Installing the PRT1-SCU11 PROFIBUS DP Gateway
2-2
Installing the PRT1-SCU11 PROFIBUS DP Gateway
2-2-1
Handling Precautions
2-2-2
Mounting the PRT1-SCU11
Mounting Procedure
! C a u t i o n
1,2,3...
2-2-3
Wiring the Power Terminals
When installing the PROFIBUS DP Gateway, observe the following handling
precautions
• Always turn OFF the power supply to the Unit before mounting or dis-
mounting the Unit or connecting or disconnecting cables.
• Provide separate conduits or ducts for the I/O lines to prevent noise from
high-tension lines or power lines.
• Prevent foreign matters to enter the Unit when wiring. Failure to do so,
may result in malfunction if foreign matter enters the Unit.
The PRT1-SCU11 can be mounted directly on a DIN-rail.
Mount the PRT1-SCU11 to the DIN-rail using the following procedure.
Always turn OFF the power supply to the Unit before mounting or dismounting
the Unit or connecting or disconnecting cables.
1. Pull the hook down on the bottom.
2. Latch the top hook onto the track
3. Push the Unit until the hook locks onto the track.
4. Push the hook back up to lock the Unit in place.
1) Pull down.
• Supply power to the Unit using the 2 pin power connector provided with
the Unit.
• When wiring the power, observe the required polarity. Failure to do so can
damage the Unit.
• Use a Phillips screw driver to tighten the connector screw, using a torque
value between 0.25 and 0.3 N·m.
2) Insert
onto track.
3) Push in on
the Unit.
Section 2-2
4) Lock
23