Block Diagram - CyberPower Professional Rack Mount UPS 2200VA User Manual

Professional rack mount ups

Advertisement

BATTERY REPLACEMENT AND STORAGE
CAUTION! Read and follow the IMPORTANT SAFETY INSTRUCTIONS before servicing the battery.
Service the battery under the supervision of personnel knowledgeable of batteries and their
precautions. Keep unauthorized personnel away from batteries. If you have questions, contact
your dealer or call the number in this manual for information on battery replacement.
CAUTION! Use only the specified type of battery. See your dealer for replacement batteries.
CAUTION! The battery may present the risk of electrical shock. Do not dispose of batteries in a
fire, as it may explode. Follow all local ordinances regarding proper disposal of batteries.
CAUTION! Do not open or mutilate the batteries. Release electrolyte is harmful to the skin and eyes
and may be toxic.
CAUTION! A battery can present a high risk of short circuit current and electrical shock. Take the
following precautions before replacing the battery:
1. Remove all watches, rings or other metal objects.
2. Only use tools with insulated handles.
3. DO NOT lay tools or other metal parts on top of battery or any battery terminals.
4. Determine if the battery is inadvertently grounded. If inadvertently grounded, remove source of
ground. CONTACT WITH A GROUNDED BATTERY CAN RESULT IN ELECTRICAL SHOCK!
The likelihood of such shock will be reduced if such grounds are removed during installation
and maintenance (applicable to a UPS and a remote battery supply not having a grounded
circuit).
5. Batteries are consider HAZARDOUS WASTE and must be disposed of properly. Contact your
local government for more information about proper disposal and recycling of batteries.
6. Turn off and unplug all connected equipment.
7. Turn the UPS off and unplug it from the AC power source.
BATTERY REPLACEMENT PROCEDURE:
STORAGE
First turn off your UPS and disconnect its power cord from the wall outlet. Disconnect all cables
connected to the UPS to avoid battery drain. To store your UPS for an extended period, cover it and
store with the battery fully charged. Recharge the battery every three months to insure battery life. If
the battery remains uncharged for an extended period of time, it may suffer permanent loss of
capacity.

