INDEX USER MANUAL – XSI-B-230V-5K VER. 2405.14 ENGLISH USER MANUAL XSI-B-230V MPPT 230V SOLAR INVERTER XSI-B-230-5K-MPPT Technical information on this manual is property of XMART This manual Information cannot be copied or distributed totally ▪ or partially without written approval of XMART. XMART can introduce modifications in their products or manuals without further notice.
INDEX USER MANUAL – XSI-B-230V-5K 1. GENERAL SAFETY INSTRUCTIONS WARNING: It is required to read and understand this manual. Follow all instructions given in this manual for starting up and operating this product. Only qualified technician must start-up, operate and maintain this product. Keep manuals as a guide for future consults. Neither manufacturer, nor distributor, will never be responsible for any accident produced by lack of knowledge or negligent practices at the moment of install, starting up or maintain this product.
INDEX USER MANUAL – XSI-B-230V-5K 2. SAFETY, QUALITY AND PERFORMANCE STANDARDS SAFETY - LOW VOLTAGE DIRECTIVE 2014/35/EU EN 62109-1: 2010 EN 62109-2: 2011 ELECTROMAGNETIC COMPATIBILITY – EN 61000-6-4: 2007+A1: 2011/IEC 61000-6-4: 2018 EMC DIRECTIVE 2014/30/EU EN 61000-6-2: 2017/ IEC 61000-6-2: 2016 EN 61000-3-12: 2011/ IEC 61000-3-12: 2011 EN 61000-3-11: 2000/ IEC 61000-3-11: 2017 CE compliant...
INDEX USER MANUAL – XSI-B-230V-5K 3. PRODUCT DESCRIPTION This unit is a multifunctional “off-grid” solar inverter with sine-wave output for 230Vac systems including an internal solar charger and AC charger. This unit can operate receiving energy from any of its 3 inputs: AC, Solar, and Batteries. A perfect inverter for hybrid “off-Grid” applications with capacities of 5KVA.
Page 6
INDEX USER MANUAL – XSI-B-230V-5K Multiple Inputs Operation Features: Sinewave output. AC Charger included. MPPT Solar Charger Cargador included. 0 mSec Transfer from AC Line to Batteries, bumpless operation for sensitive equipment. Adjustable charge current and 3 step smart recharge algorithm, to improve batteries lifespan. Design for 230Vac systems with selectable frequency (50Hz or 60Hz).
INDEX USER MANUAL – XSI-B-230V-5K 4. PARTS IDENTIFICATION Parts List 1. LCD 11. Breaker 2. Status LED 12. LCD Comm Port 3. Charge LED 13. Communication Port (Note 1) 4. Fault LED 14. Shared Current Port (Note 1) 5. Operations Keys 15.
INDEX USER MANUAL – XSI-B-230V-5K 5. INSTALLATION SAFETY INSTRUCTIONS WARNING: Before start checking information in this section, please be advised that checking and understanding safety and warning information from section 1 “Safety Instructions” is absolutely necessary. LIABILITY LIMITATION REACH AND LIABILITY LIMITATION: The preparation of the site, wiring and all protection devices must be supplied by end user and it will not be responsibility neither the inverter distributor nor the inverter technician in charge of the start-up, unless it has been previously agreed.
Page 9
INDEX USER MANUAL – XSI-B-230V-5K SITE INSPECTION AND INSTALLATION CONDITIONS REGULATIONS AND LEGAL DIRECTIVES It is necessary to check that installation site, wiring and power protection in the installation supplied by end user, fulfill technical parameters required by this manual, as well as local electrical regulation. A particular installation might accomplish with Inverter requirements but not with local directives and regulations.
Page 10
INDEX USER MANUAL – XSI-B-230V-5K Fasten the inverter using either M4 or M5 screws. Check image on the right for reference. Battery Connections It is recommended to install a Circuit Breaker that can open the battery circuit for connection and disconnection to the inverter and for maintenance tasks.
Page 11
INDEX USER MANUAL – XSI-B-230V-5K In the figure on the right, the recommended terminal for the battery cables is shown. The recommended D and L measurements for the terminal are displayed in the following table. Make sure each terminal is firmly attached to its respective cable. BATT VOLT MAX AMPS TORQUE...
Page 12
INDEX USER MANUAL – XSI-B-230V-5K AC INPUT CONNECTION Install a Circuit Breaker on the AC input cables (phase and neutral) to protect the circuit against overcurrent and to allow for circuit connection and disconnection during installation and maintenance. Select the input breaker with a rating 30% higher than the nominal current. Select cables according to the information in the table in this section.
