Any disposition, duplication, dissemination, reproduction, modification, translation, extraction, or usage of this Manual in whole or in part is prohibited without the prior written permission of Para Systems. Given that Para Systems will continuously improve and develop the product, changes may be made to the information in this Manual at any time without obligation to notify any person of such revision or changes.
1. Important Safety Warnings SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be followed during the installation and maintenance of the Battery Pack and the batteries. CAUTION! The maximum ambient operating temperature for this Battery Pack series is 40°C. CAUTION! The external vents and openings on the Battery Pack are provided for ventilation.
Page 4
2. Installation and Operation This Battery pack is ONLY intended to be installed in an indoor temperature-controlled environment that is free of conductive contaminants. DO NOT operate the Battery Pack in: extremely dusty and/or unclean areas, locations near heating devices, water, or excessive humidity, or where the Battery Pack is exposed to direct sunlight. Select a location, which will always provide good air circulation for the Battery Pack.
Page 5
2-2 Installation Be sure to read the installation and all the cautions before installing the Battery Pack. Place the Battery Pack in the final desired location and complete the rest of the installation procedure. 2-3 Rear Panel 1. External battery connector: connects to either UPS or 2 Battery Pack 2.
3. Replacing the Battery QUALIFIED SERVICE PERSONNEL ONLY Please read all the WARNINGS and CAUTIONS before attempting to service the batteries. Typical battery life is 3 to 5 years. Environmental factors do affect battery life. High temperatures, poor utility power, and frequent, short duration discharges have a negative impact on battery life.
BATTERY REPLACEMENT PROCEDURE (QUALIFIED SERVICE PERSONNEL ONLY) PLEASE READ THE CAUTIONS AND WARNINGS BEFORE ATTEMPTING TO REPLACE THE BATTERIES Hot-swappable batteries mean that the batteries can be replaced without powering down the whole UPS system. NOTE: If there is a power interruption while replacing the hot-swappable batteries, with the UPS on, the load will not be backed up.
Page 8
28. Re-install the cover. 29. Re-install the cover screws. 30. Reconnect all the external battery cables. 31. Turn on all the DC circuit breakers on the rear panel of all the Battery Packs. 32. Turn on the input breaker on the rear panel of the UPS to start the UPS in the Bypass mode. 33.
7. Specifications MODEL BP240TWR OUTPUT Output 240VDC / 50Amps BATTERY Type Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid Typical Recharge Time 9-hours to 90% after a full load discharge Quantity / Rating 40 - 12V/9Ah Charging Current 1 Amp ± 10% (max.) Charging Voltage 273 VDC ±...