Airwell YDAX-140H-09T35 Technical Manual

Airwell YDAX-140H-09T35 Technical Manual

Floor standing type
Hide thumbs Also See for YDAX-140H-09T35:

Advertisement

Quick Links

Tecnical manual
Floor Standing Type air conditioner
SDMX R32
English
23.AW.SDMX.048.R32.TM.EN.03.10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the YDAX-140H-09T35 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Airwell YDAX-140H-09T35

  • Page 1 Tecnical manual Floor Standing Type air conditioner SDMX R32 English 23.AW.SDMX.048.R32.TM.EN.03.10...
  • Page 2: Table Of Contents

    Table of Contents Page 1. Specifications ....................3 Model Reference General Specifications Dimensional Drawings Centre of Gravity Electrical Wiring Diagrams Refrigerant Cycle Diagrams Capacity Tables Capacity Correction Factor for Height Difference Noise Criterion Curves Electrical Characteristics 2. Product Features ................... 26 Operation Modes and Functions Remote Controller Functions 3.
  • Page 3: Specifications

    Specifications Contents Model Reference ....................4 General Specifications ...................5 Dimensional Drawings ..................7 Centre of Gravity ....................9 Electrical Wiring Diagrams ..................10 Refrigerant Cycle Diagrams ................13 Capacity Tables ....................14 Capacity Correction Factor for Height Difference ..........22 Noise Criterion Curves ..................23 Electrical Characteristics ..................25...
  • Page 4: Model Reference

    1. Model Reference Refer to the following table to determine the specific indoor and outdoor unit model number of your purchased equipment. Outdoor Unit Model Indoor Unit Model Capacity (Btu/h) Power Supply YDAX-140H-09T35 SDMX-140N-09M35 380-415V~, 50Hz,3Ph  Page 4 ...
  • Page 5: General Specifications

    2. General Specifications SDMX-140N-09M35 Indoor Model YDAX-140H-09T35 Outdoor Model Power supply V-Hz-Ph 380-415-3-50 Rated Power Input 6900 Rated Current Starting current Model KTQ420D1UMU Type ROTARY Brand GMCC Capacity 13700 Input 3700 Compressor Rated current(RLA) 7.02 Locked rotor Amp(LRA) Thermal protector...
  • Page 6 Type Refrigerant Charged quantity Design pressure 4.3/1.7 ɸ 9.52/ ɸ 15.9(3/8”/5/8”) Liquid side/ Gas side mm(inch) Refrigerant piping Max. refrigerant pipe length Max. difference in level Connection wiring 1.5x4 Plug type no-plug Thermostat type Remote Control ℃ Operation temperature 17-30 Indoor(cooling/ heating) ℃...
  • Page 7: Dimensional Drawings

    3. Dimensional Drawings Indoor Unit  Page 7 ...
  • Page 8 Outdoor Unit Double Fan Outdoor Unit Model unit 1333 1045 YDAX-140H-09T35 inch 37.48 16.34 52.48 41.14 24.96 15.9 17.99  Page 8 ...
  • Page 9: Centre Of Gravity

    4. Centre of gravity YDAX-140H-09T35  Page 9 ...
  • Page 10: Electrical Wiring Diagrams

    5. Electrical Wiring Diagrams Indoor unit Abbreviation Paraphrase Yellow-Green Conductor HOR-SW Horizontal Fan VER-AC MOTOR,VER-DC MOTOR Vertical Fan L or 1 LIVE 2(N) NEUTRAL Indoor Room Temperature Coil Temperature of Indoor Heat Exchanger 3(5 ) DC MOTOR Y/ G DRIVE R MODLE DC MOTOR Y/ G DRIVE R MODLE...
  • Page 11 Outdoor Unit Abbreviation Paraphrase COMP Compressor CAP1,CAP2 Fan Motor Capacitor AC Current Detector Electric Expansion Valve DC FAN1,DC FAN2 Outdoor DC Fan AC FAN1,AC FAN2 Outdoor AC Fan HEAT_Y,HEAT_D Crankcase Heating H-PRO High Pressure Switch L-PRO Low Pressure Switch 4-Way Valve Exhaust Temperature Sensor Condenser Temperature Sensor Outdoor Ambient Temperature Sensor...
  • Page 12 YDAX-140H-09T35  Page 12 ...
  • Page 13: Refrigerant Cycle Diagrams

    6. Refrigerant Cycle Diagrams Pipe Size (Diameter:ø) Piping length(m/ft) Elevation(m/ft) mm(inch) Model No. Additional Refrigerant Rated Max. Rated Liquid Max. YDAX-140H-09T35 15.9(5/8) 9.52(3/8) 5/16.4 30g/m (0.32oz/ft) 65/213.3 30/98.4  Page 13 ...
  • Page 14: Capacity Tables

