  • Page 1: Table Of Contents

    THE WORLD LEADER IN CLEAN AIR SOLUTIONS AstroPure™ 600N Index Safety Precautions Important Notes Introduction 1.1 About this Document 1.2 Product Overview 1.3 Product Component Principle of Operation 2.1 Unit Airflow Direction 2.2 Application Installation 3.1 Standard Packing List 3.2 Pressure Gauge 3.3 Housing Installation 3.4 Filter Installation 3.5 Controller Wiring &...
  • Page 2: Safety Precautions

    Safety Precautions Please familiarize with safety alert symbol show in this manual before using your AAF equipment. Attention Wear Mask Pay extra attention To protect from hazardous dust inhalation Wear Gloves High Voltage Warning Prevent injury from sharp edges and cuts...
  • Page 3 ▪ During use • Do not use chlorinated or acidic detergents. (Injury may result from the degradation or cracking of plastic, or harm may be caused to health from the production of toxic gases) • Keep burning cigarattes or incense sticks away from the unit. (Fire or smoke may result from ignition or suction toward the unit) •...
  • Page 4: Important Notes

    Important Notes Air quality is a key factor in maintaining the comfort and health of building occupants, optimizing production processes and reducing the environmental impact. Therefore, it is necessary to perform filters change-out when they are no longer functioning properly or at an optimum point to maintain desired level of filtration at minimum cost.
  • Page 5: Introduction

    1.0 Introduction 1.1 About this Document This document contains the information necessary to properly install, operate and maintain the AAF AstroPure™ 600N. The purchaser, installer and operator of this equipment MUST read and comply with this document in its entirety prior to installation of the equipment and its operation. Failure to comply with the requirements of this manual may void the equipment warranty.
  • Page 6: Product Component

    1.3 Product Components 1. Pre-filter 6. Door latches 11. Pressure ports 2. Secondary filter (Optional) 7. HEPA filter locking mechanism 12. Side access door 3. HEPA filter 8. UV light (UV model only) 13. Collar 4. Detachable hinges 9. Fan motor 14.
  • Page 7: Application

    2.2 Application AstroPure™ 600N is designed as a multi-application air purifier, it can be used to improve the air quality of the recirculation air by reducing PM2.5, bacteria, and virus carried by building occupants entering the room. It is also recommended for Negative Pressure rooms to clean exhaust/contaminated air before releasing it to the environment.
  • Page 8: Housing Installation

    3.3 Housing Installation 1. Housing installation and commissioning should be handled by at least 2 trained and qualified personnel. 2. There are two recommended methods of installation. B) 4x hanging bracket at side of the housing. (Use for M6/M8 threaded rod with nut) (820x335) mm 3.
  • Page 9 Step 1 Open the door latches as per shown in figure above, to open the filter access door. The access door can be taken out by sliding to the right from the detachable hinge. Pull out the used filters and placed them in a trash bag and seal up immediately. *The HEPA filter can be pulled out using the straps attached on the HEPA filter.
  • Page 10: Controller Wiring & Manual

    3.5 Controller Wiring & Manual AstroPure™ 600N AstroPure™ 600N UV Controller Components Functions AstroPure™ 600N Potentiometer To increase (Clockwise) or reduce (Anticlockwise) the fan speed. Rated airflow of 670 CMH is achieved when the fan speed is set at 100% on the potentiometer. AstroPure™...
  • Page 11: Start-Up Instructions

    Monitor the pressure drop across the filter system to ensure that the filters are operating within the pressure range expected and to ensure that the pressure drop is not too high. Consult the AAF personnel for the expected clean filter pressure differentials.
  • Page 12: Spare Parts List

    6.0 Spare Parts List Components EC fan ZWW92C-AC1-A06 Potentiometer knob 999-3220-018 EPDM gasket for access door 915-001-658 Door latch 915-020-156 Door detachable hinge 916-400-269 UV light 9W UV light holder 916-401-005 UV light ballast 999-299-178 Limit switch 999-3220-020 7.0 Equipment Dimension and Weight 7.1 Specification Airflow 80-670 m...
  • Page 13: Wiring Diagram

    8.0 Wiring Diagram AstroPure™ 600N AstroPure™ 600N UV...
  • Page 14 (This page is left blank intentionally)
  • Page 15 (This page is left blank intentionally)
  • Page 16 Asia Sales Office American Air Filter Manufacturing Sdn. Bhd. (HQ – Malaysia) Tel : +60 3 5039 7777 AAF has a policy of continuous product research and (Penang – Malaysia) Tel : +60 4638 4100 improvement and reserves the right to change AAF Australia Pty.