3-7 Installing the Video Input Unit
A Video Input Unit (NS-CA001 or NS-CA002) can be mounted to an NS-series PT. Mounting
a Video Input Unit allows images from a video camera or vision sensor to be displayed on
the PT screen. This section explains how to connect a Video Input Unit to the PT with a cable
using the NS-CA001 as an example.
A Video Input Unit can be connected to the NS8, NS10, NS12 or NS15 (except that the NS-
CA001 cannot be connected to the NS15. Also, the NS15 does not support video input from
the NS-CA002, but it does support analog RGB input from the NS-CA002). A Video Input
Unit cannot be connected to the NS5.
Reference
3-7-1
Video Input Unit Components
The following table shows the Video Input Unit's product configuration.
Model
NS-CA001
Video Input Unit
Precautions
for Safe Use
Refer to the NS Series RGB and Video Input Unit Operation Manual (Cat. No. V086)
for information on NS-CA002 installation methods.
Name
Video Board (1)
Cover (1)
Cable (1)
Screw (M3) (9)
Instruction sheet
To comply with EC Directives when mounting the Video Input Unit on the PT,
attach the PT to a control panel that has been cut to fit the size. (Refer to 3-1-3
Mounting the PT to the Control Panel for panel cutout dimensions.)
Components
Contents
Allows video input.
Protects Video Board.
Connects the PT's functional
ground terminal and the cover to
prevent noise.
These screws are used for the
following:
• Securing the Video Board to
the back of the PT.
• Securing the cover to the back
of the PT.
• Attaching the cable to the
cover.