of a change of the target value by more than 2 °C, the stabilisation period is restarted.
- Actual temperature value “iii” in °C of the PIREG-C2 at the beginning of the off-state. The actual value “iii” is limited to a maximum of 999 and negative actual values are set to zero.
Control set, BI = 37h RS485: Response: Long set with DB0 k3 k2 k1 k0 b3 b3 b1 b0 Description: Querying the state of the PIREG-C2 with the following assignments: Assignment Operating state: 0= Initialisation 4= Error state 1= OFF state...
Querying the "zzzzzzz" (0...9999999) sealing cycles performed by the PIREG-C2 for the stored calibrations (parameters "n"=1...8) and the total number of "ggggggggg" (0…999999999) sealing cycles performed by PIREG-C2 with the value zero for the pa- rameter "n". The calibration cycle counters (1...8) are set to zero by transferring the parameter "z" with the respective number (1...8) of the calibration cycle counter.
6. Installation and commissioning Firstly, check that the stated voltage of the PIREG-C2 power line matches the power line voltage being used, and that the transformer primary current matches the controller's load current capability. EN: For safe operation, the PIREG-C2 resistance temperature controller may only operate in symmetrical TN and TT networks.
After successful calibration, the PIREG-C2 will return to the OFF state and be on standby ( Fig- ure 1). If "Store calibration" is chosen as calibration mode, the PIREG-C2 will return to the off or error state after the power is switched on and will wait for the "Calibration start" signal. The alarm and calibration LEDs may be off, on or flashing.
- Protéger le transformateur de courant et acheminer les conducteurs de manière à ce qu’ils ne soient pas en contact direct avec des bornes sous tension ou avec le bus. 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 57 of 66...
The temperature of the heating conductor can only be determined by the PIREG-C2 as the mean of all parts of the heating conductor. If any individual parts of the heating conductor are exposed or otherwise not in contact with any heat dissipating areas, they will heat up faster than those sections of the heating conductor that are able to dissipate their heat.
Nominal current: = 5 A (Actuator Internal thyristors) Actuators: Internal thyristors: Actuator with antiparallel thyristors on an internal heat sink in the PIREG-C2 Continuous heating, maximum load current: = 5 A - 100 % operation factor Impulse heating, maximum load current: = 25 A - max.
Page 60
Initialisation: After power on or reset signal: 500 ms Power interruption: During an interruption to the line voltage, the PIREG-C2 switches to 80 ms the error state or starts with a reset once the line voltage has been re-established. Reset Stop heating 5...25 ms...
35-mm mounting rails, in accordance with EN 60715 (EN 50022) Dimensions (W x H x D): 70 x 42,5 x 103,5 mm Weight: 180 g Shock resistance: 10 g 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 61 of 66...
Special version number (assigned by manufacturer) 0= Standard version Bus system 0= without bus system 1= ProfiNet 2= EtherNet/IP Line voltage 2= 100...127 V / 200...240 V 4= 380...415 V 16502 PIREG-C2 Gerätebeschreibung 220627 - EN.docx/ Page 62 of 66...
10. Application note 10.1. Application instructions The following application instructions are available for the PIREG-C2 which should simply operation of the PIREG-C2. 8-point Tc correction: Operation of the 8-point Tc correction, which is an additional component of the calibration of the PIREG-C2 to perform a temperature coefficient correction for the heating conductor (...
11. Disposal EN: Do not dispose of the device with household waste! The PIREG-C2 and its components must be disposed of via the local collection points for electronic waste in accordance with the WEEE Directive 2012/19/EU on waste electrical and electronic equipment.
Need help?
Do you have a question about the PIREG-C2 and is the answer not in the manual?
Questions and answers