Page 13
INDEX USER MANUAL – XSI-B-230V-5K Notas: • Make sure AC cables are connected with the correct polarity. Reversing the Line and Neutral connections could cause AC line short circuits if the inverters operate in parallel. • If you are powering the inverter with a generator, we recommend using one with twice the capacity of the inverter and that can handle the following parameters: Waveform: Sine wave Voltage range: 180 to 270 Vac...
Page 14
INDEX USER MANUAL – XSI-B-230V-5K Once all cables are connected, the inverter should be closed by placing the bottom cover in its position and screwing the 2 screws back in place, as shown in the figure on the right: REMOTE LCD - INSTALLATION LCD panel can be removed for remote installation and control of the equipment, communicating with the inverter via a standard network cable (not provided).
Page 15
INDEX USER MANUAL – XSI-B-230V-5K Connection: Connect the LCD Communication Port to the inverter using an RJ45 communication cable. This cable is not included with the inverter. This is the cable identified as 1 in the figure on the right. RJ45 Cable Specifications: - Recommended length: 2 meters (Do not exceed 5 meters) - Standard 1:1 connection of all pins between both ends of...
INDEX USER MANUAL – XSI-B-230V-5K 6. OPERATION MODES This inverter can operate in 4 main modes: Stand-By: Connected to the input power sources (AC and/or Solar), but with the power switch in <OFF>. Power Saving: If enabled, it allows the inverter to shut off its output when the consumption is very low. Line: Connected to the input power sources (AC and/or Solar) and with the power switch in <ON>.
Page 17
INDEX USER MANUAL – XSI-B-230V-5K Without AC input, solar input can recharge batteries. The inverter output is powered by solar input only. In this mode, the inverter is only Without AC input, solar input can recharge batteries. The connected to the solar power source. inverter output is powered by batteries and the solar input.
Page 18
INDEX USER MANUAL – XSI-B-230V-5K The inverter charges the batteries with the Grid and the solar input. The inverter charges the batteries only with the solar input. In this mode, the inverter will power its BYPASS MODE / output from the main AC line (Grid). The batteries can be charged either by the Grid or by the solar inputs.
Page 19
INDEX USER MANUAL – XSI-B-230V-5K 7. KEYBOARD & LCD Operations panel is located on the inverter front panel, consisting of an LCD screen, status and output indicator LEDs, operation buttons, and ON/OFF button. Output LEDs Indicator LEDs Operation Operation Buttons Buttons On/Off Button LEDS DESCRIPTION:...
Page 20
INDEX USER MANUAL – XSI-B-230V-5K LCD DESCRIPTION LCD screen can be divided into 4 areas to provide specific information about the inverter: (1) SETTING MENU PARAMETER / ALARMS INFORMATION / FAILURES Located in the upper left area, this area can display the ID of configurable function (when in configuration mode) or the alarm/error code (when an error or alarm occurs).
Page 21
INDEX USER MANUAL – XSI-B-230V-5K 1. FLOWCHART – INVERTER STATUS Located at the bottom of the screen. Graphically indicates the inverter's status and operating mode, as shown in the image on the right. AC INPUT DETECTED SOLAR INPUT DETECTED BYPASS ACTIVE Load is being powered by AC Line CHARGER IN OPERATION (LINE MODE) Batteries are charged by AC Line...
Page 22
INDEX USER MANUAL – XSI-B-230V-5K OUTPUT POWER DELIVERED (LOAD CONNECTED TO INVERTER OUTPUT) Graphically indicates the load level (as a percentage) connected to the INVERTER output: OVERLOAD Load power consumption exceeds Max. Capacity of the inverter OUTPUT ENERGIZED LOAD Load from 0 to 24% Load connected to the inverter output, represented by the bar on the screen, as shown in the images on the right.
Page 23
INDEX USER MANUAL – XSI-B-230V-5K BATTERY REPORT IN BATTERY MODE: Represents the remaining energy of the batteries. The thresholds for the different segments are determined by the individual battery voltages, varying with the percentage of load connected to the inverter, as shown in the following table. Load Percentage Battery Voltage LCD Display...
INDEX USER MANUAL – XSI-B-230V-5K 8. STARTUP AND OPERATION INSPECTION BEFORE STARTUP Make sure all wires are tightly connected to terminal block. Any loose connection will produce overheating, failures, and damage to the unit. Make sure all instructions of installation sections have been performed correctly. Verify wiring and Circuit Breakers are correctly installed.
