Connect [Power +] and [Power –] terminals to 12-24VDC power source UL listed for the application (TowerIQ Guardian BBU or similar). 400mA are required. Use [+ AUX –] terminals of Guardian BBU. Carefully observe polarity, damage may occur.
Page 3
power-limited Fig 1 AC Fail Charger Low Bat AC Power Fail AC Power Low Battery(<30%) Chrgr Charging Circuit Battery Low Component Fail CMP Fail Ground Fault RF Emitter Charger Fail Component Donor Antenna Disconnect GND Fault Ground Donor Antenna Malfunction Comm Fault Sys Cmpnt Fail...
Page 4
GUARDIAN ANNUNCIATOR LED DIAGNOSTICS: Decription AC Power Fail Green: AC power normal, Red: AC power failure or brownout. Battery Low Green: Battery normal. Red: Battery is missing or discharged below 30% capacity. Charger Fail Green: Charger operates normally. Red: Charger failure. Green: No critical component failure detected.
Page 5
GUARDIAN ANNUNCIATOR TERMINAL IDENTIFICATION OUTPUTS: Terminal Legend Function/Description AC Fail Form”C” relay output. 1A/28V, 0.6 power factor. EOL C NC NO Relay is normally energized. Reports AC failure to FACP (Fig. 1m, pg. 3) Batt Fail Form”C” relay output. 1A/28V, 0.6 power factor. EOL C NC NO Relay is normally energized.
Page 6
TOWERIQ GUARDIAN ANNUNCIATOR CONNECTIONS TO THE GUARDIAN BBU POWER SUPPLY: See Guardian BBU Power Supply Installation Guide 5403500 Rev. A for more information. Use [AUX +/–] terminals of Guardian BBU power supply to connect to power terminals of Guardian Annunciator. Any other 12-24V UL listed UL864 compliant power source can be used.