    7. Capacity Tables 7.1 Cooling ID WB 16.0 18.0 19.0 22.0 INDOOR (℃) OUTDOOR AIRFLOW DB(℃) ID DB (CMH) 23.0 25.0 27.0 29.0 23.0 25.0 27.0 29.0 23.0 25.0 27.0 29.0 23.0 25.0 27.0 29.0 (℃) 14.70 14.69 14.84 14.99 15.46 15.79 15.79...
  • Page 15 15.02 15.02 15.17 15.33 15.79 15.79 15.79 15.94 16.17 16.17 16.17 16.17 17.19 17.19 17.19 17.19 0.73 0.83 0.98 1.00 0.58 0.68 0.76 0.86 0.50 0.60 0.69 0.78 0.34 0.42 0.51 0.59 3.37 3.37 3.37 3.37 3.35 3.35 3.35 3.35 3.35 3.35 3.35...
  • Page 16 15.33 15.48 15.63 15.78 16.12 16.12 16.12 16.27 16.53 16.53 16.53 16.53 17.54 17.54 17.54 17.54 0.75 0.85 1.00 1.00 0.59 0.69 0.78 0.98 0.51 0.61 0.70 0.80 0.33 0.42 0.51 0.61 3.43 3.43 3.43 3.43 3.43 3.43 3.43 3.43 3.42 3.42 3.42...
  • Page 17 7.2 Heating [SI_Unit] HEATING PERFORMANCE AT INDOOR DRY BULB TEMPERATURE INDOOR TC:TOTAL CAPACITY IN KILOWATTS PI: TOTAL POWER IN KILOWATTS AIRFLOW OUTDOOR Indoor Conditions (DB ℃ ) Indoor Conditions (DB ℃) (CMH) DB(℃) 16.0 20.0 22.0 24.0 16.0 20.0 22.0 24.0 -15.0 13.06...
  • Page 18 8. . Capacity Co ection Factor for Height Difference Model Pipe Length (m) Cooling 0.880 0.838 0.796 Indoor 0.918 0.889 0.846 0.804 Upper than 0.956 0.927 0.898 0.855 0.812 Outdoor 0.995 0.966 0.937 0.907 0.864 0.820 Height difference 1.000 0.971 0.941 0.912 0.868...
  • Page 19: Noise Criterion Curves

    9. . Noise Criterion Curv Indoor Unit Notes: -Sound measured at 1m away from the noisiest location of the unit. -Data is valid at free field condition -Data is valid at nominal operation condition -Reference acoustic pressure OdB = 20µPa -Sound level will vary depending on a range of factors such as the construction -(acoustic absorption coefficient) of particular room in which the equipment is installed.
  • Page 20 -Reference acoustic pressure OdB=20µPa -Sound level will vary depending on arrange off actors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed. -The operating conditions are assumed to be standard. YDAX-140H-09T35  Page 20 ...
  • Page 21 10. 0. Electrical Characterist MFGD-48HRFN8-RRD0W(GA) Model 3- - Pha Phase Power 380-415V~,50Hz Frequency and Voltage 32/25 Circuit Breaker/ Fuse (A) 5x2.5 Outdoor Unit Power Wiring (mm 4×1.5 Strong Electric Signal Indoor/Outdoor Connecting Wiring (mm Weak Electric Signal  Page 21 ...
  • Page 22: Product Features

    Product Features Contents Operation Modes and Functions ................27 Abbreviations ....................27 Safety Features ....................27 Digital Display ....................27 Fan ......................28 Cooling Mode .....................28 Heating Mode .....................29 Auto Mode ....................30 Drying Mode ....................30 Sleep Function .....................30 1.10 8°C Heating(Optional) .................30 1.11 Self Clean(Optional) ..................30 1.12 Follow Me(Optional) ..................30 1.13 Silence(Optional) ..................31 1.14 Auto-Restart ....................31...
  • Page 23: Noise Criterion Curves

    1. Operation Modes and Functions This function is active only when cooling mode is selected. It will detect if the compressor is being damaged by refrigerant leakage or by compressor overload. This is Abbreviation measured using the coil temperature of evaporator T2 when the compressor is in operation.
  • Page 24: Cooling Mode

    Auto operation 120 minutes. Cooling operation • If the following conditions are satisfied, the compressor ceases operation. Dry operation • When calculated frequency(fb) is less than minimum Heating operation limit frequency(FminC). • When protective time is more than or equal to ten Fan operation minutes.
  • Page 25: Heating Mode