Page 25
INDEX USER MANUAL – XSI-B-230V-5K Solar Input = 80V Output Voltage = 230V Load: Solar Input Voltage Between 50% & 75% Batteries: Being charged by Solar Input and AC Input. Charge between 75% & 100% PV Current = 2.5A Solar Input Current Remaining data stays the same Solar Input Power PV Power = 500W...
Page 26
INDEX USER MANUAL – XSI-B-230V-5K Load Total Power = 500W Source: AC & Solar Load Total Power = 500W Charging Power Source: Solar Load Total Powe =: 500W Source: AC Battery Voltage = 50V Output and Battery Voltages Output Voltage = 230V Battery Voltage = 50V Battery Voltage and Output Frequency...
Page 27
INDEX USER MANUAL – XSI-B-230V-5K Battery Voltage = 50V Load Connected to Inverter = 350VA Note: For load < 1KVA, it is displayed in VA on the screen. Battery Voltage and Load in VA Battery Voltage = 50V Load Connected to Inverter = 1.5KVA Note: For load ≥...
Page 28
INDEX USER MANUAL – XSI-B-230V-5K Energy Generated This Year = 3.88 Energy Generated This Year and Energy Consumed by Load This Year Energy Consumed by Load This Year = 9.88 MWh Total Energy Generated to Date = 38.8 MWh Total Energy Generated and Total Energy Consumed by Load Total Energy Consumed by Load to Date = 98.8 MWh...
INDEX USER MANUAL – XSI-B-230V-5K 9. CONFIGURATION Configuration menu provides access to the INVERTER's adjustable functions and parameters. It is activated by pressing the ENTER button for 3 seconds. Use keys to scroll through the menu. Select the desired value with the (Enter) key and confirm the selection.
Page 30
INDEX USER MANUAL – XSI-B-230V-5K BATTERY TYPE: Sets parameters for battery charger. AGM: For AGM battery (default) FLD: For Flooded battery USE: For special batteries. Charging voltages must be defined with parameters 26, 27, and 29. For Xmart LiFePO4 batteries, select USE battery type, and set parameters 26, 27, and 29 as explained in Annex 6.
Page 31
INDEX USER MANUAL – XSI-B-230V-5K AUTO-RESTART AFTER AN OVERLOAD EVENT AT THE INVERTER OUTPUT LTD: Disable (Default) LTE: Enable AUTO-RESTART AFTER AN OVERHEATING EVENT TTD: Disable (default) TTE: Enable OUTPUT FREQUENCY 50: Sets output frequency to 50Hz (default) 60: Sets output frequency to 60Hz OPERATION LOGIC AUTOMATIC: Allows the inverter to operate in Line Mode or Normal Mode as long as the AC Line is available.
Page 32
INDEX USER MANUAL – XSI-B-230V-5K AC CHARGER MAXIMUM CHARGE CURRENT: Sets the AC input recharge current: Available options: 2A, 10A, 20A, 30A (Default), 40A, 50A, 60A. LOW BATTERY LEVEL TO USE AC INPUT: Sets the battery voltage value at which the inverter will switch to using the AC input (when configured in "SBU"...
Page 33
INDEX USER MANUAL – XSI-B-230V-5K ALARM CONTROL: bON: Alarm enabled (default) bOF: Alarm disabled AUTO RETURN TO START DISPLAY: ESP: After 1 minute of no screen operation, it will return to the start screen. tEP: It will stay on the last screen selected by the operator. LCD BACKLIGHT: LON: Screen backlight ON LOF: Screen backlight OFF...
Page 34
INDEX USER MANUAL – XSI-B-230V-5K BYPASS FUNCTION: BYF (Bypass Forbidden): If selected, Bypass is not allowed, therefore, the unit will not be able to enter in Bypass/ECO Mode. BYd (Bypass Disabled): If selected, when turning on the inverter, it will only be able to enter Bypass/ECO Mode if AC Input is available.
Page 35
INDEX USER MANUAL – XSI-B-230V-5K 3P1: Option for three-phase installations of inverters in parallel. This option should be configured on inverters connected to phase L1 (R). Refer to Annex 4of this manual for detailed information on the configuration, installation, and operation of these units in parallel systems.
Page 36
INDEX USER MANUAL – XSI-B-230V-5K BATTERY EQUALIZATION VOLTAGE Sets Battery Equalization Voltage Range: From 48VDC to 58.4VDC, 0.1VDC increment by click See Section 11. BATTERY EQUALIZATION for details about Battery Equalization Function. BATTERY EQUALIZATION TIME Sets Battery Equalization Time. Range: From 5 up to 900 minutes, 5 minutes increment per click Default 60 Min See Section 11.