Block Diagram

AVR Switch
Input
Battery
Battery
Charger
1. Remove the right side front panel.
2. Remove the two retaining screws of the
cable protection cover then remove the
cover.
3. Disconnect the black and red cable.
4. Remove the four retaining screws.
5. Pull the battery pack out from the unit.
6. Slide a new battery pack into the unit.
Assemble the screws, cover, cable and
front panel in the reverse sequence of
above steps.
REMINDER: Recharge the unit for 4 – 8
hours to ensure the UPS performs expected
runtime.
Transformer
Output
Inverter
(DC/AC)
TROUBLE SHOOTING
Problem
Possible Cause
Batteries are not fully charged.
The UPS does not
perform expected
runtime.
Battery is slightly worn out.
The on/off switch is designed to
prevent damage by rapidly
turning it off and on.
The UPS will not
The unit is not connected to an
AC outlet.
turn on.
The battery is worn out.
Mechanical problem.
Circuit breaker is tripped due to
overload.
Outlets do not
provide power to
Batteries are discharged
equipment
Unit has been damaged by a
surge or spike.
The serial/USB cable is not
connected.
The serial/USB cable is
PowerPanel
connected to the wrong port.
Business Edition
or PowerPanel is
The unit is not providing battery
inactive (all icons
power.
are gray).
The serial cable is not the cable
that was provided with the unit.
TECHNICAL SPECIFICATIONS
Model
Capacity (VA)
Capacity (Watts)
Input
Input Voltage Range
Frequency Range
O
u
p t
t u
On Battery Output Voltage
On Battery Output Frequency
Overload Protection
On Utility: Circuit Breaker, On Battery: internal current limiting
Surge Protection and Filtering
Lightning / Surge Protection
Network Protection
Physical
Total # of UPS Receptacles
Maximum Dimensions
Weight (Kg)
Battery
Sealed Maintenance Free Lead Acid
Battery
User Replaceable
Typical Recharge Time
Warning Diagnostics
Indicators
Audible Alarms
Environmental
Operating Temperature
Operating Relative Humidity
Communication
PowerPanel
Business edition
Software
Management
Auto-Charger
Auto-Restart
USB
SNMP/HTTP network function
DEFINITIONS FOR ILLUMINATED LED INDICATORS
Power
Circuit
Using
AVR
Breaker Alarm
On
Battery
On
Off
Off
Set
Off
Slow
On
Off
Set
Off
flash
Rapid
On
Off
Set
Off
flash
ON
On
Off
Set
Off
Two
Off
Off
On
Set
Beeps
Rapid
Off
Off
On
Set
Beeps
On/ Off
Long
On/Off
On/Off
Set
/Flash
Beep
Long
Off
Off
On
Up
Beep
Off
Off
Off
Set
Off
For more information, visit eu.cyberpowersystems.com or contact
CyberPower Systems B.V. Flight Forum 3545,5657DW Eindhoven,The Netherlands
Tel: + 31(0)40 2348170, Fax : + 31(0)40 2340314, E-MAIL: sales@cyberpower-eu.com
CyberPower Systems Inc. (USA) 4241 12th Avenue East Suite 400 Shakopee, MN 55379 ,
U.S.A.
Tel: +1 952 4039500, Fax: +1 952 4030009, E-MAIL: sales@cyberpowersystems.com
Entire contents copyright ©2004 CyberPower Systems B.V., All rights reserved.
Reproduction in whole or in part without permission is prohibited.
PowerPanel and PowerPanel Plus are trademarks of CyberPower Systems (USA) Inc.
CyberPower warrants to you, the original purchaser, that CyberPower UPS will be free from defects in design,
assembly, materials and workmanship for two years ( battery is only one year) from the date of original purchase.
Any warranty services, please contact your local dealers or distributors.
Solution
Recharge the battery by leaving the UPS plugged
in.
Contact Cyber Power Systems at
service@cyberpower-eu.com
Turn the UPS off. Wait 10 seconds and then turn
the UPS on.
The unit must be connected to a 220-240V
50/60Hz outlet.
Contact Cyber Power Systems at
service@cyberpower-eu.com
Contact Cyber Power Systems at
service@cyberpower-eu.com
Turn the UPS off and unplug at least one piece of
equipment. Wait 10 seconds, reset the circuit
breaker and then turn the UPS on.
Allow the unit to recharge for at least 4 hours.
Contact Cyber Power Systems at
service@cyberpower-eu.com
Connect the serial/USB cable to the UPS unit and
an open serial port on the back of the computer.
You must use the cable that came with the unit.
Try another serial/USB port of your computer.
Shut down your computer and turn the UPS off.
Wait 10 seconds and turn the UPS back on. This
should reset the unit.
You must use the cable included with the unit for
the software.
PR1500E
PR2200E
1500VA
2200VA
1000W
1600W
220-240Vac
50/60 Hz
Pure Sine Wave at 230Vac +/- 7%
50/60 Hz
Yes
RJ45 (One In/One Out)
6
43.3cm*8.8cm*38.8cm
26.4
32.1
12V / 7AHx4
12V / 9AHx4
Yes, Hot Swappable Battery Pack
8 Hours
Power On, Using Battery, AVR, Load Level, Battery Level
On Battery, Low Battery, Overload, Self-test
+32°F to 95°F ( 0°C to 35°C )
0 to 95% NON-CONDENSING
Windows 98/ME/2000/NT/XP, Server 2003
Yes
Yes
Yes
Optional
Condition
Normal
AVR- Max. boost 13% of input voltage for output
regulation while input voltage is from 8% to 15% under
nominal.
AVR- Max. boost 26% of input voltage for output
regulation while input voltage is from 15% to 26% under
nominal.
AVR- Max. buck 11% of input voltage for output regulation
while input voltage is from 8% to 26% over nominal.
Utility Failure- The UPS is providing battery power to the
outlets.
Utility Failure- The UPS is providing battery power.
Rapid beeps indicate the battery will run out of charge
within a few minutes.
Overload- Please turn the UPS off and unplug at least one
piece of equipment from the UPS. Wait 5 seconds, reset
the circuit breaker and restart the UPS.
Overload- Please turn the UPS off and unplug at least one
piece of equipment from the UPS. Wait 5 seconds, reset
the circuit breaker and restart the UPS.
Surge Protection Malfunction- Power surge has
damaged the unit. Please contact CyberPower Systems.