    When evaporator temperature drops below a configured • Auto fan action in heating mode: value, the compressor and outdoor fan cease operation. Heating Mode(Heat pump units) 1.6.1 Compressor Control 1) Reach the configured temperature • If the following conditions are satisfied, the compressor ceases operation.
  • Page 26: Auto Mode

    heating mode: hours, the temperature stops rising and the indoor fan is fixed at low speed. • T3 rises above TCDE1+4°C. • When heating, the temperature decreases 1°C(2°F) • T3 maintained above TCDE2+4°C for 80 seconds. (to not lower than 16°C(60.8°F)) every hour. After •...
  • Page 27: Silence(Optional)

    1.13 Silence(Optional) • Press “Silence” on the remote control to enable the SILENCE function. While this function is active, the compressor frequency is maintained at a lower level than F3. The indoor unit will run at faint breeze, which reduces noise to the lowest possible level. •...
  • Page 29 Installation Contents Accessories ........................30 Installation Overview ..................31 Location Selection ....................32 Indoor Unit Installation ..................33 Outdoor Unit Installation ..................34 Drainage Pipe Installation ...................35 Refrigerant Pipe Installation ................36 Vacuum Drying and Leakage Checking ..............37 Additional Refrigerant Charge ................38 Engineering of Electrical Wiring ................39 Test Operation ....................39...
  • Page 30: Accessories

    Accessories Name Shape Quantity Self-tapping screw (Used to fix the cord clamp of indoor unit after wire connection) Indoor unit installation Flat washers Bushing-sleeve cover Soundproof/insulation sheath Refrigeration Fittings (some models) Drain hose(some models) Band (some models) Drainpipe Fittings Drain joint (some models) Seal ring (some models) Remote controller Fixing screw for remote controller...
  • Page 31: Installation Overview

    1. Installation Overview-Indoor Unit Install the outdoor unit Install the indoor unit Perform a test run Evacuate the refrigeration system Connect the wires Page 31  ...
  • Page 32: Location Selection

    2. Location selection 2.1 Unit location selection can refer to installation manual. 2.2 DO NOT install the unit in the following locations: • Where oil drilling or fracking is taking place. • Coastal areas with high salt content in the air. •...
  • Page 33: Indoor Unit Installation

    3. Indoor Unit Installation 3.1 Service space for indoor unit 30cm (11.8in) or more 5cm (2in) or more 200cm (78.7in) or more Air-inlet Grid • Remove all of the accessories placed inside the bottom cavity of the indoor unit. • Check that all of the accessories match those found on 50cm (19.7in) the “Accessories”...
  • Page 34: Outdoor Unit Installation

    4. Connect a drain hose extension (not included) to the Model drain joint to redirect water from the unit during heating mode. YDAX-140H-09T35 • If the drain joint doesn’t come with a rubber seal (see Fig. B ), do the following: 4.3 Install Outdoor Unit 1.
  • Page 35: Drainage Pipe Installation

    5. Drainpipe installation the hole. This protects the edges of the hole and will help seal it when you finish the installation process. The drainpipe is used to drain water from the unit. Improper installation may cause unit and property damage. CAUTION: •...
  • Page 36: Refrigerant Pipe Installation

    6. Refrigerant Pipe Installation 90° Oblique Rough Warped 6.1 Maximum length and drop height Ensure that the length of the refrigerant pipe, the number of bends, and the drop height between the indoor and outdoor units meets the requirements shown in the following table.
  • Page 37: Vacuum Drying And Leakage Checking

    • 7. Vacuum Drying and Leakage Be sure to use two spanners and proper torque to fasten the nut, too large torque will damage the Checking bellmouthing, and too small torque may cause leakage. Refer the following table for different pipe 7.1 Purpose of vacuum drying connection.
  • Page 38: Additional Refrigerant Charge

    8. Additional Refrigerant Charge 4. Rain water might penetrate into pipeline during construction. • After the vacuum drying process is carried out, the additional refrigerant charge process need to be performed. Procedures of special vacuum drying are as follows: • The outdoor unit is factory charged with refrigerant.
  • Page 39: Engineering Of Electrical Wiring

    9. Engineering of Electrical Wiring 10. Test Operation 1. Highlights of electrical wiring installation 1. The test operation must be carried out after the entire installation has been • All field wiring construction should be finished by qualified electrician. completed. •...
  • Page 40 unit do not disturb your neighbors or pose a safety hazard. 3. Drainage Test a. Ensure the drainpipe flows smoothly. New buildings should perform this test before finishing the ceiling. b. Remove the test cover. Add 2000ml of water to the tank through the attached tube.
  • Page 42 GROUPE AIRWELL 10,Rue du Fort de Saint Cyr, 78180 Montigny le Bretonneux - France www.airwell.com 23.AW.SDMX.048.R32.TM.EN.03.10...