Page 37
INDEX USER MANUAL – XSI-B-230V-5K DATA LOG ERASING: No Reset (Default Value): Does not clear the record data. Reset: Clears the record data. DATA LOGGING INTERVAL: Available values: 3min, 5min, 10min, 20min, 30min, and 60min Default Value: 10 min. Note: Maximum number of records is 1440 data entries, after which the log will begin to overwrite data starting from the first record.
Page 38
INDEX USER MANUAL – XSI-B-230V-5K USB FUNCTION SETTING: This inverter allows communication with external USB drives through its USB port. With this communication, the following functions can be performed: Inverter firmware update. Overwrite inverter settings by taking them from the disk. Export the data log.
Page 39
INDEX USER MANUAL – XSI-B-230V-5K USB FUNCTION ERROR MESSAGES If an error occurs during the execution of a USB Function, the corresponding error code will be displayed for 5 seconds, and then the LCD will return to the initial screen. Therefore, it is recommended to carry out these procedures carefully to confirm their success. Available error codes are shown in the following table.
Page 40
INDEX USER MANUAL – XSI-B-230V-5K 10. ERRORS & ALARMS CODES / TROUBLESHOOTING IMPORTANT: All alarm and errors are informed on the LCD by dedicated codes and symbols. ▪ ALARMS: Are usually represented by blinking codes or symbols. Audible alarm beeps are also intermittent for alarms. Alarm ▪...
Page 41
INDEX USER MANUAL – XSI-B-230V-5K ERROR (FAULT) CODES FAULT FAULT ERROR CONDITION CODE ICON Fan blocked - Inverter off Overheating Very high battery voltage Very low battery voltage Output short-circuit or high converter temperature Output voltage out of range Output overload (overload time out) Very high DC bus voltage DC bus soft start failure Overcurrent in the PFC...
Page 42
INDEX USER MANUAL – XSI-B-230V-5K TROUBLESHOOTING PROBLEM PROBABLE CAUSE & SOLUCION Automatically shuts down during startup Issue: Batteries discharged below 11.45V (per battery). Screen remains on for 3 seconds and Solution: Recharge the batteries in standby mode or replace batteries if then turns off damaged.
INDEX USER MANUAL – XSI-B-230V-5K 11. BATTERY EQUALIZATION The equalization function of the XSI has been included in the battery charger control to reverse negative chemical effects such as stratification, a condition where the acid concentration is higher at the bottom of the battery than at the top. Additionally, it helps removing sulfate crystals that may accumulate on the battery plates.
INDEX USER MANUAL – XSI-B-230V-5K 12. SPECIFICATIONS XSI-B - SOLAR INVERTER 230V - MPP (1/2) 5KP-48-MPP Out Capacity / Capacidad de Salida (VA) 5000 VA Output Capacity / Capacidad de Salida (W) 5000 W MAIN FEATURES / FUNCIONALIDADES Parallel / Operación paralela 9 units max Optional / Opcional Built-in Charger / Cargador incorporado MPPT...
Page 45
INDEX USER MANUAL – XSI-B-230V-5K XSI-B - SOLAR INVERTER 230V - MPP (2/2) 5KP-48-MPP CHARGERS (SOLAR & AC) Solar charger type / Cargador solar MPPT Charging procedure / Tipo de recarga 3 steps: 1-Constant Current (Bulk), 2-Constant Voltage, 3-Floating Bulk Charging / Voltaje cargador (Etapa Bulk) AGM: 58.4 VDC - AGM/GEL: 56.4 Floating Charging / Voltaje cargador (Etapa Floating) 54 VDC...
Page 46
INDEX USER MANUAL – XSI-B-230V-5K ANNEX 1. SOLAR PANELS ARRAYS SOLAR PANELS ARRAYS SUGGESTED FOR: XSI-B-230V-5K -MPP Suggestions based on 270W and 330W solar panels. ARRAY WITH XPV-270-30P PANEL INVERTER SOLAR INPUT INFO. / PANEL DATA / DATOS DEL PANEL DATOS DE LA ENTRADA SOLAR DEL INVERSOR Max.
Page 47
INDEX USER MANUAL – XSI-B-230V-5K ARRAY WITH XPV-330-30P PANEL INVERTER SOLAR INPUT INFO. / SOLAR PANEL INFO. / DATOS DE LA ENTRADA SOLAR DEL INVERSOR DATOS DEL PANEL SOLAR Max. Power Range (Vdc) I Max Power (Vdc) x MPPT (Vdc) (Vdc) (Adc) 4000...
Page 48
INDEX USER MANUAL – XSI-B-230V-5K ANNEX 2. BACKUP TABLES & RECHARGE TIMES BACKUP TABLES IMPORTANT: Backup times indicated in this section are approximate. Some of the values have been determined through laboratory tests, while others have been determined through calculations based on the discharge tables provided by the battery manufacturers. Backup times assume that Shutdown Voltage is 11.5VDC per battery.
Page 49
INDEX USER MANUAL – XSI-B-230V-5K RECHARGE TABLES IMPORTANT: The value of the recharge current from the AC and Solar charger is adjustable. It is recommended that the total recharge current (AC + Solar) never exceed 20% of the AH capacity of the battery bank (0.2C). For example, for a 100AH battery bank, a maximum total recharge current of 20A is recommended (100AH * 0.2).
Page 50
INDEX USER MANUAL – XSI-B-230V-5K ANNEX 3. BATTERY CHARGER XMART XSI-B-230V inverters come with 2 powerful internal battery chargers. First one is connected to the AC input, while second one is connected to solar input. Both can recharge batteries either simultaneously or separately, depending on the configuration of the inverter. CHARGERS SETTINGS: Chargers used by this inverter are of modern technology and can be configured to limit maximum recharge current according to the capacity of the battery bank connected to the inverter.
Page 51
INDEX USER MANUAL – XSI-B-230V-5K ANNEX 4. PARALLEL CONNECTION PARALLEL OPERATION This unit can operate in parallel to increase capacity or to provide redundancy and more reliability to the power supply of your installation. The maximum number of units that can be installed in parallel is 9, so the maximum capacity that can be achieved in a parallel system is 54KW/54KW.
Page 52
INDEX USER MANUAL – XSI-B-230V-5K 2. As shown in the figure on the right, remove the two screws to take out the identified board. Remove the 2 cables from the board, one with 2 pins and the other with 14 pins. 3.
Page 53
INDEX USER MANUAL – XSI-B-230V-5K MOUNTING THE UNITS Proceed to install the units (up to 9, maximum), placing them close to each other while maintaining the distances indicated in section 5. Installation of this manual, as shown in the following figure. This will ensure the necessary space for good ventilation of the units and heat dissipation.
Page 54
INDEX USER MANUAL – XSI-B-230V-5K CONNECTIONS: For connections and cable selection, follow the instructions in Chapter 5. INSTALLATION of this manual. AC LINES: AC inputs must be connected in parallel to each inverter. The same should be done with the AC outputs. It is recommended to use a circuit breaker and magnetic-thermal protector on the input and output phases of each inverter.
Page 55
INDEX USER MANUAL – XSI-B-230V-5K Therefore, the communication and shared current cables must connect the respective ports of all units operating in parallel, maintaining the order shown in the following figures, according to the number of units to be installed in parallel. As shown in the following figures: SINGLE-PHASE INSTALLATIONS www.xmart-ups.com VER.2405.14- (ESP)
Page 56
INDEX USER MANUAL – XSI-B-230V-5K www.xmart-ups.com VER.2405.14- (ESP)
Page 57
INDEX USER MANUAL – XSI-B-230V-5K THREE-PHASE INSTALLATIONS Arrangement for 3 Inverters Inverters in Phase #1: 1 Inverters in Phase #2: 1 Inverters in Phase #3: 1 Electrical Connections Control Cables Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units.
Page 58
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 4 Inverters Inverters in Phase #1: 2 Inverters in Phase #2: 1 Inverters in Phase #3: 1 Electrical Connections Control Cables Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units.
Page 59
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 5 Inverters Inverters in Phase #1: 2 Inverters in Phase #2: 2 Inverters in Phase #3: 1 Electrical Connections Control Cables Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units.
Page 60
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 5 Inverters Inverters in Phase #1: 3 Inverters in Phase #2: 1 Inverters in Phase #3: 1 Electrical Connections Control Cables Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units.
Page 61
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 6 Inverters Inverters in Phase #1: 3 Inverters in Phase #2: 2 Inverters in Phase #3: 1 Conexión Eléctrica Cables de Control Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units. www.xmart-ups.com VER.2405.14- (ESP)
Page 62
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 6 Inverters Inverters in Phase #1: 4 Inverters in Phase #2: 1 Inverters in Phase #3: 1 Conexión Eléctrica Cables de Control Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units. www.xmart-ups.com VER.2405.14- (ESP)
Page 63
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 6 Inverters Inverters in Phase #1: 2 Inverters in Phase #2: 2 Inverters in Phase #3: 2 Conexión Eléctrica Cables de Control Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units. www.xmart-ups.com VER.2405.14- (ESP)
Page 64
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 9 Inverters Inverters in Phase #1: 3 Inverters in Phase #2: 3 Inverters in Phase #3: 3 Conexión Eléctrica Cables de Control Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units. www.xmart-ups.com VER.2405.14- (ESP)
Page 65
INDEX USER MANUAL – XSI-B-230V-5K Arrangement for 9 Inverters Inverters in Phase #1: 7 Inverters in Phase #2: 1 Inverters in Phase #3: 1 Conexión Eléctrica Cables de Control Note: Do not connect the shared current cables between inverters powered by different phases. Doing so can damage the units. www.xmart-ups.com VER.2405.14- (ESP)
Page 66
INDEX USER MANUAL – XSI-B-230V-5K LCD AND CONFIGURATION: To ensure proper operation of your inverters in parallel, they must be correctly configured. To do this, you should set the inverter to "Standby" mode and set parameters 28 and 30, as shown in the following table: OPERATION MODE: SINGLE / PARALLEL SIG: Mode for single inverter operation.
Page 67
INDEX USER MANUAL – XSI-B-230V-5K FAULT CODES The following error messages are available when the units operate in parallel: FAULT DESCRIPTION FAULT CODE FAULT ICON Electrical feedback protection Inconsistent internal firmware version Shared current failure CAN data loss Loss of internal network server Loss of synchronization Difference in battery voltage between inverters Voltage and/or frequency differences between AC input phases of the equipment.
Page 68
INDEX USER MANUAL – XSI-B-230V-5K Master Unit Screen Master Unit Screen If everything is correct and there are no alarm indications, the parallel system is fully operational. Proceed to connect (turn on) the circuit breakers of the output lines of all units so that the system starts supplying power to the installation.
Page 69
INDEX USER MANUAL – XSI-B-230V-5K TROUBLESHOOTING SITUATION PROBABLE CAUSE & SOLUTION 1. Restart the inverter. 2. Check the polarity of the Phases (L1, L2, & L3) and Neutral cables. 3. Ensure that the shared current and communication cables are properly Code 60 connected to all inverters in single-phase installations.
Page 70
INDEX USER MANUAL – XSI-B-230V-5K ANNEX 5. BMS COMMUNICATION When using lithium batteries, it is recommended to install an RJ-45 BMS communication cable (not supplied with this inverter) that allows information and signals transmission between battery bank and the inverter. Consult your battery supplier for the availability of the cable. Communication with the battery bank allows: •...
Page 71
INDEX USER MANUAL – XSI-B-230V-5K LCD SCREEN INFORMATION As explained in section 8. START-UP, pressing keys will sequentially display screens with the inverter's operational information. Once communication with the batteries has been successfully established, a screen like the one in the following figure will be displayed just before the main CPU Firmware Version screen to indicate the number of battery packs and groups connected to the inverter.
Page 72
INDEX USER MANUAL – XSI-B-230V-5K ANNEX 6: XMART LiFePO4 BATTERIES. SETTING INTRODUCTION TO XMART LiFePO4 BATTERIES These batteries belong to the Lithium-Ion battery group, specifically the LiFePO4 type (Lithium Iron Phosphate, LFP). They are the safest type of Lithium batteries, provided that all safety, storage, and operation regulations are followed to avoid overheating, fire, and/or explosions.
Page 73
INDEX USER MANUAL – XSI-B-230V-5K Environment Temperature Maximum Charging Current (where the battery is located) for each series battery group Between -20ºC & 0ºC Charging NOT allowed Between 0ºC & 10ºC 0.10C (10A) Between 10ºC & 15ºC 0.20C (20A) Between 15ºC & 20ºC 0.50C (50A) Between 20ºC &...
Page 74
INDEX USER MANUAL – XSI-B-230V-5K WARRANTY & SUPPORT Support: If a failure or problem is detected please check troubleshooting section in user manual. If problem cannot be solved, please contact authorized service center or authorized dealer. Batteries: Rechargeable batteries can be charged and discharged hundreds of times. However, they will eventually wear out. This is not a defect or failure so that batteries wear out is not covered by this warranty.
Page 76